What is HD620 Standard Cable?

Comprehensive Technical Guide to CENELEC Harmonization Document HD 620 — Medium Voltage Power Distribution Cables with Extruded Insulation for Rated Voltages from 3.6/6 (7.2) kV to 20.8/36 (42) kV

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
What is HD620 Standard Cable? | Anhui Feichun Special Cable Co., Ltd. 安徽飞纯特种电缆有限公司

What is HD620 Standard Cable?

Comprehensive Technical Guide to CENELEC Harmonization Document HD 620 — Medium Voltage Power Distribution Cables with Extruded Insulation for Rated Voltages from 3.6/6 (7.2) kV to 20.8/36 (42) kV

CENELEC HD 620 S3 IEC 60502-2 DIN VDE 0276-620 XLPE / EPR / HEPR 3.6kV – 36kV

Introduction to HD 620 Standard

Harmonization Document HD 620 is a CENELEC (European Committee for Electrotechnical Standardization) standard that specifies requirements for medium voltage power distribution cables with extruded insulation. The standard covers cables with rated voltages from 3.6/6 (7.2) kV up to 20.8/36 (42) kV, used extensively in power distribution networks across Europe and internationally. The latest iteration, HD 620 S3, was released and ratified by CENELEC member countries in 2023.

HD 620 is commonly linked to the German national standard DIN VDE 0276 Part 620 and is harmonized with international standard IEC 60502-2. The standard establishes comprehensive construction requirements, dimensional specifications, and test methods that exceed the baseline requirements of IEC 60502-2. Both HD 620 and IEC 60502-2 require compulsory conductor and insulation screening, typically applied through a triple extrusion process with the insulation layer. The test methodology for compliance is set out in HD 605 subclause 2.1.1 for insulation material and HD 605 subclause 2.1.2 for sheath material.

🇪🇺 CENELEC Harmonization

HD 620 serves as the harmonized European standard for medium voltage power cables, ensuring consistent quality and performance across all CENELEC member countries. National adoptions include UNE-HD 620 (Spain), NEN-HD 620 (Netherlands), CEI-HD 620 (Italy), DS-HD 620 (Denmark), and equivalence with DIN VDE 0276-620 (Germany).

🌎 Español (América del Sur)

El Documento de Armonización HD 620 es una norma CENELEC que especifica los requisitos para cables de distribución de media tensión con aislamiento extruido. La norma abarca cables con tensiones nominales desde 3,6/6 (7,2) kV hasta 20,8/36 (42) kV, utilizados ampliamente en redes de distribución de energía en Europa e internacionalmente. La última versión, HD 620 S3, fue publicada y ratificada por los países miembros de CENELEC en 2023.

HD 620 está comúnmente vinculada a la norma alemana DIN VDE 0276 Parte 620 y está armonizada con la norma internacional IEC 60502-2. Establece requisitos de construcción, especificaciones dimensionales y métodos de ensayo que superan los requisitos base de IEC 60502-2. Los tipos de aislamiento cubiertos incluyen XLPE (polietileno reticulado), EPR (caucho de etileno-propileno) y HEPR (caucho de etileno-propileno de grado duro).

🔷 繁體中文說明

協調文件 HD 620 是 CENELEC(歐洲電工標準化委員會)制定的標準,規定了擠出絕緣中壓電力分配電纜的要求。該標準涵蓋額定電壓從 3.6/6 (7.2) kV 到 20.8/36 (42) kV 的電纜,廣泛應用於歐洲及國際電力分配網絡。最新版本 HD 620 S3 於 2023 年由 CENELEC 成員國發布並批准。

HD 620 與德國國家標準 DIN VDE 0276 第 620 部分密切相關,並與國際標準 IEC 60502-2 協調一致。該標準規定的結構要求、尺寸規格和測試方法超出了 IEC 60502-2 的基本要求。HD 620 和 IEC 60502-2 都要求強制性的導體和絕緣屏蔽,通常通過與絕緣層的三重擠出工藝實現。涵蓋的絕緣類型包括 XLPE(交聯聚乙烯)、EPR(乙丙橡膠)和 HEPR(硬質乙丙橡膠)。

Voltage Ratings & Classifications

HD 620 covers five standard voltage ratings for medium voltage power distribution cables. The voltage designation follows the format U₀/U (Um), where U₀ is the rated power-frequency voltage between conductor and earth, U is the rated voltage between conductors, and Um is the maximum voltage that can be sustained under normal operating conditions.

3.6/6 kV
Um = 7.2 kV
6/10 kV
Um = 12 kV
8.7/15 kV
Um = 17.5 kV
12/20 kV
Um = 24 kV
18/30 kV
Um = 36 kV

Additionally, HD 620 covers the higher voltage rating of 20.8/36 (42) kV for specialized applications. The standard also references voltage designations used in some countries such as 3.5/6 kV, 5.8/10 kV, 11.5/20 kV, and 17.3/30 kV which are considered equivalent.

Source: Eland Cables HD620 Standard, Tratos Group HD 620 S2

HD 620 Standard Structure

HD 620 is organized into multiple parts, with Part 1 covering general requirements applicable to all cable types. Subsequent parts address specific insulation materials: HEPR (Part 9), XLPE (Part 10), and EPR (Part 11). Parts 2, 3, and 4 are currently spare (previously withdrawn), while Parts 5 & 6 have been consolidated into Part 10 XLPE, and Parts 7 & 8 now form Part 11 EPR.

HD 620 Part 1
General Requirements
Common requirements applicable to all cable types unless otherwise specified in specific parts.
HD 620 Part 9
HEPR Insulated Cables
Hard Grade Ethylene Propylene Rubber insulated single-core cables and pre-assembled cables.
HD 620 Part 10
XLPE Insulated Cables
Cross-linked Polyethylene insulated single-core and 3-core cables, including pre-assembled cables.
HD 620 Part 11
EPR Insulated Cables
Ethylene Propylene Rubber insulated single-core and 3-core cables.

HD 620 Part 10 Sub-Sections (XLPE Cables)

Sub-SectionDescriptionSheath Type
HD 620 10-AXLPE insulation; PE or PVC sheathPE / PVC
HD 620 10-BXLPE insulation; PE, PVC or Polyolefin compound sheathPE / PVC / Polyolefin
HD 620 10-CXLPE insulation; PE or PVC sheathPE / PVC
HD 620 10-ECables with Polyolefin compound sheath (Types 10E-1 to 10E-5)Polyolefin
HD 620 10-FMultiple cable types (10F-1 to 10F-14) including laid-up and messenger configurationsPVC / PE
HD 620 10-GLaid-up cables (Types 10G-1 to 10G-5) with/without messengerPVC / PE
HD 620 10-ITriplex formation MV cables with reduced insulation thickness, Al tape screenPE
HD 620 10-JSingle-core and three-core cables (Types 10J-1 to 10J-3)PE / PVC / PVC-FR
HD 620 10-KCables with PE sheath (10K-1) or PVC sheath (10K-2)PE / PVC
HD 620 10-O11kV and 33kV copper wire screened cables; lead sheathed with PE outerPE / Polyolefin / Lead + PE

National Adoptions

DIN VDE 0276-620
Germany
UNE-HD 620
Spain
NEN-HD 620
Netherlands
CEI-HD 620
Italy
DS-HD 620
Denmark
BS 7870-4
UK (Related)

Source: Eland Cables HD620, GlobalSpec HD 620 S1/A3

Technical Specifications

HD 620 cables must meet stringent construction and performance requirements. The standard specifies parameters for conductor types, insulation materials, screening, and outer sheaths, with specific test requirements beyond those of IEC 60502-2.

Insulation Material Properties

Insulation TypeMax. Conductor Temp.Short-Circuit Temp.Voltage RangeHD 620 Part
XLPE (Cross-linked PE)90°C250°C3.6/6 – 20.8/36 kVPart 10
EPR (Ethylene Propylene)90°C250°C3.6/6 – 20.8/36 kVPart 11
HEPR (Hard EPR)90°C250°C3.6/6 – 20.8/36 kVPart 9
PVC/B70°C160°C3.6/6 kV only—

Nominal Insulation Thickness (XLPE)

Conductor Size (mm²)6/10 kV8.7/15 kV12/20 kV18/30 kV
25 – 503.4 mm4.5 mm5.5 mm8.0 mm
70 – 1203.4 mm4.5 mm5.5 mm8.0 mm
150 – 2403.4 mm4.5 mm5.5 mm8.0 mm
300 – 5003.4 mm4.5 mm5.5 mm8.0 mm
630 – 10003.4 mm4.5 mm5.5 mm8.0 mm
1200 – 16003.4 mm4.5 mm5.5 mm8.0 mm

Construction Requirements

ComponentSpecificationStandard Reference
ConductorClass 1 (solid) or Class 2 (stranded) copper/aluminiumIEC 60228 / BS EN 60228
Conductor Size Range10 mm² to 1600 mm²IEC 60502-2
Conductor ScreenSemi-conducting compound, extruded (compulsory)HD 620 / IEC 60502-2
Insulation ScreenSemi-conducting compound, extruded (compulsory)HD 620 / IEC 60502-2
Triple ExtrusionConductor screen + insulation + insulation screen in single passHD 620
Metallic ScreenCopper wire screen, copper tape, or aluminium tapeHD 620
Water BlockingSwellable tapes/powders for (F) and (FL) typesHD 620
Outer SheathPE (MDPE/HDPE), PVC, or Polyolefin compoundHD 605

Mechanical Parameters

ParameterSingle-CoreThree-CoreNotes
Minimum Bending Radius15 × OD12 × ODDuring installation
Operating Temperature0°C to +90°C0°C to +90°CXLPE/EPR/HEPR
Installation Temperature0°C to +60°C0°C to +60°CDuring laying
Short-Circuit Durationmax. 5 secmax. 5 secAt 250°C (XLPE)

Source: Tratos IEC 60502-2, Caledonian HD620 Cables

🌎 Español (América del Sur)

Las especificaciones técnicas de HD 620 definen requisitos estrictos para cables de media tensión. Los materiales de aislamiento principales incluyen XLPE, EPR y HEPR, todos con temperatura máxima de conductor de 90°C y temperatura de cortocircuito de 250°C. El espesor nominal de aislamiento XLPE varía desde 3.4 mm (6/10 kV) hasta 8.0 mm (18/30 kV). La construcción requiere pantallas de conductor y aislamiento obligatorias mediante extrusión triple. El radio de curvatura mínimo es 15 veces el diámetro exterior para cables unipolares y 12 veces para cables tripolares.

🔷 繁體中文說明

HD 620 的技術規格對中壓電纜規定了嚴格的要求。主要絕緣材料包括 XLPE、EPR 和 HEPR,均具有 90°C 的最高導體溫度和 250°C 的短路溫度。XLPE 絕緣的標稱厚度從 3.4 mm(6/10 kV)到 8.0 mm(18/30 kV)不等。結構要求通過三重擠出工藝實現強制性的導體和絕緣屏蔽。導體尺寸範圍為 10 mm² 至 1600 mm²,符合 IEC 60228 標準。單芯電纜的最小彎曲半徑為外徑的 15 倍,三芯電纜為外徑的 12 倍。

HD620 Cable Types Comparison

The following comprehensive comparison covers the major cable types manufactured in accordance with HD 620, organized by conductor material and voltage rating. These designations follow the German VDE nomenclature commonly used alongside HD 620 references.

Copper Conductor Cables

Type CodeInsulationSheathWater BlockVoltage RatingsHD 620 Part
N2XSYXLPEPVCNo6/10, 12/20, 18/30 kVPart 10
N2XS2YXLPEPE (MDPE)No6/10, 12/20, 18/30 kVPart 10
N2XS(F)2YXLPEPE (MDPE)Longitudinal6/10, 12/20, 18/30 kVPart 10
N2XS(FL)2YXLPEPE (bonded)Long. + Radial6/10, 12/20 kVPart 10
N2XSEYXLPEPVCNo6/10 kV (3-core)Part 10

Aluminium Conductor Cables

Type CodeInsulationSheathWater BlockVoltage RatingsHD 620 Part
NA2XSYXLPEPVCNo6/10, 12/20, 18/30 kVPart 10
NA2XS2YXLPEPE (MDPE)No6/10, 12/20, 18/30 kVPart 10
NA2XS(F)2YXLPEPE (MDPE)Longitudinal6/10, 12/20, 18/30 kVPart 10
NA2XS(FL)2YXLPEPE (bonded)Long. + Radial6/10, 12/20, 18/30 kVPart 10

National Variant Designations

DesignationCountry/RegionConductorDescriptionVoltage Ratings
YMz1KrvasdlwdEuropeanCopperXLPE insulated, Cu wire screen, PE sheath8.7/15, 12/20, 18/30 kV
YMz1Krvasdlwd-ALEuropeanAluminiumXLPE insulated, Cu wire screen, PE sheath8.7/15, 12/20, 18/30 kV
YMeKrvasdlwdEuropeanAluminiumEPR insulated, MDPE sheath, single/3-core6/10 – 18/30 kV
AHXCMK-WTCInternationalAluminiumXLPE, concentric Cu, flame retardant6/10 – 18/30 kV
AXQJ-F / AXLJ-FNordicAluminiumXLPE insulated, water-blocked, PE sheath12/20, 18/30 kV
FXLJ-FNordicCopperXLPE insulated, water-blocked, PE sheath12/20 kV
XHIE / LXHIEEuropeanCu / AlXLPE, individual screen, PE sheath6/10 – 18/30 kV
XHIV / LXHIVEuropeanCu / AlXLPE, individual screen, PVC sheath6/10 – 18/30 kV
ARE4H5EX / ARE4H5EXYItalian (CEI)AluminiumXLPE, Cu screen, halogen-free sheath12/20, 18/30 kV
RG7H1ONR / ARG7H1ORItalian (CEI)Cu / AlHEPR insulated, Cu screen, halogen-free12/20, 18/30 kV
EXeCWBBritishCopperXLPE, concentric Cu, water-blocked11kV, 33kV

Source: Eland Cables HD620 Products, Tratos Group HD 620

Applications & Installation

HD 620 cables are designed for power distribution networks, industrial installations, and infrastructure applications. These medium voltage cables are suitable for permanent installation in various environments including underground, outdoor, and cable ducting installations.

ApplicationRecommended Cable TypesInstallation MethodSpecial Requirements
Primary DistributionN2XSY, NA2XSY, N2XS2Y, NA2XS2YDirect burial, ducts, cable traysStandard PE or PVC sheath
Wet/Waterlogged AreasN2XS(F)2Y, NA2XS(F)2Y, N2XS(FL)2YDirect burial in wet soilWater-blocking required
Industrial PlantsN2XSEY, XHIV, LXHIVCable trays, indoor installationsIndividual core screening
Fire-Risk AreasARE4H5EX, RG7H1ONR, AHXCMK-WTCTunnels, public buildingsHalogen-free, flame retardant
Railways/TransportAXLJ-F TT, XHIOE, LXHIOETrack-side, substationsEnhanced mechanical protection
Renewable EnergyNA2XS2Y, YMz1Krvasdlwd-ALSolar farms, wind installationsUV-resistant PE sheath
Utility NetworksEXeCWB, TRIPLEX formationsDNO networks, overhead to groundBS 7870 compliance
✓ Installation Suitability

HD 620 cables are suitable for fixed installation in: power distribution networks underground, outdoors in free air, in cable ducts and conduits, industrial facilities and power stations, and areas where fire, smoke emission and toxic fumes create potential threats (when halogen-free variants are specified). The cables are designed for rated voltages up to 36 kV and conductor cross-sections from 10 mm² to 1600 mm².

Source: Caledonian Railway Power Cables, Tratos IEC 60502 Applications

📚 Authoritative References & Standards

  • HD 620 S3 (2023) — CENELEC Harmonization Document for MV distribution cables | Eland Cables
  • IEC 60502-2 — Power cables 6kV to 30kV with extruded insulation | Tratos Group
  • DIN VDE 0276-620 — German national adoption of HD 620 | Eland Cables VDE 0276
  • HD 605 — Test methods for insulation and sheath materials | GlobalSpec
  • IEC 60228 — Conductor specifications for cables | Tratos IEC 60502-1
  • BS 7870-4 — UK MV polymeric insulated cables (related) | Tratos HD 620
  • Caledonian HD620 Power Cables — Railway and industrial applications | Caledonian Cables
  • HELUKABEL MV Cables — 6/10kV, 12/20kV, 18/30kV specifications | HELUKABEL

Contact Anhui Feichun Special Cable

For technical inquiries regarding HD 620 medium voltage power cables, XLPE/EPR insulated cable specifications, or quotation requests for European market projects, please contact our engineering team.

WhatsApp / Phone +86 138 5512 3218
Technical Support Email [email protected]
Quick Contact Chat on WhatsApp
Previous Article

What is DIN VDE 0812 Cable?

Next Article

What is IEC 60502 Cable?

Write a Comment

Leave a Comment

您的邮箱地址不会被公开。 必填项已用 * 标注