What is DIN VDE 0276 Cable?

Comprehensive Technical Guide to the German Standard for XLPE Insulated Power Distribution Cables — Covering Low Voltage (0.6/1kV) to Medium Voltage (18/30kV) Applications

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
What is DIN VDE 0276 Cable? | Anhui Feichun Special Cable Co., Ltd. 安徽飞纯特种电缆有限公司

What is DIN VDE 0276 Cable?

Comprehensive Technical Guide to the German Standard for XLPE Insulated Power Distribution Cables — Covering Low Voltage (0.6/1kV) to Medium Voltage (18/30kV) Applications

DIN VDE 0276 IEC 60502-2 HD 620 / HD 603 6/10kV – 18/30kV

Introduction to DIN VDE 0276 Standard

DIN VDE 0276 is the widely used German standard for cables with extruded insulation used in power distribution systems. Developed by the VDE (Verband der Elektrotechnik, Elektronik und Informationstechnik e.V.), this comprehensive standard covers a significant percentage of power cables used across the European continent, establishing construction requirements, dimensional specifications, and test methods for both low voltage (0.6/1 kV) and medium voltage (up to 18/30 kV) power cables.

The standard encompasses various cable types including XLPE (cross-linked polyethylene) and PVC insulated cables with copper or aluminum conductors. Cables manufactured to DIN VDE 0276 are suitable for permanent installation in dry and wet locations, above ground, in cable ducts, directly buried in ground, or in free air installations. The standard is harmonized with European CENELEC documents HD 603 (for low voltage) and HD 620 (for medium voltage), as well as international standards IEC 60502-1 and IEC 60502-2.

🌎 Español (América del Sur)

DIN VDE 0276 es la norma alemana ampliamente utilizada para cables con aislamiento extruido en sistemas de distribución de energía eléctrica. Esta norma integral cubre un porcentaje significativo de los cables de potencia utilizados en todo el continente europeo, estableciendo requisitos de construcción, especificaciones dimensionales y métodos de ensayo para cables de baja tensión (0.6/1 kV) y media tensión (hasta 18/30 kV).

Los cables fabricados según DIN VDE 0276 incluyen tipos como N2XSY, N2XS2Y, NA2XSY, NAYY y NYCY, utilizando aislamiento XLPE o PVC con conductores de cobre o aluminio. Estos cables son adecuados para instalación permanente en ubicaciones secas y húmedas, sobre el suelo, en conductos de cables, directamente enterrados o en instalaciones al aire libre. La norma está armonizada con los documentos europeos HD 603 y HD 620.

🔷 繁體中文說明

DIN VDE 0276 是德國廣泛使用的擠出絕緣電力分配電纜標準,由德國電氣電子及資訊技術協會(VDE)制定。此綜合標準涵蓋歐洲大陸使用的大部分電力電纜,規定了低壓(0.6/1 kV)和中壓(高達 18/30 kV)電力電纜的結構要求、尺寸規格和測試方法。

根據 VDE 0276 製造的電纜類型包括 N2XSY、N2XS2Y、NA2XSY、NAYY、NYCY 等,採用 XLPE 或 PVC 絕緣材料配合銅或鋁導體。這些電纜適用於乾燥和潮濕環境的永久安裝,可架空敷設、在電纜管道中敷設、直接埋地或在空氣中敷設。對於出口歐洲市場的電力工程項目,VDE 0276 認證是確保產品合規性的重要標準。

DIN VDE 0276 Standard Structure

The DIN VDE 0276 standard is organized into multiple parts, each addressing specific voltage ranges, cable constructions, and test requirements. Understanding this structure is essential for proper cable specification and selection.

PartScope / DescriptionVoltage RangeHarmonized With
Part 1General requirements for all power cablesAll—
Part 10-CSingle-core XLPE cables with PE/PVC sheath; Three-core XLPE cables for 6/10kV6/10, 12/20, 18/30 kVHD 620
Part 603Distribution cables of nominal voltages 0.6/1kV (LV power cables)0.6/1 kVHD 603
Part 604Power cables 0.6/1kV with special fire performance for power stations0.6/1 kVHD 604
Part 604 & 605Additional test methods for fire performance cables0.6/1 kV—
Part 620Distribution cables of nominal voltages 3.6/6kV to 20.8/36kV (MV cables)3.6/6 – 20.8/36 kVHD 620
Part 1000Current carrying capacity: general requirements, conversion factorsAllIEC 60287
Part 1001Tests on laid cables: 6/10kV, 12/20kV, 18/30kV with PVC/XLPE/paper insulation6/10 – 18/30 kV—

Source: Eland Cables DIN VDE 0276 Standard, MyStandards DIN VDE 0276

Voltage Rating Classes

0.6/1 kV
Test: 4 kV AC
6/10 kV
Test: 21 kV AC
12/20 kV
Test: 42 kV AC
18/30 kV
Test: 63 kV AC

Cable Designation System (Type Codes)

German VDE cable designations follow a systematic coding structure that identifies conductor material, insulation type, screening configuration, and outer sheath material. Understanding this nomenclature is essential for correct cable specification.

N VDE standard cable (copper conductor implied)
A Aluminium conductor
2X XLPE (cross-linked polyethylene) insulation
Y PVC insulation or sheath
S Screen (copper wires + copper tape)
SE Individual core screening
C Concentric conductor
2Y PE (polyethylene) outer sheath
(F) Longitudinally water-blocking
(FL) Water-blocking + aluminum tape bonded to sheath
H Halogen-free (LSZH) materials
B Armored (steel tape or wire)

Example Designation Breakdown

📋 N2XS2Y 12/20 kV Cable

N = VDE standard (copper conductor) | 2X = XLPE insulation | S = Copper wire screen with tape | 2Y = PE outer sheath | 12/20 kV = Rated voltage (phase-to-earth/phase-to-phase)

This designation indicates a single-core, copper conductor, XLPE-insulated medium voltage cable with copper wire/tape screen and polyethylene outer sheath, rated for 12/20 kV networks.

📋 NA2XS(F)2Y 18/30 kV Cable

N = VDE standard | A = Aluminium conductor | 2X = XLPE insulation | S = Screen | (F) = Longitudinally water-blocking | 2Y = PE sheath | 18/30 kV = Rated voltage

This is an aluminium conductor XLPE-insulated cable with water-blocking powder in the screen region and PE outer sheath for 18/30 kV applications.

Source: Caledonian Cables MV Cable Designations, STEX24 Cable Designation Guide

Comprehensive Cable Type Comparison

The following tables provide detailed comparisons of all major cable types manufactured according to DIN VDE 0276, organized by voltage class and conductor material. This comprehensive reference aids in selecting the appropriate cable for specific project requirements.

Medium Voltage Cables (6/10 kV – 18/30 kV)

Type CodeConductorInsulationScreenSheathVoltage RatingsWater Block
N2XSYCopperXLPECu wire + tapePVC6/10, 12/20, 18/30 kVNo
N2XS2YCopperXLPECu wire + tapePE6/10, 12/20, 18/30 kVNo
N2XS(F)2YCopperXLPECu wire + tapePE6/10, 12/20, 18/30 kVLongitudinal
N2XS(FL)2YCopperXLPECu + Al tapePE (bonded)6/10, 12/20 kVLong. + Radial
N2XSEYCopperXLPEIndividual SEPVC6/10 kV (3-core)No
NA2XSYAluminiumXLPECu wire + tapePVC6/10, 12/20, 18/30 kVNo
NA2XS2YAluminiumXLPECu wire + tapePE6/10, 12/20, 18/30 kVNo
NA2XS(F)2YAluminiumXLPECu wire + tapePE6/10, 12/20, 18/30 kVLongitudinal
NA2XS(FL)2YAluminiumXLPECu + Al tapePE (bonded)6/10, 12/20, 18/30 kVLong. + Radial

Low Voltage Cables (0.6/1 kV)

Type CodeConductorInsulationScreen/ArmorSheathStandard PartCore Config.
NYY-J / NYY-OCopperPVCNonePVCPart 6031-5 cores
NAYY-J / NAYY-OAluminiumPVCNonePVCPart 6031-5 cores
NYCYCopperPVCConcentric CuPVCPart 603Multi-core
NYCWYCopperPVCConcentric CuPVCPart 603Multi-core
NA2XYAluminiumXLPENonePVCPart 6031-5 cores
N2XY / N2X2YCopperXLPENonePVC / PEPart 6031-5 cores
N2XCY / N2XCHCopperXLPEConcentric CuPVC / LSZHPart 603Multi-core
NYBY / N2XBYCopperPVC / XLPESteel tape armorPVCPart 603Multi-core
NYFGBY / N2XFGbYCopperPVC / XLPESteel wire armorPVCPart 603Multi-core

Fire Performance Cables (Part 604)

Type CodeConductorFire RatingCircuit IntegrityHalogen FreeFlame Test
NHXH FE180-E30CopperFE180E30 (30 min)Yes (LSZH)EN 60332-3-24
NHXH FE180-E90CopperFE180E90 (90 min)Yes (LSZH)EN 60332-3-24
NHXCH FE180-E30CopperFE180E30 (30 min)Yes (LSZH)EN 60332-3-24
NHXCH FE180-E90CopperFE180E90 (90 min)Yes (LSZH)EN 60332-3-24

Source: JYC Cable VDE 0276-620, HY Wire Cable VDE 0276-603

Technical Specifications & Parameters

Cables manufactured to DIN VDE 0276 must meet strict construction and performance requirements. The following tables detail key technical parameters for proper cable selection and installation.

Operating Parameters

ParameterPVC InsulatedXLPE InsulatedUnit
Max. Conductor Temperature (continuous)7090°C
Max. Short-Circuit Temperature160250°C
Short-Circuit Duration (max.)55seconds
Installation Temperature (min.)-5-20 (PE) / -5 (PVC)°C
Operating Temperature Range (fixed)-5 to +70-20 to +90°C
Test Voltage (0.6/1 kV)44kV AC
Test Voltage (6/10 kV)—21kV AC
Test Voltage (12/20 kV)—42kV AC
Test Voltage (18/30 kV)—63kV AC

Construction Standards

ComponentMaterial StandardKey Requirements
ConductorIEC 60228 Class 2 / VDE 0295Stranded compacted circular Cu or Al
Conductor ScreenHD 620.1Semi-conductive, min. 0.3mm, ≤500 Ω·m at 90°C
XLPE InsulationDIN VDE 0207-22, HD 620.1 (Type 2XI1)Dry-cured, contaminant-free, high cross-linking
PVC InsulationDIN VDE 0207, HD 603Type DIV 4 compound
Insulation ScreenHD 620.1Extruded semi-conductive compound
Metallic ScreenHD 620.1Cu wires uniformly spaced + counter-helix Cu tape
PE Outer SheathDIN VDE 0276-3, HD 620.1 (Type 2YM3/DMP2)UV-resistant, wall thickness ≥2.5mm
PVC Outer SheathDIN VDE 0276-6, HD 620.1 (Type YM5/DMV6)Flame retardant, wall thickness ≥2.5mm

Bending Radius Requirements

Cable TypeMinimum Bending RadiusNotes
Without metal sheath/armor15 × ODStandard unarmored MV cables
With aluminium sheath30 × ODRadially water-blocked cables
Steel wire armored20 × ODNYFGBY, N2XFGbY types
Steel tape armored15 × ODNYBY, N2XBY types
LV unarmored (NYY, NAYY)12 × ODDistribution cables

Source: Caledonian Cables Single Core MV, LAPP Group NYY Technical Data

🌎 Español (América del Sur)

Las especificaciones técnicas de los cables VDE 0276 establecen parámetros críticos para la selección e instalación correcta. Los cables con aislamiento XLPE permiten temperaturas de operación de hasta 90°C y temperaturas de cortocircuito de 250°C, superiores a los 70°C y 160°C de los cables aislados con PVC. El radio de curvatura mínimo varía según el tipo de armadura: 15 × diámetro exterior para cables sin armadura metálica, 30 × para cables con cubierta de aluminio, y 20 × para cables armados con alambre de acero.

🔷 繁體中文說明

VDE 0276 電纜的技術規格對於正確選擇和安裝至關重要。XLPE 絕緣電纜允許的連續工作溫度高達 90°C,短路溫度可達 250°C,優於 PVC 絕緣電纜的 70°C 和 160°C。導體採用符合 IEC 60228 第 2 類標準的絞合壓縮圓形銅或鋁導體。導體屏蔽層為擠出的半導電材料,最小厚度 0.3mm,在 90°C 時體積電阻率不超過 500 Ω·m。彎曲半徑要求根據電纜類型不同而變化:無金屬護套電纜為 15 倍外徑,帶鋁護套電纜為 30 倍外徑。

Applications & Installation Methods

DIN VDE 0276 cables are designed for a wide range of power distribution applications, from utility networks to industrial installations. The choice of specific cable type depends on voltage level, installation environment, and mechanical protection requirements.

ApplicationRecommended Cable TypesInstallation MethodSpecial Requirements
MV Distribution NetworksN2XSY, N2XS2Y, NA2XSY, NA2XS2YDirect burial, ducts, cable traysMin. burial depth 0.6-0.8m
Underground Networks (wet)N2XS(F)2Y, NA2XS(F)2Y, N2XS(FL)2YDirect burial in waterlogged soilWater-blocking required
Power StationsNHXH, NHXCH (FE180-E30/E90)Cable trays, tunnelsFire performance rating
Industrial PlantsN2XCY, N2XCH, NYCYIndoor, cable trays, ductsEMC screening recommended
Building DistributionNYY, NAYY, NA2XYIn/on/under plaster, ductsVDE 0100 installation rules
Street LightingNAYY-O, NYY-ODirect burialUV-resistant sheath
Mechanical Stress AreasNYBY, N2XBY, NYFGBY, N2XFGbYDirect burial, crossing roadsSteel armor protection
Renewable Energy (Solar/Wind)N2XS2Y, NA2XS2YOutdoor, underground feedersUV-resistant PE sheath
✓ Installation Suitability

Cables manufactured to DIN VDE 0276 are suitable for permanent installation in: dry and wet locations, in buildings (above, on, in, and under plaster), in cable ducts and pipes, directly buried in ground (min. depth 0.6m, or 0.8m under roads per VDE 0276-603), in free air, and in water (with appropriate water-blocking for prolonged immersion). They are suitable for use in ambient temperatures from -20°C to +40°C depending on sheath material.

Source: ZMS Cable VDE 0276 Applications, Witthinrich GmbH MV Cables

🌎 Español (América del Sur)

Los cables DIN VDE 0276 son adecuados para una amplia gama de aplicaciones de distribución de energía. Para redes de distribución de media tensión, se utilizan cables N2XSY o N2XS2Y para instalación en conductos o enterrados directamente. En áreas con alto nivel freático, se requieren cables con bloqueo de agua como N2XS(F)2Y. Para centrales eléctricas y aplicaciones con requisitos de seguridad contra incendios, se especifican cables NHXH o NHXCH con clasificación FE180-E30/E90. Los cables armados (NYBY, N2XFGbY) se utilizan donde existe riesgo de daño mecánico.

🔷 繁體中文說明

DIN VDE 0276 電纜適用於各種電力分配應用。對於中壓配電網絡,通常使用 N2XSY 或 N2XS2Y 電纜進行管道敷設或直接埋地。在地下水位高的區域,需要使用具有防水功能的電纜如 N2XS(F)2Y。對於發電廠和有防火要求的應用,應指定使用 NHXH 或 NHXCH 等級的 FE180-E30/E90 電纜。在存在機械損傷風險的區域,使用鎧裝電纜(NYBY、N2XFGbY)提供保護。低壓配電通常使用 NYY 或 NAYY 電纜,適用於建築物內和直接埋地安裝。

📚 Authoritative References & Standards

  • DIN VDE 0276 — Power cables with extruded insulation for distribution systems | Eland Cables
  • DIN VDE 0276-620 — Distribution cables 3.6/6kV to 20.8/36kV (MV) | HT Wire Cable
  • DIN VDE 0276-603 / HD 603 — Distribution cables 0.6/1kV (LV) | LAPP Group
  • DIN VDE 0207-22 — XLPE insulation compound specifications | Caledonian Cables
  • IEC 60228 — Conductor specifications for cables | Caledonian MV Cables
  • IEC 60502-2 — Power cables 1kV to 30kV (International equivalent) | ZMS Cable
  • HD 620 / HD 603 — CENELEC Harmonization Documents | JYC Cable
  • DIN VDE 0276-1000 — Current carrying capacity calculations | MyStandards

Contact Anhui Feichun Special Cable

For technical inquiries regarding DIN VDE 0276 power distribution cables, medium voltage XLPE cable specifications, or quotation requests for European market projects, please contact our engineering team.

WhatsApp / Phone +86 138 5512 3218
Technical Support Email [email protected]
Quick Contact Chat on WhatsApp
Previous Article

What is DIN VDE 0266 Cable?

Next Article

What is DIN VDE 0812 Cable?

View Comments (2)

Leave a Comment

您的邮箱地址不会被公开。 必填项已用 * 标注