What is IEC 60840 Cable?

Comprehensive Technical Guide to International Electrotechnical Commission Standard IEC 60840 — Power Cables with Extruded Insulation and Their Accessories for Rated Voltages Above 30 kV (Um = 36 kV) Up to 150 kV (Um = 170 kV)

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
What is IEC 60840 Cable? | Anhui Feichun Special Cable Co., Ltd. 安徽飞纯特种电缆有限公司

What is IEC 60840 Cable?

Comprehensive Technical Guide to International Electrotechnical Commission Standard IEC 60840 — Power Cables with Extruded Insulation and Their Accessories for Rated Voltages Above 30 kV (Um = 36 kV) Up to 150 kV (Um = 170 kV)

IEC 60840:2020 High Voltage 30kV – 150kV XLPE Insulation Um ≤ 170kV

Introduction to IEC 60840 Standard

IEC 60840 is an internationally recognized standard developed by the International Electrotechnical Commission (IEC) that defines the test methods and performance requirements for high-voltage power cable systems with extruded insulation. The standard applies to systems designed for rated voltages above 30 kV (Um = 36 kV) up to and including 150 kV (Um = 170 kV), making it the essential reference for cables used in power transmission infrastructure, grid interconnections, and large-scale industrial energy networks.

The current fifth edition, IEC 60840:2020, represents a significant technical evolution from previous versions, introducing requirements for composite outdoor termination insulators, a new low smoke halogen-free oversheath material designated ST12, additional fire performance tests, and water penetration testing in conductors. The standard covers cables, accessories (joints and terminations), and complete cable systems intended for fixed installations, applicable to both single-core cables and individually screened three-core cables under typical installation and operational conditions.

🔌 IEC 60840 Standard Scope

IEC 60840 covers power cables with extruded insulation for primary power distribution in transmission networks. Cables manufactured to this standard are designed for fixed installations and are suitable for buried applications transporting power across extended distances. The standard excludes cables for special applications such as submarine cables, mining cables, and their associated accessories where modified tests or unique conditions may be required.

⚡ 30-Year Service Life Testing

To achieve compliance with IEC 60840, cables are subject to rigorous type test sequences simulated to represent a 30-year service lifetime on cable samples of at least 1 metre. Unlike IEC 60502-2 testing for medium voltage cables, IEC 60840 applies voltage during the burner heating cycles, ensuring cables can withstand the combined thermal and electrical stresses encountered in real-world high voltage transmission applications.

🌎 Español (América del Sur)

IEC 60840 es una norma internacional desarrollada por la Comisión Electrotécnica Internacional (IEC) que define los métodos de ensayo y requisitos de rendimiento para sistemas de cables de alta tensión con aislamiento extruido. La norma se aplica a sistemas diseñados para tensiones nominales superiores a 30 kV (Um = 36 kV) hasta 150 kV (Um = 170 kV) inclusive.

La quinta edición actual, IEC 60840:2020, introduce requisitos para aisladores compuestos de terminaciones exteriores, un nuevo material de cubierta exterior libre de halógenos y baja emisión de humo designado ST12, pruebas adicionales de rendimiento ante fuego y pruebas de penetración de agua en conductores. La norma abarca cables, accesorios (empalmes y terminaciones) y sistemas de cables completos destinados a instalaciones fijas, tanto para cables unipolares como para cables tripolares con pantalla individual.

🔷 繁體中文說明

IEC 60840 是國際電工委員會(IEC)制定的國際認可標準,定義了擠出絕緣高壓電力電纜系統的測試方法和性能要求。該標準適用於額定電壓高於 30 kV(Um = 36 kV)至 150 kV(Um = 170 kV)的系統,是電力傳輸基礎設施、電網互連和大規模工業能源網絡所用電纜的重要參考依據。

現行第五版 IEC 60840:2020 相較於先前版本有重大技術進展,引入了複合材料戶外終端絕緣子要求、新的低煙無鹵素外護套材料(標記為 ST12)、額外的防火性能測試以及導體水滲透測試。該標準涵蓋電纜、附件(接頭和終端)以及用於固定安裝的完整電纜系統,適用於典型安裝和運行條件下的單芯電纜和獨立屏蔽三芯電纜。為達到 IEC 60840 合規性,電纜需經過嚴格的型式試驗序列,模擬至少 1 米電纜樣品的 30 年使用壽命。

Voltage Ratings & Classifications

IEC 60840 covers five primary voltage ratings for high voltage power transmission cables. The voltage designation follows the format U₀/U (Um), where U₀ is the rated power-frequency voltage between conductor and earth (or metallic screen), U is the rated voltage between conductors, and Um is the maximum voltage that can be sustained under normal operating conditions at any point in the system.

26/45 kV
Um = 52 kV
36/60 kV
Um = 72.5 kV
64/110 kV
Um = 123 kV
76/132 kV
Um = 145 kV
87/150 kV
Um = 170 kV

For voltages above 150 kV (Um = 170 kV) up to 500 kV (Um = 550 kV), the companion standard IEC 62067 applies. The IEC 60840 voltage range bridges the gap between medium voltage cables (covered by IEC 60502-2 up to 30 kV) and extra-high voltage transmission systems, serving as the backbone of national and regional power distribution networks.

Source: Eland Cables IEC 60840, Tratos Group IEC 60840

Cable Construction & Materials

IEC 60840 high voltage cables feature a sophisticated multi-layer construction designed to manage the intense electrical stresses at transmission voltages. Each layer serves a specific purpose in ensuring safe, reliable power transmission over the cable’s 30+ year service life. The construction typically includes a conductor, conductor screen, XLPE insulation, insulation screen, metallic screen, and protective oversheath.

Layer 1
Conductor
Stranded circular or segmental (Milliken) compacted copper or aluminium conductor per IEC 60228. Class 2 stranded conductors with water blocking for longitudinal watertightness. Operating temperature 90°C, short-circuit 250°C.
Layer 2
Conductor Screen
Extruded semi-conductive XLPE layer to provide a smooth cylindrical equi-potential surface. Eliminates air voids and prevents electric field concentration at conductor surface. Typically a few millimeters thick.
Layer 3
XLPE Insulation
Cross-linked polyethylene (XLPE) insulation with high dielectric strength. Extruded in ultra-clean process to prevent partial discharges. Continuous operation 90°C, emergency 130°C, short-circuit 250°C.
Layer 4
Insulation Screen
Extruded semi-conductive layer firmly bonded to XLPE insulation. Controls electric field outside insulation, prevents stress points leading to partial discharge. Applied in triple extrusion with conductor screen and insulation.
Layer 5
Metallic Screen/Sheath
Helically applied copper wires or aluminium laminated tape providing earth fault current path and electromagnetic shielding. May include lead sheath for water impermeability or corrugated aluminium sheath for enhanced protection.
Layer 6
Outer Sheath (Oversheath)
High Density Polyethylene (HDPE) or Medium Density Polyethylene (MDPE) providing abrasion resistance and flexibility. LSZH option (ST12) available for fire-sensitive installations. Graphite coating for DC voltage sheath testing.

Insulation & Sheath Material Properties

MaterialDesignationMax. Continuous Temp.Emergency Temp.Short-Circuit Temp.Application
XLPECross-linked Polyethylene90°C130°C250°C (5s max)Primary insulation
EPREthylene Propylene Rubber90°C130°C250°CFlexible insulation
HEPRHard Ethylene Propylene90°C130°C250°CHigh modulus insulation
HDPEHigh Density Polyethylene70°C——Outer sheath (standard)
MDPEMedium Density Polyethylene70°C——Outer sheath (flexible)
ST12 (LSZH)Low Smoke Halogen Free70°C——Fire-sensitive areas

Conductor Specifications

ParameterCopper ConductorAluminium ConductorStandard Reference
Cross-section range185 – 2500 mm²300 – 2500 mm²IEC 60228
ConstructionStranded circular or MillikenStranded circular or MillikenIEC 60840
Conductor classClass 2 (stranded)Class 2 (stranded)IEC 60228
Water blockingSwellable powder/tapeSwellable powder/tapeIEC 60840
Operating temperature90°C90°CIEC 60840
Short-circuit temperature250°C250°CIEC 60840

Source: Circuit Masterclass EHV Cable Construction, Alfanar HV Cables Technical Catalogue

IEC 60840 Cable Types Comparison

The following comprehensive comparison covers the major cable types manufactured in accordance with IEC 60840, organized by conductor material, voltage rating, and sheath type. These designations follow the VDE/CENELEC nomenclature commonly used alongside IEC references in international cable specifications.

Copper Conductor High Voltage Cables

Type CodeInsulationWater BlockMetallic ScreenOuter SheathVoltage Ratings
2XS(F)2YXLPELongitudinal (F)Cu wire + Al tapePE64/110 kV (123 kV)
2XS(FL)2Y HDPEXLPELong. + Radial (FL)Cu wire + Al laminateHDPE26/45 kV (52 kV)
2XS(FL)2Y HDPEXLPELong. + Radial (FL)Cu wire + Al laminateHDPE36/60 kV (72.5 kV)
2XS(FL)2Y HDPEXLPELong. + Radial (FL)Cu wire + Al laminateHDPE64/110 kV (123 kV)
2XS(FL)2Y HDPEXLPELong. + Radial (FL)Cu wire + Al laminateHDPE76/132 kV (145 kV)
2XS(FL)2Y MDPEXLPELong. + Radial (FL)Cu wire + Al laminateMDPE26/45 kV (52 kV)
2XS(FL)2Y MDPEXLPELong. + Radial (FL)Cu wire + Al laminateMDPE36/60 kV (72.5 kV)
2XS(FL)2Y MDPEXLPELong. + Radial (FL)Cu wire + Al laminateMDPE64/110 kV (123 kV)
2XS(FL)2Y MDPEXLPELong. + Radial (FL)Cu wire + Al laminateMDPE76/132 kV (145 kV)

Aluminium Conductor High Voltage Cables

Type CodeInsulationWater BlockMetallic ScreenOuter SheathVoltage Ratings
A2XS(F)2YXLPELongitudinal (F)Cu wire + Al tapePE64/110 kV (123 kV)
A2XS(FL)2Y HDPEXLPELong. + Radial (FL)Cu wire + Al laminateHDPE26/45 kV (52 kV)
A2XS(FL)2Y HDPEXLPELong. + Radial (FL)Cu wire + Al laminateHDPE36/60 kV (72.5 kV)
A2XS(FL)2Y HDPEXLPELong. + Radial (FL)Cu wire + Al laminateHDPE64/110 kV (123 kV)
A2XS(FL)2Y HDPEXLPELong. + Radial (FL)Cu wire + Al laminateHDPE76/132 kV (145 kV)
A2XS(FL)2Y MDPEXLPELong. + Radial (FL)Cu wire + Al laminateMDPE26/45 kV (52 kV)
A2XS(FL)2Y MDPEXLPELong. + Radial (FL)Cu wire + Al laminateMDPE36/60 kV (72.5 kV)
A2XS(FL)2Y MDPEXLPELong. + Radial (FL)Cu wire + Al laminateMDPE64/110 kV (123 kV)
A2XS(FL)2Y MDPEXLPELong. + Radial (FL)Cu wire + Al laminateMDPE76/132 kV (145 kV)

Type Code Designation System

Code ElementMeaningOptions
Prefix (none)Copper conductorDefault for copper
AAluminium conductorPrefix A indicates aluminium
2XXLPE insulationCross-linked polyethylene
SCopper wire screenMetallic screening layer
(F)Longitudinal water blockingSwellable tapes/powders
(FL)Longitudinal + Radial water blockingComplete water sealing
2YPE outer sheathPolyethylene oversheath
HDPEHigh Density Polyethylene sheathEnhanced abrasion resistance
MDPEMedium Density Polyethylene sheathEnhanced flexibility

Source: Eland Cables IEC 60840 Products, ZMS IEC 60840 Cable

Test Requirements & Compliance

IEC 60840 specifies comprehensive test requirements to ensure cable systems meet the demanding performance standards for high voltage transmission. The testing regime includes routine tests performed on every manufactured cable length, sample tests on representative samples, type tests to verify design compliance, and prequalification tests to demonstrate long-term reliability.

Test Categories

Test CategoryPurposeFrequencyKey Tests
Routine TestsProduction quality verificationEvery cable lengthPartial discharge, voltage test, conductor resistance
Sample TestsMaterial compliance verificationPer batch/lotHot set test, thickness measurement, capacitance
Type TestsDesign validation (30-year simulation)Initial + changesBending test, heating cycle, lightning impulse, water penetration
Prequalification TestsLong-term reliability demonstrationNew designsExtended heating cycles, high electrical stress validation

IEC 60840:2020 Technical Updates

Update AreaDescriptionReference
Gas-immersed terminationsRequired to meet IEC 62271-209 for voltages above 52 kVIEC 62271-209
Composite insulatorsNew requirements for composite outdoor termination insulatorsIEC 60840:2020
Bending test cylindersModified diameters per IEC TR 61901:2016IEC TR 61901
ST12 oversheathNew low smoke halogen-free material designationIEC 60840:2020
Fire performance testsVertical flame spread, smoke density, acidity, conductivityIEC 60332
Water penetration testNew test for water ingress into conductorIEC 60840:2020
Screen sectionalizingType tests on joint screen sectionalizing insulationIEC 60840:2020

Source: IEC 60840:2020 Standard Document, Document Center IEC 60840

Applications & Installation

IEC 60840 cables are designed for fixed installations in high voltage power transmission networks, serving as the primary means of distributing electrical power over extended distances. These cables are suitable for both underground buried installations and overhead line applications where robustly sheathed.

ApplicationRecommended Cable TypesVoltage RangeKey Requirements
Grid Transmission2XS(FL)2Y, A2XS(FL)2Y64/110 – 87/150 kVHigh current capacity, FL water blocking
Direct Burial2XS(FL)2Y HDPE, A2XS(FL)2Y HDPE26/45 – 76/132 kVHDPE sheath, complete water blocking
Cable TunnelsST12 (LSZH) variantsAll voltagesLow smoke, halogen-free sheath
Substation Links2XS(F)2Y, A2XS(F)2Y64/110 kVLongitudinal water blocking
Industrial Plants2XS(FL)2Y MDPE36/60 – 64/110 kVMDPE for flexibility
Renewable EnergyA2XS(FL)2Y HDPE26/45 – 76/132 kVAl conductor for cost efficiency
⚠️ Exclusions from IEC 60840

IEC 60840 does not extend to special applications such as submarine cables and their associated accessories, mining cables, or installations where modified tests or unique conditions may be required. For such applications, specific standards like IEC 63026 (submarine power cables) should be referenced, or cables should be specified as manufactured “generally to IEC 60840” with additional project-specific requirements.

Source: Tratos Group IEC 60840 Applications, Power and Cables IEC 60840

📚 Authoritative References & Standards

  • IEC 60840:2020 — Power cables 30kV to 150kV with extruded insulation | IEC Standard Document
  • IEC 60840 Overview — High voltage cable standard guide | Eland Cables
  • Tratos IEC 60840 — Standard scope and applications | Tratos Group
  • IEC 62067 — Cables above 150kV up to 500kV (companion standard) | Document Center
  • IEC 60228 — Conductor specifications for cables | ZMS Cable
  • EHV XLPE Cable Construction — Technical construction guide | Circuit Masterclass
  • Alfanar HV Cables — Technical catalogue | Alfanar
  • Power & Cables IEC 60840 — Standards and accessories guide | Power and Cables

Contact Anhui Feichun Special Cable

For technical inquiries regarding IEC 60840 high voltage power cables, XLPE insulated transmission cable specifications, or quotation requests for power grid and industrial transmission projects, please contact our engineering team.

WhatsApp / Phone +86 138 5512 3218
Technical Support Email [email protected]
Quick Contact Chat on WhatsApp

Previous Article

What is IEC 60502 Cable?

Next Article

What is IEC 62026-3 Cable?

Write a Comment

Leave a Comment

您的邮箱地址不会被公开。 必填项已用 * 标注