What is NEK 606 Cable?

Complete Technical Guide to Norwegian Offshore Oil & Gas Cable Standard — BFOU, RFOU, TFOU Power Cables, Instrumentation Cables, MUD Resistant, Fire Resistant, Halogen Free

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
What is NEK 606 Cable? Norwegian Offshore Oil & Gas Cable Standard Guide | Feichun Cable

Anhui Feichun Special Cable Co., Ltd.

安徽飞纯特种电缆有限公司

What is NEK 606 Cable?

Complete Technical Guide to Norwegian Offshore Oil & Gas Cable Standard — BFOU, RFOU, TFOU Power Cables, Instrumentation Cables, MUD Resistant, Fire Resistant, Halogen Free

🇳🇴 NEK TS 606:2022 🔥 Fire Resistant BFOU 🛢️ MUD Resistant ⚡ 0.6/1kV – 18/30kV 🏭 DNV Approved 🚢 Lloyd’s Register

1. Introduction to NEK 606 Standard

NEK TS 606 is the Norwegian offshore industry technical specification (TS) covering a range of power, instrumentation and earth cables that are halogen free and/or MUD resistant, protecting them against the type of hydrocarbon-laden drilling liquid used in drilling operations which can have an adverse effect on cable sheathing materials. Originally published in 1993 by the Norwegian Electrotechnical Committee (NEK) as a successor to the ‘Recommended Practice for Specification of Cables’ of the Norwegian Oil Industry Association, NEK 606 has evolved to become an internationally accepted standard for offshore cable applications.

The NEK 606 cable standard technical specification has been widely adopted in Europe and internationally with BFOU (fire resistant) and RFOU (flame retardant) cables, and UX Earth cables in common use. NEK 606 cables are designed to withstand the harsh and hazardous operating conditions of the global oil and gas industry, with stringent requirements for conductor, insulation, screen, braid armour, bedding and cable jacket compounds.

📋 NEK TS 606 Standard Overview
Full TitleCables for Offshore Installations — Halogen Free and Mud Resistant
Issuing BodyNorwegian Electrotechnical Committee (NEK)
First Edition1993
Current EditionNEK TS 606:2022
ScopeLV/MV/HV power, control, instrumentation, telecom, optical fibre cables
Voltage Range150/250V (instrumentation) to 18/30kV (HV power)
Key FeaturesHalogen free, MUD resistant, fire resistant, flame retardant
Related StandardsIEC 60092-350/353/354/376, BS 6883, IEEE 1580 Type P

NEK 606 MUD resistant cables have many similarities with cables covered under IEEE 1580 Type P (American) and British Standard BS 6883, with distinct requirements in relation to the insulation, screening, braiding, bedding and sheathing compound. The standard requires SHF2 (thermosetting halogen-free) rated sheathing for MUD resistance as specified in IEC 60092-360.

Source: Eland Cables – NEK 606 Standard Cable

EspañolIntroducción al Estándar NEK 606

NEK TS 606 es la especificación técnica de la industria offshore noruega que cubre una gama de cables de potencia, instrumentación y tierra que son libres de halógenos y/o resistentes al LODO (MUD), protegiéndolos contra el líquido de perforación cargado de hidrocarburos utilizado en operaciones de perforación. Publicado originalmente en 1993 por el Comité Electrotécnico Noruego (NEK), NEK 606 se ha convertido en un estándar aceptado internacionalmente para aplicaciones de cables offshore. Los cables BFOU (resistentes al fuego) y RFOU (retardantes de llama), así como los cables de tierra UX, son de uso común. Los cables NEK 606 están diseñados para resistir las condiciones operativas adversas y peligrosas de la industria global del petróleo y gas.

繁體中文NEK 606 標準簡介

NEK TS 606是挪威離岸工業技術規範(TS),涵蓋一系列無鹵素和/或耐泥漿(MUD resistant)的電力、儀表和接地電纜,保護它們免受鑽井作業中使用的含碳氫化合物鑽井液的不利影響。NEK 606最初於1993年由挪威電工委員會(NEK)發布,作為挪威石油工業協會”電纜規格推薦實踐”的繼承者,現已發展成為國際公認的離岸電纜標準。BFOU(耐火)和RFOU(阻燃)電纜以及UX接地電纜是常用的NEK 606電纜類型。這些電纜設計用於承受全球石油和天然氣工業的嚴苛和危險操作條件,對導體、絕緣、屏蔽、編織鎧裝、墊層和電纜護套化合物有嚴格要求。NEK 606要求使用SHF2(熱固性無鹵素)額定護套以確保耐泥漿性能。

2. NEK 606 Cable Code Designation

NEK 606 uses a systematic 2-4 letter code to describe the construction and properties of offshore cables. Understanding this code designation is essential for engineers, procurement specialists, and installation personnel working in the offshore oil and gas industry.

🔤 NEK 606 Cable Code System

PositionLetterMeaningDescription
1st Letter
Insulation
BFire Resistant + Halogen FreeEPR insulation with mica glass tape (MGT) fire barrier
REthylene Propylene Rubber (EPR)Flame retardant, excellent low-temp flexibility (-40°C)
TCross-linked Polyethylene (XLPE)Better electrical properties, higher ampacity
2nd Letter
Bedding
FHalogen Free BeddingInner sheath/bedding present between cores and armour
3rd Letter
Armour/Screen
OWire Braid (Copper)Tinned copper wire braid (TCWB) armour
CWire Braid (Steel)Galvanized steel wire braid armour
4th Letter
Outer Sheath
UHalogen Free + MUD ResistantSHF2 or SHF MUD thermosetting compound
Suffix
Screening
(i)Individual ScreenEach pair/triple separately screened (for 4-20mA analog)
(c)Collective ScreenSingle screen over all pairs (for digital signals)

2.1 Cable Type Examples

CodeBreakdownFull Description
BFOUB + F + O + UFire resistant EPR insulation + bedding + copper braid + MUD resistant sheath
RFOUR + F + O + UEPR insulation + bedding + copper braid + MUD resistant sheath
TFOUT + F + O + UXLPE insulation + bedding + copper braid + MUD resistant sheath
BUB + UFire resistant EPR + MUD resistant sheath (unarmoured)
RUR + UEPR insulation + MUD resistant sheath (unarmoured)
UXU + XEarth cable with halogen-free MUD resistant sheath

Source: Incore Cables – NEK 606 Standard Features

3. BFOU vs RFOU — Critical Selection Criteria

The distinction between BFOU (fire resistant) and RFOU (flame retardant) cables is critical for offshore safety. Incorrect selection can compromise life safety systems during emergencies.

🔥 Fire Performance Comparison
PropertyBFOU Fire ResistantRFOU Flame Retardant
Fire BarrierMica glass tape (MGT) over conductorNone
Circuit IntegrityMaintained during fire (2-3 hours)NOT maintained during fire
Test StandardIEC 60331-21, IEC 60331-31IEC 60332-3-22
Fire Temperature750-830°C sustained, 1000°C for 180 minSelf-extinguishing only
ConstructionTC/MGT/EPR/SHF2/TCWB/SHF2TC/EPR/SHF2/TCWB/SHF2
ApplicationEmergency systems, fire alarms, evacuationGeneral power, non-critical circuits
CostHigher (mica tape layer)Standard

3.1 Application Selection Guide

ApplicationCable TypeReason
BFOU Required (Fire Resistant)
Emergency shutdown systems (ESD)BFOUMust function during fire
Fire and gas detection systemsBFOUCritical safety function
Emergency lightingBFOUEvacuation visibility
Public address and alarm systemsBFOUEvacuation communication
Fire pump power supplyBFOUFirefighting capability
Life safety systemsBFOUPersonnel protection
RFOU Acceptable (Flame Retardant)
General power distributionRFOUNon-critical during fire
Non-critical instrumentationRFOUCan be isolated in emergency
Lighting in safe areasRFOUNot evacuation critical
HVAC systemsRFOUCan be shut down in fire

Source: Eland Cables – BFOU & RFOU Cables

4. NEK 606 Power Cables

NEK 606 power cables supply electromechanical and electrical equipment on offshore platforms, including emergency and critical systems such as lighting systems. Available in low voltage (0.6/1kV) and medium/high voltage (3.6/6kV to 18/30kV) ratings.

CodeTypeVoltage (U₀/U)ConstructionFire RatingApplication
Low Voltage Power Cables (0.6/1kV)
P101 RFOUFlame Retardant0.6/1kVTC/EPR/SHF2/TCWB/SHF2IEC 60332-3-22General power distribution
P101 TFOUFlame Retardant XLPE0.6/1kVTC/XLPE/SHF2/TCWB/SHF2IEC 60332-3-22Higher ampacity applications
P105 BFOUFire Resistant0.6/1kVTC/MGT/EPR/SHF2/TCWB/SHF2IEC 60331Emergency systems
P108 UXEarth Cable0.6/1kVTC/SHF2 (Green/Yellow)IEC 60332-1Earthing and bonding
P110 BUFire Resistant Unarmoured0.6/1kVTC/MGT/EPR/SHF2IEC 60331Emergency (no armour)
Medium/High Voltage Power Cables
P102 RFOUMV Flame Retardant3.6/6kVTC/EPR/SHF2/TCWB/SHF2IEC 60332-3-22MV power distribution
P103 RFOUMV Flame Retardant6/10kVTC/EPR/SHF2/TCWB/SHF2IEC 60332-3-22MV power distribution
P104 RFOUMV Flame Retardant8.7/15kVTC/EPR/SHF2/TCWB/SHF2IEC 60332-3-22MV power distribution
P112 RFOUHV Flame Retardant12/20kVTC/EPR/SHF2/TCWB/SHF2IEC 60332-3-22HV power distribution
P113 RFOUHV Flame Retardant18/30kVTC/EPR/SHF2/TCWB/SHF2IEC 60332-3-22HV power distribution

Construction Key: TC = Tinned Copper conductor, MGT = Mica Glass Tape fire barrier, EPR = Ethylene Propylene Rubber, XLPE = Cross-linked Polyethylene, SHF2 = Thermosetting Halogen Free sheath, TCWB = Tinned Copper Wire Braid armour.

5. NEK 606 Instrumentation Cables

NEK 606 instrumentation cables are designed for control and instrumentation systems on offshore platforms. They feature excellent screening properties to reduce electromagnetic interference (EMI) and are available with individual (i) or collective (c) screening options.

CodeTypeVoltageScreenFire RatingApplication
Flame Retardant Instrumentation Cables
S101 RFOU(i)Individual Screen150/250VEach pair screenedIEC 60332-3-224-20mA analog signals
S102 RFOU(c)Collective Screen150/250VOverall screenIEC 60332-3-22Digital signals
Fire Resistant Instrumentation Cables
S103 BFOU(i)Individual Screen + Fire Barrier150/250VEach pair screenedIEC 60331Emergency instrumentation
S104 BFOU(c)Collective Screen + Fire Barrier150/250VOverall screenIEC 60331Emergency control circuits
Unarmoured Instrumentation Cables
S105 RU(i)Individual Screen Unarmoured150/250VEach pair screenedFlame RetardantProtected routes
S106 RU(c)Collective Screen Unarmoured150/250VOverall screenFlame RetardantProtected routes
S107 BU(i)Fire Resistant Unarmoured150/250VEach pair screenedIEC 60331Emergency (no armour)
S108 BU(c)Fire Resistant Unarmoured150/250VOverall screenIEC 60331Emergency (no armour)

Source: Habia – BFOU and RFOU Cables NEK TS 606

6. MUD Resistance Requirements

NEK TS 606 imposes significantly more stringent oil and mud resistance requirements compared to IEC 60092-360, reflecting real-world offshore conditions where cables are exposed to drilling mud, hydraulic fluids, crude oil, and various chemical treatments.

🛢️ SHF2 MUD Resistant Sheath Requirements
PropertySHF1SHF2SHF2 MUD
Halogen Content<0.5%<0.5%<0.5%
ThermosettingYesYesYes
Oil Resistance (ISO 1817)BasicEnhanced (Category b)Enhanced (Category b)
Drilling Mud ResistanceNoNoYes (Category c)
Hydraulic Oil ResistanceNoOptionalYes (Category d)
UV ResistanceBasicEnhancedEnhanced
Temperature Range-40°C to +90°C-40°C to +90°C-40°C to +90°C

6.1 Sheath Code Designations

CodeDescriptionOil ResistanceApplication
(no marking)Minimum requirementsBasicGeneral offshore
EEnhanced Oil ResistantCategory bOil exposure areas
MEnhanced Oil + MUD ResistantCategory b + cDrilling areas
HEnhanced Oil + Hydraulic OilCategory b + dHydraulic systems
H-MEnhanced Oil + Hydraulic + MUDCategory b + c + dAll drilling areas

Source: Cleveland Cable Company – NEK 606 Cable

7. Key Technical Parameters

Voltage Range

150V – 30kV
U₀/U rating

Conductor

Tinned Cu
Class 2 EN 60228

Temp Range

-40°C to +90°C
Operating

Fire Test

750-1000°C
IEC 60331

Insulation

EPR / XLPE
Halogen-free

Armour

TCWB
Tinned copper braid

7.1 Typical Cable Construction

ConductorTinned annealed stranded copper, Class 2 per EN 60228
Fire Barrier (BFOU)Mica glass tape (MGT) wrapped around conductor
InsulationEPR (flame retardant) or XLPE (higher ampacity)
Inner Sheath/BeddingSHF2 halogen-free thermosetting compound
Screen (Instrumentation)Aluminium/polyester tape + tinned copper drain wire
ArmourTinned copper wire braid (TCWB), 85%+ coverage
Outer SheathSHF2 or SHF MUD thermosetting halogen-free compound
Sheath ColourBlack (power), Grey/Blue (instrumentation), Green/Yellow (earth)

8. Certifications and Approvals

NEK 606 cables manufactured for the offshore industry require certification from classification societies to ensure compliance with safety and quality standards.

Certification BodyAbbreviationRegionScope
Det Norske VeritasDNVNorway (International)Marine & offshore classification
Lloyd’s RegisterLRUK (International)Marine certification
American Bureau of ShippingABSUSA (International)Marine & offshore
Bureau VeritasBVFrance (International)Marine classification
Germanischer LloydGL (now DNV GL)GermanyMarine classification
China Classification SocietyCCSChinaMarine certification

NEK 606 cables are also designed to comply with related IEC standards including IEC 60092-350 (general construction), IEC 60092-353 (1kV/3kV power cables), IEC 60092-354 (6-30kV power cables), and IEC 60092-376 (instrumentation cables).

9. Complete Cable Model Summary

CodeTypeVoltageArmourFireApplication
Power Cables
P101 RFOU/TFOUFlame Retardant0.6/1kVTCWBFRGeneral power
P105 BFOUFire Resistant0.6/1kVTCWBFire ResEmergency power
P102 RFOUFlame Retardant3.6/6kVTCWBFRMV power
P103 RFOUFlame Retardant6/10kVTCWBFRMV power
P104 RFOUFlame Retardant8.7/15kVTCWBFRMV power
P112 RFOUFlame Retardant12/20kVTCWBFRHV power
P113 RFOUFlame Retardant18/30kVTCWBFRHV power
P108 UXEarth Cable0.6/1kVNoFREarthing
P110 BUFire Res Unarmoured0.6/1kVNoFire ResEmergency
P111 RUFlame Ret Unarmoured0.6/1kVNoFRProtected routes
Instrumentation Cables
S101 RFOU(i)Individual Screen150/250VTCWBFRAnalog signals
S102 RFOU(c)Collective Screen150/250VTCWBFRDigital signals
S103 BFOU(i)Fire Res Individual150/250VTCWBFire ResEmergency inst.
S104 BFOU(c)Fire Res Collective150/250VTCWBFire ResEmergency control
S105 RU(i)Unarmoured Individual150/250VNoFRProtected routes
S106 RU(c)Unarmoured Collective150/250VNoFRProtected routes
S107 BU(i)Fire Res Unarm. (i)150/250VNoFire ResEmergency
S108 BU(c)Fire Res Unarm. (c)150/250VNoFire ResEmergency

Legend: FR = Flame Retardant (IEC 60332), Fire Res = Fire Resistant (IEC 60331), (i) = Individual screen, (c) = Collective screen, TCWB = Tinned Copper Wire Braid

Authoritative External References

●
Eland Cables – NEK 606 Standard Cable
https://www.elandcables.com/…/nek-606-cable
●
Eland Cables – BFOU & RFOU Cables
https://www.elandcables.com/cables/bfou-and-rfou-cables
●
Habia – BFOU and RFOU Cables NEK TS 606
https://www.habia.com/…/bfou-and-rfou-cables
●
Incore Cables – NEK 606 Standard Features
https://www.incore-cables.com/nek-606-standard
●
Cleveland Cable Company – NEK 606 Cable
https://www.clevelandcable.com/…/nek606-cable
●
NEK – Norwegian Electrotechnical Committee (Official)
https://www.nek.no/…/Preview_NEKTS6062022en.pdf
●
CMC Cable – NEK 606 Offshore Cable
https://cmc-cable.com/…/offshore-cable
●
Power and Cables – NEK 606 BFOU RFOU Offshore
https://www.powerandcables.com/…/offshore-marine-cables
●
Prysmian Draka – NEK 606 Product Catalog
https://www.powerandcables.com/…/Prysmian-Draka-NEK606
●
ZMS Cable – NEK 606 Cable Standard
https://kvcable.com/nek606-cable

Contact Feichun Cable

For technical support with NEK 606 offshore cables, BFOU/RFOU power cables, instrumentation cables, or oil & gas industry cable applications, please contact our engineering team.

📱
📧

Technical Support

[email protected]
👤

Sales – Mr. Zihao Yang

[email protected]
👤

Sales – Mr. Ziyu Huang

[email protected]

Anhui Feichun Special Cable Co., Ltd. | 安徽飞纯特种电缆有限公司

Professional Manufacturer of NEK 606 BFOU, RFOU Offshore Oil & Gas Cables

© 2025 Feichun Cable. All rights reserved.

Previous Article

What is IEC 61158 Cable?

Next Article

What is NF C 33-226 Cables FR-N20XA8E & FR-N30XA8E -R/AR?