HIGH-VOLTAGE XLPE POWER CABLES
36/60÷69(72.5) kV
Professional Wind Turbine Cable Solutions — XRUHKXS, 2XS(FL)2Y, N2XS(FL)2Y Series conforming to IEC 60840 and DIN VDE 0276-632 standards. Engineered for offshore wind farms, power transmission networks, and renewable energy infrastructure.
Technical Overview
High-voltage XLPE (Cross-Linked Polyethylene) insulated power cables rated at 36/60÷69(72.5) kV represent the backbone of modern power transmission infrastructure. These cables are specifically engineered for applications requiring exceptional electrical performance, thermal stability, and mechanical durability under demanding operational conditions.
The cable designations XRUHKXS, 2XS(FL)2Y, and N2XS(FL)2Y indicate specific construction standards and regional compliance requirements. According to the International Electrotechnical Commission, IEC 60840 defines test methods and performance requirements for high-voltage power cable systems with extruded insulation, covering systems designed for rated voltages above 30 kV (Um = 36 kV) up to and including 150 kV (Um = 170 kV).
Voltage Rating
Nominal voltage U₀/U(Um): 36/60(72.5) kV to 40/69(72.5) kV. Maximum system voltage 72.5 kV with conductor operating temperature up to 90°C.
Conductor Range
Cross-sectional area from 120 mm² to 3000 mm² with round stranded (RM/RMC) or Milliken segmented (RMS) copper conductor designs per IEC 60228 Class 2.
Insulation System
Triple-extruded XLPE insulation with semi-conductive conductor and insulation screens. Nominal insulation thickness: 10.0 mm for enhanced electrical stress management.
Applications
Wind turbine installations, offshore/onshore wind farms, substation interconnections, underground power distribution, and renewable energy grid integration.
Cable Type Designations
XRUHKXS
According to IEC 60840
Single-core high-voltage cable with XLPE insulation, copper wire screen with longitudinal water barrier, and PE outer sheath. Designed for fixed installations in power transmission systems.
2XS(FL)2Y
According to IEC 60840
XLPE insulated cable with copper wire screen, longitudinally applied laminated sheath (FL), and HDPE outer covering. The “2” prefix indicates XLPE insulation material.
N2XS(FL)2Y
According to DIN VDE 0276-632
German standard designation for XLPE insulated high-voltage cable. “N” indicates standardized construction, “(FL)” denotes longitudinal water barrier, “2Y” specifies PE outer sheath.
Cable Construction Standards
These high-voltage cables are manufactured in accordance with multiple international standards to ensure global compatibility and performance reliability. As noted by industry sources, compliance with IEC 60840 standards ensures consistent electrical and mechanical performance across high-voltage networks, representing critical infrastructure investments designed for decades of reliable service.
Cable Construction Details
-
1Conductor: Copper, round stranded compacted (RM/RMC) or Milliken segmented (RMS) design per IEC 60228 Class 2. Cross-sections from 120 mm² to 3000 mm² available.
-
2Conductor Screen: Extruded semi-conductive XLPE compound, providing uniform electric field distribution at the conductor surface.
-
3Insulation: Cross-linked polyethylene (XLPE), nominal thickness 10.0 mm. Maximum conductor temperature 90°C continuous, 250°C short-circuit.
-
4Insulation Screen: Extruded semi-conductive XLPE compound bonded to insulation, ensuring controlled electric stress at insulation boundary.
-
5Metallic Screen: Copper wire screen with cross-sections of 35 mm² or 50 mm². Short-circuit rating: 7.4 kA/s (35 mm²) or 10.6 kA/s (50 mm²).
-
6Water Barrier (FL): Longitudinally applied laminated aluminum/PE tape providing radial water blocking capability.
-
7Outer Sheath: High-density polyethylene (HDPE) or PE, providing mechanical protection and environmental resistance.
Technical Note: Conductor Types
- RM (RMC) — Round Multiwire Conductor (Compacted), Class 2 per IEC 60228
- RMS (Milliken type) — Round Multiwire Segmented Conductor for reduced skin effect in large cross-sections
- SPB — Single Point Bonded earthing method
- CB — Cross Bonded earthing method for long cable routes
- De — Cable outer diameter for spacing calculations
Physical Specifications
The following table presents comprehensive dimensional and mechanical data for the complete range of conductor sizes. All specifications conform to IEC 60840:2020 requirements.
| Cross Section (mm²) | Conductor Diameter (mm) | Insulation Thickness (mm) | Diameter Over Insulation (mm) | Screen Cross Section (mm²) | Diameter Over Screen (mm) | Outer Diameter De (mm) | Cable Weight (kg/km) | Max Pulling Force (kN) | Min Bending Radius (m) |
|---|---|---|---|---|---|---|---|---|---|
| 120RM | 12.8 + 0.3 | 10.0 | 34.0 | 35 | 37.8 | 44.1 | 2,670 | 6.0 | 1.10 |
| 150RM | 14.25 + 0.3 | 10.0 | 35.4 | 35 | 39.2 | 45.6 | 2,980 | 7.5 | 1.14 |
| 185RM | 15.85 + 0.3 | 10.0 | 37.0 | 35 | 40.8 | 47.2 | 3,370 | 9.25 | 1.18 |
| 240RM | 18.5 + 0.3 | 10.0 | 39.7 | 35 | 43.5 | 50.0 | 3,990 | 12.0 | 1.25 |
| 300RM | 20.3 + 0.4 | 10.0 | 41.5 | 35 | 45.3 | 51.8 | 4,610 | 15.0 | 1.30 |
| 400RM | 23.5 + 0.4 | 10.0 | 45.1 | 35 | 49.3 | 56.2 | 5,650 | 20.0 | 1.40 |
| 500RM | 26.3 + 0.5 | 10.0 | 47.9 | 35 | 52.1 | 59.2 | 6,780 | 25.0 | 1.48 |
| 630RM | 30.0 + 0.5 | 10.0 | 51.8 | 35 | 56.0 | 63.3 | 8,190 | 31.5 | 1.58 |
| 800RM | 34.4 + 0.7 | 10.0 | 56.2 | 35 | 60.4 | 67.9 | 9,940 | 40.0 | 1.70 |
| 1000RM | 38.3 + 0.7 | 10.0 | 60.5 | 35 | 65.1 | 73.0 | 12,130 | 50.0 | 1.83 |
| 1200RMS | 42.0 + 0.8 | 10.0 | 66.0 | 50 | 70.6 | 78.9 | 14,530 | 60.0 | 1.97 |
| 1400RMS | 45.8 + 0.8 | 10.0 | 69.8 | 50 | 74.4 | 82.9 | 16,620 | 70.0 | 2.08 |
| 1600RMS | 49.0 + 1.2 | 10.0 | 73.0 | 50 | 77.6 | 86.3 | 18,520 | 80.0 | 2.16 |
| 1800RMS | 52.1 + 1.0 | 10.0 | 76.1 | 50 | 80.7 | 89.8 | 20,880 | 90.0 | 2.25 |
| 2000RMS | 54.4 + 1.0 | 10.0 | 78.4 | 50 | 83.0 | 92.1 | 22,460 | 100.0 | 2.31 |
| 2500RMS | 60.5 + 1.0 | 10.0 | 85.5 | 50 | 90.5 | 100.2 | 27,490 | 100.0 | 2.50 |
| 3000RMS | 68.4 + 1.0 | 10.0 | 93.4 | 50 | 98.4 | 108.7 | 33,760 | 100.0 | 2.72 |
Electrical Parameters
Electrical characteristics are critical for system design, including conductor resistance, capacitance, inductance, and current-carrying capacity. Data is provided for both buried (in ground) and aerial (in air) installation conditions.
| Cross Section (mm²) | Conductor R DC 20°C (Ω/km) | Conductor R AC 90°C (Ω/km) | Screen R DC 20°C (Ω/km) | Screen R DC 80°C (Ω/km) | Electric Field Stress (kV/mm) | Short-Circuit Conductor (kA/s) | Short-Circuit Screen (kA/s) | Capacitance (μF/km) | Inductance (mH/km) |
|---|---|---|---|---|---|---|---|---|---|
| 120RM | 0.1530 | 0.1957 | 0.526 | 0.650 | 5.8 / 2.39 | 17.4 | 7.4 | 0.150 | 0.621 |
| 150RM | 0.1240 | 0.1589 | 0.526 | 0.650 | 5.62 / 2.44 | 21.8 | 7.4 | 0.160 | 0.606 |
| 185RM | 0.0991 | 0.1273 | 0.526 | 0.650 | 5.45 / 2.5 | 26.8 | 7.4 | 0.171 | 0.592 |
| 240RM | 0.0754 | 0.0975 | 0.526 | 0.650 | 5.22 / 2.59 | 34.7 | 7.4 | 0.190 | 0.572 |
| 300RM | 0.0601 | 0.0784 | 0.526 | 0.650 | 5.09 / 2.64 | 43.4 | 7.4 | 0.203 | 0.561 |
| 400RM | 0.0470 | 0.0622 | 0.526 | 0.650 | 4.89 / 2.72 | 57.8 | 7.4 | 0.228 | 0.548 |
| 500RM | 0.0366 | 0.0497 | 0.526 | 0.650 | 4.77 / 2.78 | 72.2 | 7.4 | 0.247 | 0.536 |
| 630RM | 0.0283 | 0.0400 | 0.526 | 0.650 | 4.64 / 2.85 | 90.8 | 7.4 | 0.273 | 0.523 |
| 800RM | 0.0221 | 0.0332 | 0.526 | 0.650 | 4.52 / 2.91 | 115.3 | 7.4 | 0.303 | 0.509 |
| 1000RM | 0.0176 | 0.0283 | 0.378 | 0.467 | 4.43 / 2.97 | 144.0 | 10.6 | 0.332 | 0.502 |
| 1200RMS | 0.0151 | 0.0224 | 0.378 | 0.467 | 4.34 / 3.02 | 172.7 | 10.6 | 0.369 | 0.500 |
| 1400RMS | 0.0129 | 0.0200 | 0.378 | 0.467 | 4.28 / 3.06 | 201.4 | 10.6 | 0.395 | 0.492 |
| 1600RMS | 0.0113 | 0.0184 | 0.378 | 0.467 | 4.24 / 3.08 | 230.1 | 10.6 | 0.416 | 0.487 |
| 1800RMS | 0.0101 | 0.0172 | 0.378 | 0.467 | 4.21 / 3.1 | 258.8 | 10.6 | 0.437 | 0.482 |
| 2000RMS | 0.0090 | 0.0161 | 0.378 | 0.467 | 4.19 / 3.12 | 287.4 | 10.6 | 0.453 | 0.479 |
| 2500RMS | 0.0072 | 0.0143 | 0.378 | 0.467 | 4.13 / 3.16 | 359.1 | 10.6 | 0.500 | 0.474 |
| 3000RMS | 0.0060 | 0.0132 | 0.378 | 0.467 | 4.07 / 3.2 | 430.8 | 10.6 | 0.553 | 0.466 |
| Cross Section (mm²) | In Ground (A) | In Air (A) | ||
|---|---|---|---|---|
| Flat Formation SPB/CB ① | Trefoil Formation SPB/CB ② | Flat Formation SPB/CB ① | Trefoil Formation SPB/CB ② | |
| 120RM | 390 | 370 | 480 | 415 |
| 150RM | 440 | 415 | 545 | 470 |
| 185RM | 495 | 470 | 625 | 540 |
| 240RM | 575 | 545 | 740 | 635 |
| 300RM | 650 | 615 | 850 | 730 |
| 400RM | 745 | 700 | 985 | 845 |
| 500RM | 850 | 795 | 1,145 | 975 |
| 630RM | 970 | 895 | 1,330 | 1,120 |
| 800RM | 1,090 | 1,000 | 1,535 | 1,275 |
| 1000RM | 1,210 | 1,090 | 1,720 | 1,420 |
| 1200RMS | 1,335 | 1,235 | 1,915 | 1,625 |
| 1400RMS | 1,435 | 1,320 | 2,090 | 1,760 |
| 1600RMS | 1,520 | 1,385 | 2,245 | 1,880 |
| 1800RMS | 1,590 | 1,440 | 2,380 | 1,980 |
| 2000RMS | 1,660 | 1,490 | 2,490 | 2,060 |
| 2500RMS | 1,790 | 1,595 | 2,720 | 2,240 |
| 3000RMS | 1,930 | 1,695 | 3,005 | 2,440 |
Installation Configuration Notes
- ① Flat formation: cables in flat formation, distance between cables = 2 × De
- ② Trefoil formation: cables in trefoil formation, distance between cables = De
- Ampacity values based on: Conductor temperature 90°C, soil temperature 20°C, burial depth 1200mm, soil thermal resistivity 1.0 K·m/W
- Air installation assumes ambient temperature 30°C with natural convection cooling
Wind Turbine Cable Applications
The 36/60(72.5) kV XLPE cables are extensively deployed in wind energy infrastructure, particularly for connecting wind turbines to collector substations and integrating renewable energy into existing grid systems. The transition from 33kV to 66kV array cables represents a significant advancement in offshore wind farm efficiency.
Industry research indicates that higher voltage cables can increase transmittable power by over 100%, enabling the development of larger arrays with more turbines per array circuit. The 66kV voltage level has become the standard for modern offshore wind farm inter-array cabling, with cables typically ranging from 150mm² to 800mm² conductor sizes.
Offshore Wind Farms
Inter-array cables connecting wind turbines to offshore substations. Dynamic cable sections accommodate floating platform movements. Typical cable lengths: 1.5 km or longer per circuit.
Onshore Wind Installations
Underground collector cables from turbine bases to substation. Direct burial or ducted installation methods. Designed for maintenance-free 30+ year service life.
Substation Connections
High-capacity feeder cables connecting collector substations to grid interconnection points. Supports both single-point bonded and cross-bonded earthing configurations.
Grid Integration
Export cables linking wind farms to shore-based grid infrastructure. Compatible with HVAC transmission systems up to 72.5 kV maximum system voltage.
Key Performance Advantages
XLPE insulated high-voltage cables offer numerous advantages for wind turbine applications compared to alternative technologies:
-
✓Superior Thermal Performance: Maximum continuous conductor temperature of 90°C enables higher current density and reduced cable cross-sections compared to PVC or EPR alternatives.
-
✓Excellent Dielectric Properties: Low dielectric constant (ε ≈ 2.3) and dissipation factor minimize capacitive charging current on long cable routes.
-
✓Mechanical Robustness: Cross-linked molecular structure provides superior tensile strength, elongation, and impact resistance for installation in harsh environments.
-
✓Environmental Resistance: Excellent resistance to moisture, chemicals, UV radiation, and marine environments without oil leakage concerns.
-
✓Long Service Life: Type-tested per IEC 60840 to demonstrate 30+ year operational reliability under cyclic loading conditions.
Standards Compliance
Anhui Feichun Special Cable Co., Ltd. manufactures high-voltage XLPE cables in full compliance with international and regional standards to ensure global market acceptance and installation compatibility.
IEC 60840:2020
International Standard
Power cables with extruded insulation and their accessories for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) — Test methods and requirements.
DIN VDE 0276-632
German National Standard
Power cables with extruded insulation for rated voltages from 36 kV up to 150 kV. Harmonized with HD 632 (CENELEC harmonization document).
IEC 60228
Conductor Standard
Conductors of insulated cables — specifies conductor requirements for Class 2 stranded conductors used in high-voltage power cables.
IEC 60287
Current Rating Standard
Electric cables — Calculation of the current rating. Provides methodology for determining continuous current-carrying capacity under various installation conditions.
Testing Requirements
Per IEC 60840, cables undergo comprehensive type testing, routine testing, and sample testing to verify performance and reliability:
Type Test Sequence (30-Year Life Simulation)
- Partial discharge test at ambient and elevated temperature
- Tan δ measurement at various temperatures
- Heating cycle voltage test (20 cycles at 2U₀)
- Lightning impulse voltage test (±10 impulses)
- Examination of completed cable
Contact Anhui Feichun Special Cable Co., Ltd.
安徽飞纯特种电缆有限公司 — Your trusted partner for high-voltage XLPE power cable solutions. Contact our technical team for project consultation, specifications, and quotations.
Technical Support
[email protected]Sales — Zihao Yang
[email protected]Sales — Ziyu Huang
[email protected]References & Resources
For additional information on high-voltage cable technology, installation practices, and industry standards, the following resources are recommended:
-
1International Electrotechnical Commission: IEC 60840:2020 — Power cables with extruded insulation and their accessories for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV)
-
2DIN VDE Standards: DIN VDE 0276-632 — German standard for high-voltage extruded insulation power cables
-
3Industry Partner: Feichun Port and Maritime Cables — EU Cable Standards Guide
-
4CENELEC: HD 632 — Harmonization document for power cables with extruded insulation for rated voltages from 36 kV to 150 kV