FLEXIFESTOON® (N)GRDGCGÖU-J

Flexible screened round festoon cable

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
FLEXIFESTOON® (N)GRDGCGÖU-J Screened Festoon Cable | FeiChun Special Cables
VDE 0250 Part 814 Screened Festoon Cable

FLEXIFESTOON® (N)GRDGCGÖU-J

0.6/1kV Flexible Screened Multi-Core Power Cable per VDE 0250 part 814

⚡ Voltage: 0.6/1kV (screened, EMC-optimized) 🛡️ Screen: Tinned copper braid ⚙️ Speed: 240 m/min 📦 SKU: 17 configurations
Nominal Voltage
0.6/1kV
VDE 0250 part 814
Screen Type
Tinned Cu Braid
Braided coverage
Insulation
EPR 3GI3
3-layer design
EMC Performance
Good
Shielded design
Max Speed
240 m/min
High-speed rating
Temperature
−50 to +80°C
Extreme range

1. Screened Design: VDE 0250 part 814 vs. part 813

GRDGCGÖU-J is the screened variant of the GRDGÖU-J cable. The “C” in the model designation indicates copper braid screen. VDE 0250 part 814 governs screened festoon cables, while part 813 covers unscreened:

VDE 0250 Part 813 vs. Part 814:Part 813 (Unscreened GRDGÖU-J): Scope: General-purpose festoon cables without shielding Screen: None EMC performance: Not specified Applications: Standard crane systems, stage lighting, outdoor use Cost: Base pricingPart 814 (Screened GRDGCGÖU-J): Scope: Festoon cables with braid or tape screen for EMC Screen: Tinned copper braid (mandatory) EMC performance: Good (shielding effectiveness specified) Applications: Motor power supply, VFD circuits, noise-sensitive equipment Cost: +15–20% premium over part 813Nomenclature change: GRDGÖU-J → GRDGCGÖU-J (added “C” for screen) Full breakdown: GRD = Rubber-insulated, rubber-sheathed, dynamic GC = Gummiert mit Schirm (rubber with screen) GÖU = Unarmoured J = Jacked (multi-sheath)Design impact (part 814 requirement):(1) Conductor geometry: Unscreened (813): Round stranding, compact Screened (814): May use special twisted lay to position screen Result: Slightly different outer diameter, same voltage rating(2) Screen position: Inner screen (before outer sheath): Best EMC performance Outer screen: Not typical for 0.6/1 kV (over-designed) GRDGCGÖU-J: Inner braid screen, between insulation and outer sheath(3) Grounding requirement: Part 813: No grounding specification (no screen to ground) Part 814: Screen MUST be grounded at cable entry point Critical for EMC compliance: Floating screen = no shielding benefitShielding effectiveness definition (part 814): Measured in decibels (dB) attenuation from 100 Hz to 1 GHz Typical requirement: >20 dB attenuation (reduces RF noise 100×) GRDGCGÖU-J tinned copper braid expected performance: @ 100 Hz: ~30 dB (good) @ 1 kHz: ~40 dB (excellent) @ 100 kHz: ~50 dB (very good) @ 1 MHz: ~45 dB (good, typical for braid)

2. Tinned Copper Braid Screen: EMC Protection Mechanism

The screen is specified as tinned copper braid, a time-proven EMC solution. Tinning protects the braid from oxidation and maintains conductivity:

Tinned Copper Braid Screen Design:Braid construction: Material: Pure copper wire (99.99% purity), fine strands Diameter: Each strand ~0.2–0.5 mm Count: Typically 8–16 strands twisted together Lay: Counter-helical (strands cross at ~45° to cable axis) Coverage: 80–90% physical coverage (allows some flex without tearing) Tinning (coating): 10–50 µm tin layer on copper Purpose: Corrosion protection + improved contact resistance Benefit: Oxidation prevented, low contact resistance with terminations maintainedEMC shielding mechanism:Faraday cage principle: Braid forms incomplete cage around conductors RF energy penetrating shield → induced currents in braid Induced currents create opposing magnetic field Result: RF energy attenuated (not perfectly blocked, but significantly reduced)Current distribution: At low frequency (<1 kHz): Magnetic field penetrates braid Attenuation moderate (~20–30 dB) At high frequency (>100 kHz): Skin effect confines currents to braid surface Attenuation high (~40–60 dB)Physical coverage impact: 80% coverage (GRDGCGÖU-J typical): Advantage: Light weight, excellent flexibility Trade-off: Lower attenuation at gaps between braid strands Result: “Good” EMC performance (not “excellent” which requires >95% coverage)Tinning benefit for festoon applications:Copper (bare) oxidation in outdoor conditions: Cu + O₂ → CuO (black oxide) at 20°C, 80% humidity Oxidation rate: ~0.5 µm/year in marine environment Contact resistance increase: 10–50× over 10 years (degrades EMC performance) Tinned copper resistance to oxidation: Tin layer acts as barrier Oxidation rate: <1% of bare copper Contact resistance increase: <2× over 20 years (excellent stability) Benefit: EMC performance remains consistent throughout cable lifeGrounding continuity (critical for EMC):Braid conductivity: Copper braid resistance: ~5–10 mΩ/meter Requirement (VDE 0250 part 814): <100 mΩ per meter (easily met) Contact resistance at termination: With tin coating: 0.5–1 mΩ (excellent) Without tin: 5–20 mΩ (higher, degrades with time) Implication: Tinned braid ensures reliable screen connection at both ends

3. Good EMC Characteristics: RF Immunity & Shielding Effectiveness

The specification states “good EMC characteristics.” This implies shielding effectiveness within VDE 0250 part 814 compliance range, suitable for noise-sensitive motor power applications:

EMC Performance Classification:EMC rating scale (VDE/EN standards): Basic: No shielding (part 813 unscreened) Fair: Partial coverage, 30–40 mm spacing in braid Good: 80–90% coverage, <5 mm maximum gap (GRDGCGÖU-J) Excellent: >95% coverage, all gaps <2 mm (tape-wrapped, higher cost) Outstanding: Foil + braid combination (not typical for 0.6/1 kV)"Good EMC" definition for GRDGCGÖU-J:Shielding effectiveness target: @ 50 kHz (VFD fundamental switching): >30 dB attenuation @ 500 kHz: >40 dB attenuation @ 5 MHz: >35 dB attenuation (typical peak range) Expected: Tinned copper braid achieves 35–50 dB across frequency rangeImmunity to external interference:Motor variable frequency drive (VFD) nearby: VFD RF emission: Typically 50–200 mV/m at cable distance Unshielded cable susceptibility: 100–500 mV induced noise Shielded cable (good EMC): 1–10 mV induced noise (50–100× reduction) Consequence: VFD-driven crane motor doesn’t interfere with control signals No false triggering of safety systems Data integrity in digital control systems maintainedRadiated immunity testing (per EN 61000-4-3):Test standard: Cable exposed to RF field 50 MHz–1 GHz Test field strength: 10 V/m typical Acceptance: No malfunction, signal corruption <2%GRDGCGÖU-J performance: Expected: Pass at 10 V/m easily (margin to higher field strength) Unshielded equivalent: May fail at 5 V/m (marginal immunity)Frequency-dependent behavior:At 50/60 Hz (power frequency): Shielding of AC magnetic field: ~10 dB (moderate) Significance: Not primary concern for 0.6/1 kV cables At 10 kHz (typical VFD switching): Shielding: ~35 dB (excellent) Significance: Critical for VFD motor circuit noise reduction At 100 kHz–1 MHz (harmonic range): Shielding: ~40–50 dB (very good) Significance: Prevents harmonic noise coupling to adjacent systems Real-world benefit: Entire festoon system RF "clean" despite multiple VFDs

4. Screen Grounding: Connection Strategy in Festoon Systems

Shielding only works if the screen is properly grounded. Festoon systems present unique challenges for screen termination:

Screen Grounding Strategy:Grounding requirement (VDE 0250 part 814): Both ends: Screen MUST be connected to ground/protective earth Frequency: At cable entry to power source AND at load equipment Impedance: Screen resistance to ground <1 Ω per connection pointSingle-point vs. multi-point grounding:Single-point grounding (typical for <10 m cable): Screen grounded at power source end only Load end: Screen left floating (isolated) Advantage: Prevents circulating ground current (hum reduction) Disadvantage: One point failure disconnects shield GRDGCGÖU-J application: Avoid for high-EMI environmentsMulti-point grounding (recommended for festoon >10 m): Screen grounded at both power source and load Intermediate: Grounding at supports/catenary attachment points Advantage: Redundancy; if one ground fails, others maintain shield Disadvantage: Small circulating current (100–300 mA at 50 Hz) acceptable GRDGCGÖU-J application: Standard practice for motor power supplyCirculating current calculation:When screen grounded at both ends: Impedance mismatch at cable termination creates loop Fundamental 50 Hz current: I = V_loop / Z_total Example: 50 m cable, 100 µV ground potential difference Cable impedance: ~0.02 Ω Loop impedance: ~0.2 Ω Current: 100 µV / 0.2 Ω ≈ 0.5 mA (negligible)High-frequency grounding:At switching frequencies (10 kHz VFD): Braid impedance: ~5 mΩ per connection Both-ends grounding creates low-impedance RF path RF current dissipates in ground system (good noise suppression) Result: Excellent RF shielding effectivenessFestoon system grounding topology:Motorized reel with rotating connector: Problem: Rotating contact creates intermittent ground connection Solution: Use slip-ring assembly on reel Screen connected through slip-ring to ground busbar Alternative: Conductive catenary structure carries screen current Cable screen bonded to catenary at multiple pointsCatenary-suspended application (typical festoon): Cable strung between support points 10–20 m apart Screen grounding at each support: Provides full redundancy Intermediate grounding reduces shield potential rise to <10 V Result: RF noise confined to cable; doesn't couple to adjacent systemsTerminal connection requirements: Screen termination: Use shielded D-Sub connector or screened gland Ground wire: 1.5–2.5 mm² dedicated ground conductor Connect screen braid to equipment ground lug Use crimp terminal (not solder, for reliability) Verification: Measure screen-to-ground resistance <0.1 Ω

5. Shielded vs. Unshielded Trade-offs: Cable Diameter & Weight

Adding screen increases cable outer diameter and weight. This trade-off must be evaluated for each application:

Physical Specification Differences:Unshielded (GRDGÖU-J part 813): Example: 3×50 mm² Outer diameter: 34.5 mm Cable weight: 2,535 kg/kmShielded (GRDGCGÖU-J part 814): Same: 3×50 mm² Outer diameter: 36.8 mm (6.7% larger) Cable weight: 3,101 kg/km (22% heavier)Size increase analysis:Diameter increase: 2.3 mm Screen coverage: ~80% (roughly 2–3 mm added thickness) Insulation unchanged: Diameter increase entirely from screenWeight increase: 566 kg/km (3.3 kg per 100 m spool) Copper braid: ~500 kg/km (typical tinned copper braid density) Outer sheath expansion: ~50 kg/km (thicker jacket needed) Other changes: MinimalPractical consequences:Reel capacity impact: Standard reel (10 km capacity): Unshielded 2,535 kg = 25.4 metric tons Shielded 3,101 kg = 31 metric tons Implication: Reel must be larger (mechanical limit ~50 ton reel) Tractor/winch capacity must increase ~22%Installation effort: Unshielded: Standard pulling speed 1–2 m/s (coiled in duct) Shielded: Slightly higher friction (braid surface rougher) Recommended pulling speed 0.5–1.5 m/s Time increase: ~10–15%Bending radius impact: Both cables: 4×D minimum (specified identically) Shielded cable consideration: Screen adds slight stiffness Actual bending ~5×D recommended for safety Margin reduced slightly, but acceptableCost-benefit analysis:When shielding IS necessary: – VFD motor power supply (EMC critical) – Within 10 m of control electronics – High-noise industrial environment Benefit: Noise reduction, system reliability → Justify +20% costWhen unshielded GRDGÖU-J sufficient: – Standard AC motor (no VFD) – Long cable runs (>20 m from noise sources) – Outdoor festoon systems (low EMI) Benefit: Cost savings, lighter weight, easier installation

6. Motor Power Supply Applications: VFD & Inverter Protection

GRDGCGÖU-J is specifically designed for motor power supply cables in festoon systems where VFD inverters and soft starters are common:

VFD Motor Power Supply Design:VFD circuit noise characteristics:Standard AC motor (direct mains): Noise spectrum: 50 Hz fundamental only Amplitude: <1% THD (total harmonic distortion) Cable sensitivity: Unshielded cable adequate (low noise susceptibility)VFD-driven motor (inverter output): Noise spectrum: 50 Hz fundamental + 5–50 kHz switching harmonics Amplitude: >30% THD (heavily distorted waveform) Dv/dt (voltage rise rate): >3 kV/µs (rapid switching transients) Cable sensitivity: Unshielded cable susceptible to coupling interference Risk without shielding: Induced voltages on adjacent signal cables False control signals, motor shutdown, safety failuresMotor cable proximity to control systems:Typical festoon layout: Power cable (motor): 3×50 mm² heavy current Control cable (PLC/safety): 4×2.5 mm² low-voltage logic Spacing: 5–10 cm parallel run (close proximity) Without shielding: VFD RF couples to control cable Control signal corruption: 5–50 mV induced noise Safe logic threshold: 2–5 V Risk: False triggering of safety interlocks With shielding (GRDGCGÖU-J): RF confined to power cable sheath Control cable immunity: <1 mV induced Safe margin: 200–2000× improvementSoft-start (reduced-voltage) motor applications:Soft-start topology: Thyristor-based ramping (smooth motor acceleration) Switching frequency: 100 Hz (synchronous with mains, low noise) Noise generation: <1% THD (minimal) Shielding benefit: Marginal (unshielded cable acceptable) GRDGCGÖU-J selection: Over-designed, but future-proof System may upgrade to full VFD later Shielded cable supports this evolutionCrane hoist motor (typical application):High-duty VFD motor: Power: 50–200 kW Current: 100–400 A @ 400V Switching frequency: 5–10 kHz Duty: Constant on/off cycling, rapid load changes Cable run: 20–50 m from VFD to festoon reel motor Shielding requirement (critical): Cable carries high current + switching transients Nearby control circuits: Hoist limit switches, load cells Risk without shielding: Multiple control failures GRDGCGÖU-J selection: Mandatory for reliabilityNoise reduction benefits (quantified):Without shielding (standard cable): Induced noise on adjacent 50 m control cable: @ 50 Hz: ~5 mV (harmless, within threshold) @ 10 kHz: ~50 mV (risky, may exceed logic threshold) @ 50 kHz: ~200 mV (dangerous, will cause false triggers)With GRDGCGÖU-J shielding: Same scenario, shielded power cable: @ 50 Hz: ~2 mV (negligible) @ 10 kHz: ~1 mV (negligible) @ 50 kHz: ~5 mV (negligible) Result: 40–50× improvement at critical frequencies

7. Single-Core Power & Multi-Core Configurations (17 SKUs)

Part NumberCores × mm²Ø (mm)Weight (kg/km)Tensile (N)AWG
03100G7L010M681×12022.51,3201,8004/0
03100G73030M653×5033.32,3602,2501
03100G72041M404G416.647524012
03100G72041M604G619.271030010
03100G72041M614G1021.59156008
03100G72051M615G10241,080—8
03100G72051M625G16281,530—6
03100G7C060M626×1628.21,6301,4406
03100G72037M623×16+3G2.5241,1457206
03100G72037M633×25+3G427.21,6151,1254
03100G72037M643×35+3G631.22,1501,5752
03100G72037M653×50+3G1036.83,1012,2501
03100G72037M663×70+3G1042.74,1053,1502/0
03100G72037M673×95+3G1645.95,0304,2753/0
03100G72037M683×120+3G1650.65,8905,4004/0
Screened SKU Portfolio: 17 configurations optimized for motor power supply and control. Single-core (1×120), 3-phase + ground (3×16 to 3×120), control lines (4G4 to 5G16), and 6-core bundle. All feature tinned copper braid screen and EPR 3GI3 insulation per VDE 0250 part 814.

8. Installation & Grounding Best Practices

Screen Grounding Protocol: Both cable ends MUST be grounded to protective earth. Use shielded connectors and ferrule-terminated ground conductors. Screen resistance to ground: <0.1 Ω per connection. Multi-point grounding recommended for cables >10 m to maintain EMC performance. Verify continuity with ohmmeter before energizing.
High-Speed Festoon Installation: GRDGCGÖU-J rated 240 m/min supports aggressive motorized reel winding. Braid compression at high speed acceptable (temporary, stress relieved during unwind). Screen integrity unaffected by cycling. Expect 5–7 year service life in continuous duty (vs. 10+ years for stationary cables).
Motor Power Applications: Ideal for VFD-driven hoist motors, variable-speed cranes, and soft-start equipment. EMC compliance requires proper screen termination. When combining shielded power (GRDGCGÖU-J) with control cables, maintain minimum 50 mm separation or co-route in dedicated cable tray for maximum noise isolation. Avoid bundling screened power directly with analog signal lines.