What is 3.6/6kV Cable?

Complete Technical Encyclopedia of Medium Voltage Power Cables — IEC 60502-2, German VDE, Portuguese Nomenclature & International Standards

3.6/6kV cable, 6kV cable, 6kV power cable, medium voltage cable, MV cable, IEC 60502-2, XLPE cable 6kV, 6kV XLPE insulated cable, medium voltage power cable, 6kV distribution cable
What is 3.6/6kV Cable? Complete Technical Guide | Anhui Feichun Special Cable Co., Ltd.

Anhui Feichun Special Cable Co., Ltd.

安徽飞纯特种电缆有限公司

What is 3.6/6kV Cable?

Complete Technical Encyclopedia of Medium Voltage Power Cables — IEC 60502-2, German VDE, Portuguese Nomenclature & International Standards

⚡ 3.6/6(7.2)kV 📋 IEC 60502-2 🔧 VDE 0276 🌡️ XLPE 90°C ⛏️ Mining Applications

1. Introduction to 3.6/6kV Medium Voltage Cables

Cables with a rated voltage of 3.6/6kV under IEC 60502-2 represent the entry point into Medium Voltage (MV) power distribution systems. These cables are generally specified for equipment connections, power distribution networks, transformer stations, and industrial applications requiring voltages above low voltage (1kV) but below high voltage transmission levels.

3.6/6kV Voltage Rating Explained

U₀ (Phase to Earth)

3.6 kV
Rated voltage to ground

U (Phase to Phase)

6 kV
Rated voltage between phases

Um (Maximum System)

7.2 kV
Highest system voltage

Test Voltage

12.6 kV
AC withstand test (routine)

Source: Eland Cables – IEC 60502 Cable Standard

Like other Medium Voltage cables, 3.6/6kV cables are available in both armoured and unarmoured constructions, and with a range of outer sheathing materials across MDPE, PVC and LSZH materials depending on the application demands and installation parameters. IEC 60502-2 specifies the construction, dimensions, and test requirements of power cables with extruded solid insulation for rated voltages from 6 kV (Um = 7.2 kV) up to 30 kV (Um = 36 kV).

Source: Tratos Group – IEC 60502 Standard

EspañolIntroducción a los Cables de Media Tensión 3.6/6kV

Los cables con tensión nominal de 3.6/6kV según IEC 60502-2 representan el punto de entrada a los sistemas de distribución de Media Tensión (MT). Estos cables se especifican generalmente para conexiones de equipos, redes de distribución de energía, estaciones transformadoras y aplicaciones industriales que requieren tensiones superiores a baja tensión (1kV). La designación 3.6/6(7.2)kV indica: U₀ = 3.6kV (tensión fase-tierra), U = 6kV (tensión fase-fase), Um = 7.2kV (tensión máxima del sistema). Están disponibles en construcciones armadas y sin armar, con materiales de cubierta exterior que incluyen MDPE, PVC y LSZH.

繁體中文3.6/6kV 中壓電纜簡介

按照IEC 60502-2標準,額定電壓為3.6/6kV的電纜代表中壓(MV)配電系統的入門級別。這些電纜通常用於設備連接、配電網絡、變壓站和需要高於低壓(1kV)的工業應用。電壓標示3.6/6(7.2)kV表示:U₀ = 3.6kV(相對地電壓)、U = 6kV(相間電壓)、Um = 7.2kV(最高系統電壓)。電纜有鎧裝和非鎧裝結構可選,外護套材料包括MDPE、PVC和LSZH,可根據應用需求和安裝參數選擇。IEC 60502-2規定了額定電壓6kV至30kV擠出固體絕緣電力電纜的結構、尺寸和測試要求。

2. IEC 60502-2 Standard Requirements

International Standard IEC 60502-2, prepared by IEC Technical Committee 20: Electric Cables, specifies the construction, dimensions, and test requirements of power cables with extruded solid insulation for rated voltages from 6 kV up to 30 kV for fixed installations such as distribution networks or industrial installations.

Voltage Ratings Covered by IEC 60502-2

Voltage Rating U₀/UMaximum UmTest Voltage (AC)Impulse Test (kV)
3.6/6 kV7.2 kV12.6 kV40 kV
6/10 kV12 kV21 kV60 kV
8.7/15 kV17.5 kV30 kV75 kV
12/20 kV24 kV42 kV95 kV
18/30 kV36 kV63 kV125 kV

Insulation Types and Temperature Ratings

Insulation TypeOperating TempEmergency OverloadShort Circuit (5s)For 3.6/6kV
XLPE Cross-linked Polyethylene90°C130°C250°CYes (Preferred)
EPR Ethylene Propylene Rubber90°C130°C250°CYes
HEPR Hard Ethylene Propylene Rubber90°C130°C250°CYes
PVC/B Polyvinyl Chloride Type B70°C100°C160°CYes (3.6/6kV only)

Insulation Thickness for 3.6/6kV Cables

Insulation MaterialNominal ThicknessConductor Size Range
XLPE or EPR/HEPR3.4 mm10 – 1600 mm²
PVC/B (3.6/6kV only)3.4 mm10 – 1600 mm²

Source: Addison Cables – IEC 60502 Medium Voltage Cables

Conductor and Screening Requirements

Types of conductors include Class 1 (solid) or Class 2 (stranded) of plain or metal-coated annealed copper, plain aluminium or aluminium alloy in accordance with IEC 60228. The conductor size range includes 10mm² up to and including 1600mm². EPR and HEPR (3.6/6kV) cables may be unscreened providing an increased radial thickness of insulation is used. All other cables must contain a semiconducting conductor screen and a semiconducting insulation screen plus a metallic layer surrounding the cores.

Screening Requirements for 3.6/6kV Cables

Conductor Screen: Extruded layer of non-metallic, semi-conducting compound firmly bonded to the insulation. The conductor screen is optional for PVC and EPR/HEPR insulated 3.6/6kV cables.

Insulation Screen: Extruded layer of semi-conducting compound (minimum 0.3mm thickness, maximum resistivity 500 Ohm-m at 90°C) tightly fitted to the insulation. Optional for PVC and EPR/HEPR insulated 3.6/6kV cables.

Metallic Screen: Copper tapes, copper wires, or combination providing earth fault current path. Cross-sectional area determined by fault level requirements.

Source: Caledonian Cables – Medium Voltage Cables to IEC 60502

3. International Cable Nomenclature Systems

3.6/6kV cables are manufactured worldwide using various national naming conventions. Understanding these nomenclatures is essential for international cable specification and procurement. The same construction may be referenced differently depending on the country of origin or destination market.

German VDE Nomenclature

🇩🇪 German Standard (DIN VDE 0276)

Cable CodeConductorInsulationScreenSheath
N2XSYCopperXLPECu wire + tapePVC (red)
NA2XSYAluminiumXLPECu wire + tapePVC (red)
N2XS2YCopperXLPECu wire + tapePE (black)
NYFGYCopperPVC—PVC + Steel armour
N2XSEYCopperXLPEEach core screenedPVC

Source: Eland Cables – DIN VDE 0276 Cable

German Cable Designation Key

LetterPositionMeaning
N1stEnergy cable (Copper conductor)
NA1stEnergy cable (Aluminium conductor)
2XInsulationXLPE (Cross-linked Polyethylene)
YInsulationPVC (Polyvinyl Chloride)
SScreenCopper wire screen
SEScreenEach core individually screened
(FL)Water blockingLongitudinal + radial water blocking
2YSheathPE outer sheath
FGArmourFlat steel wire armour

Source: Eland Cables – N2XSY Cable

Portuguese Nomenclature

🇵🇹 Portuguese Standard (IEC 60502-2 / HD620)

Cable CodeConductorScreen TypeArmourSheath
XHIVX = CopperCu tape—PVC (V)
LXHIVLX = AluminiumCu tape—PVC (V)
XHIEX = CopperCu tape—PE (E)
XHIOVX = CopperCu wire (O)—PVC (V)
XHIRVX = CopperCu tapeSWA (R)PVC (V)
XHIAVX = CopperCu tapeSTA (A)PVC (V)
XHI1AVX = CopperCu tapeATA (1A)PVC (V)

Source: Eland Cables – XHIV & LXHIV Cables

Portuguese Cable Designation Key

CodeMeaningCodeMeaning
XCopper conductorVPVC sheath
LXAluminium conductorEPE sheath
HXLPE insulationRSteel wire armour (SWA)
ICu tape screenASteel tape armour (STA)
IOCu tape + wire screen1AAluminium tape armour (ATA)

Source: Eland Cables – XHIOV & LXHIOV Cables

4. Complete 3.6/6kV Cable Model Comparison

The following comprehensive table compares all major 3.6/6kV cable types available in the market, including German VDE, Portuguese, Italian, and mining cable designations.

Cable ModelStandardConductorInsulationScreenArmourApplication
German VDE Standard Cables
N2XSYVDE 0276-620CuXLPECu wire+tape—Power distribution, transformer stations
NA2XSYVDE 0276-620AlXLPECu wire+tape—Cost-effective distribution
NYFGYVDE 0271CuPVC—Flat steel wirePower plants, heavy industry
N2XS(FL)2YVDE 0276-620CuXLPEWater blocked—Wet locations, flooded ducts
Portuguese Standard Cables
XHIVIEC 60502-2CuXLPECu tape—Indoor/outdoor distribution
LXHIVIEC 60502-2AlXLPECu tape—Lightweight distribution
XHIOVIEC 60502-2CuXLPECu wire—Enhanced EMC protection
XHIRVIEC 60502-2CuXLPECu tapeSWADirect burial with protection
XHIAVIEC 60502-2CuXLPECu tapeSTAMechanical protection
Italian Standard Cables
FG7H1OARCEI 20-13CuHEPRCu wireSWAIndustrial, LSZH installations
Mining & Special Application Cables
(N)TSCGEWÖUMining specCuEPRCu braid—Mining trailing cables
(N)TSCGECEWÖUMining specCuEPRIndividual + overall—Mining with earth check
(N)3GHSSHCHMining specCuEPRScreened—Mining, halogen-free

5. 3.6/6kV Cable Construction Details

Medium voltage cables for 3.6/6kV applications require specific construction elements to ensure safe and reliable operation. The construction follows IEC 60502-2 requirements with variations depending on specific application needs.

Typical Cable Construction Layers

LayerMaterialFunctionRequirement
1. ConductorCu (Class 1/2) or Al (Class 2)Current carryingIEC 60228, 10-1600mm²
2. Conductor ScreenSemiconducting XLPEElectric field gradingOptional for 3.6/6kV PVC/EPR
3. InsulationXLPE / EPR / HEPR / PVCElectrical insulation3.4mm nominal thickness
4. Insulation ScreenSemiconducting compoundField uniformityMin 0.3mm, max 500 Ohm-m
5. Metallic ScreenCu wires + Cu tapeEarth fault pathSized per fault current
6. Water BlockingSwellable tape/powderPrevent water ingressOptional
7. Bedding/SeparatorPVC / PE / LSZHProtection under armourMin 1.2mm if no lead sheath
8. Armour (if required)Steel wire/tape, Al tapeMechanical protectionPer IEC 60502-2 Table 9/10
9. Outer SheathPVC / PE / LSZHEnvironmental protectionUV resistant for external

Conductor Specifications

Copper Conductor

Class 1/2
Solid or stranded, IEC 60228

Aluminium Conductor

Class 2
Stranded only, IEC 60228

Size Range

10 – 1600 mm²
Standard range

Compacted Stranding

Optional
Reduces overall diameter

EspañolConstrucción de Cables 3.6/6kV

Los cables de media tensión para aplicaciones de 3.6/6kV requieren elementos de construcción específicos según IEC 60502-2. Las capas incluyen: conductor (Cu Clase 1/2 o Al Clase 2, 10-1600mm²), pantalla del conductor (semiconductora, opcional para 3.6/6kV), aislamiento (XLPE/EPR/HEPR/PVC, 3.4mm nominal), pantalla de aislamiento (min 0.3mm), pantalla metálica (hilos + cinta de Cu), bloqueo de agua (opcional), separador (min 1.2mm), armadura (alambre/cinta de acero si se requiere), y cubierta exterior (PVC/PE/LSZH). El proceso de extrusión triple garantiza interfaces lisas entre pantalla del conductor, aislamiento y pantalla de aislamiento.

繁體中文3.6/6kV 電纜結構詳解

3.6/6kV應用的中壓電纜需要按照IEC 60502-2要求的特定結構元件。各層包括:導體(Cu 1/2類或Al 2類,10-1600mm²)、導體屏蔽(半導體,3.6/6kV可選)、絕緣(XLPE/EPR/HEPR/PVC,標稱3.4mm)、絕緣屏蔽(最小0.3mm)、金屬屏蔽(銅絲+銅帶)、阻水層(可選)、隔離層(最小1.2mm)、鎧裝(鋼絲/帶,如需要)、外護套(PVC/PE/LSZH)。三重擠出工藝確保導體屏蔽、絕緣和絕緣屏蔽之間的光滑界面,消除氣隙和電場集中。

6. Current Ratings for 3.6/6kV XLPE Cables

Current carrying capacity (ampacity) depends on conductor material, size, installation method, ambient temperature, and soil thermal resistivity. The following tables provide typical current ratings for 3.6/6kV XLPE insulated cables per IEC 60502-2 Annex B.

Single-Core Cables – Trefoil Formation in Ground

Conductor Size (mm²)Copper (A)Aluminium (A)DC Resistance Cu (Ω/km)DC Resistance Al (Ω/km)
251401100.7271.20
351701300.5240.868
502001550.3870.641
702451900.2680.443
952952300.1930.320
1203402650.1530.253
1503853000.1240.206
1854403400.09910.164
2405204050.07540.125
3005954650.06010.100
4006955450.04700.0778
5008006250.03660.0605

Reference conditions: Ground temperature 20°C, soil thermal resistivity 1.0 K·m/W, depth of laying 0.8m

Derating Factors

ConditionValueDerating Factor
Ambient Ground Temperature (Reference: 20°C)
Ground temperature15°C1.04
Ground temperature25°C0.96
Ground temperature30°C0.93
Ground temperature35°C0.89
Soil Thermal Resistivity (Reference: 1.0 K·m/W)
Soil thermal resistivity0.7 K·m/W (wet)1.10
Soil thermal resistivity1.5 K·m/W (dry)0.88
Soil thermal resistivity2.0 K·m/W (very dry)0.79
Depth of Laying (Reference: 0.8m)
Depth0.5m1.03
Depth1.0m0.98
Depth1.5m0.94

Source: IEC 60502-2 Annex B – Current Ratings

7. Applications for 3.6/6kV Cables

3.6/6kV cables serve a wide range of applications in power distribution and industrial settings. The specific cable type selected depends on installation environment, mechanical requirements, and regulatory compliance.

⚡ Power Distribution

Primary and secondary distribution networks, industrial power supply, commercial buildings, transformer station connections.

🏭 Industrial Plants

Motor feeders, switchgear connections, process equipment, manufacturing facilities, heavy machinery power supply.

⛏️ Mining Operations

Trailing cables for mobile equipment, longwall systems, shuttle cars, continuous miners, submersible pumps.

🌿 Renewable Energy

Solar farm collection circuits, wind turbine connections, battery storage systems, inverter connections.

🏗️ Construction Sites

Temporary power distribution, tower cranes, construction hoists, site lighting systems.

🚇 Infrastructure

Railway traction substations, tunnel ventilation, airport systems, port facilities, water treatment plants.

Installation Methods

Installation TypeCable Type RequiredKey Considerations
Direct burialArmoured (SWA/STA) or unarmoured with mechanical protectionSoil thermal resistivity, depth ≥0.8m under roads
Cable ducts/conduitsUnarmoured preferredDuct fill ratio, pulling tension limits
Cable traysUnarmoured or armouredSpacing, fire retardancy requirements
Outdoor exposedUV-resistant PE sheath (XHIE, N2XS2Y)UV protection, mechanical damage risk
Indoor installationsPVC sheath (XHIV, N2XSY) or LSZHFlame retardancy, smoke emission
Wet/flooded conditionsWater-blocked construction (FL type)Longitudinal and radial water sealing

8. Mining Cable Variants for 3.6/6kV

In addition to general equipment power connections, 6kV cables are commonly specified in mining equipment, where power cables with fibre optic, ground check conductors, and submersible variants are available. These mining cables often have a robust rubber outer sheath that offers flexibility and durability.

Cable ModelTypeFeaturesApplication
(N)TSCGEWÖUStandard trailingEPR insulated, rubber sheath, flexibleMobile mining equipment
(N)TSCGEWÖU FOFibre opticIntegrated optical fibres for dataAutomated equipment, monitoring
(N)TSCGECEWÖU ATBGround checkEarth check conductor for safetyLongwall systems, shuttle cars
(N)TSCGEWÖU SubmersibleSubmersibleWater resistant, suitable for pumpsMine dewatering pumps
(N)TSCGEWÖU ZHZero halogenLSZH sheath, reduced toxicityUnderground with ventilation concerns
(N)TMCGEWÖUHeavy dutyEnhanced mechanical protectionDraglines, shovels
Mining Cable Construction Features

Conductor: Tinned copper, Class 5 flexible stranding for repeated bending

Insulation: EPR (Ethylene Propylene Rubber) for flexibility and oil resistance

Screen: Copper braid or tape for EMC and fault current

Sheath: Heavy-duty rubber (CPE, EPR, or PCP) for abrasion and cut resistance

Temperature Range: -40°C to +90°C for harsh underground conditions

9. Feichun Cable 3.6/6kV Product Range

Anhui Feichun Special Cable Co., Ltd. (安徽飞纯特种电缆有限公司) manufactures a comprehensive range of 3.6/6kV medium voltage cables compliant with IEC 60502-2, German VDE 0276, and international standards for power distribution, industrial, and mining applications.

Product CategoryStandardsModels AvailableApplications
XLPE Power Cable (Cu)IEC 60502-2, VDE 0276N2XSY, XHIV, YJVPower distribution, transformer stations
XLPE Power Cable (Al)IEC 60502-2, VDE 0276NA2XSY, LXHIV, YJLVCost-effective distribution networks
Armoured MV CableIEC 60502-2XHIRV, XHIAV, N2XSRYDirect burial, mechanical protection
Mining Trailing CableMining specifications(N)TSCGEWÖU seriesMining equipment, mobile machinery
LSZH MV CableIEC 60502-2, IEC 60332N2XSH, LSZH variantsTunnels, buildings, confined spaces
Water-Blocked CableIEC 60502-2N2XS(FL)2Y, XHIOE(cbe)Wet locations, flooded ducts

Authoritative External References

The technical information in this article is supported by the following authoritative sources from standards organizations, industry publications, and recognized technical resources.

●
Eland Cables – IEC 60502 Standard
https://www.elandcables.com/…/iec-60502-cable
IEC 60502 standard overview and cable specifications
●
Tratos Group – IEC 60502
https://tratosgroup.com/products/standards/international/iec-60502/
Comprehensive IEC 60502-1 and IEC 60502-2 explanation
●
Eland Cables – N2XSY Cable
https://www.elandcables.com/cables/n2xsy-copper-conductor-cable
German VDE N2XSY cable specifications
●
Eland Cables – DIN VDE 0276
https://www.elandcables.com/…/vde0276-cable
German VDE 0276 medium voltage cable standard
●
Eland Cables – XHIV & LXHIV Cables
https://www.elandcables.com/cables/xhiv-lxhiv-cable
Portuguese nomenclature MV cables
●
Eland Cables – XHIOV & LXHIOV Cables
https://www.elandcables.com/cables/xhiov-lxhiov-cable
Portuguese copper wire screened MV cables
●
Eland Cables – NYFGY Cable
https://www.elandcables.com/cables/nyfgy-cables
German armoured MV cable specifications
●
Addison Cables – IEC 60502 MV Cables
https://www.addison-cables.com/…/single-core-cables-iec60502.html
Technical specifications for IEC 60502 cables
●
Caledonian Cables – MV Cables to IEC 60502
https://www.caledonian-cables.net/…/single-core-cables-iec60502.html
Medium voltage cable construction details
●
GUDA Cable – MV Cable Selection Guide
https://www.gudacable.com/medium-voltage-cable-selection-guide-6kv-36kv/
Comprehensive MV cable selection guidance

Contact Feichun Cable

For technical support with 3.6/6kV medium voltage cable requirements, specifications, or custom designs, please contact our engineering team.

📱
📧

Technical Support

[email protected]
👤

Sales – Mr. Zihao Yang

[email protected]
👤

Sales – Mr. Ziyu Huang

[email protected]

Company Address: Building A, Private Science and Technology Park, Hefei Economic and Technological Development Zone, Anhui Province, China

Anhui Feichun Special Cable Co., Ltd. | 安徽飞纯特种电缆有限公司

Professional Manufacturer of 3.6/6kV Medium Voltage Power Cables

© 2025 Feichun Cable. All rights reserved. | Technical content compiled from authoritative industry sources.

Previous Article

What is OGUK / UKOOA Cable?

Next Article

What is 1.9/3.3kV Cable?

Write a Comment

Leave a Comment

您的邮箱地址不会被公开。 必填项已用 * 标注