What is PROTOMONT EMV-FC (N)SSHCOEU 1 kV for Variable Frequency Converter?

Complete technical guide to EMC-optimized motor power supply cables for frequency converter controlled drives in mining, construction, and industrial applications | Anhui Feichun Special Cable Co., Ltd. (安徽飞纯特种电缆有限公司)

What is PROTOMONT EMV-FC (N)SSHCOEU 1 kV for Variable Frequency Converter?
Complete technical guide to EMC-optimized motor power supply cables for frequency converter controlled drives in mining, construction, and industrial applications | Anhui Feichun Special Cable Co., Ltd. (安徽飞纯特种电缆有限公司)
What is PROTOMONT EMV-FC (N)SSHCOEU 1 kV for Variable Frequency Converter? Complete technical guide to EMC-optimized motor power supply cables for frequency converter controlled drives in mining, construction, and industrial applications | Anhui Feichun Special Cable Co., Ltd. (安徽飞纯特种电缆有限公司)
What is PROTOMONT EMV-FC (N)SSHCOEU 1 kV for Variable Frequency Converter? | Complete Technical Guide – Anhui Feichun Special Cable Co., Ltd.

What is PROTOMONT EMV-FC (N)SSHCOEU 1 kV for Variable Frequency Converter?

Complete technical guide to EMC-optimized motor power supply cables for frequency converter controlled drives in mining, construction, and industrial applications | Anhui Feichun Special Cable Co., Ltd. (安徽飞纯特种电缆有限公司)

EMC Optimized Shield MSHA P-189-3 Certified EAC Certificate DIN VDE 0250-812

Introduction to PROTOMONT EMV-FC (N)SSHCOEU 1 kV Cable

The PROTOMONT EMV-FC (N)SSHCOEU represents a specialized category of EMC-optimized rubber-sheathed flexible cables engineered specifically for motor power supply applications in Variable Frequency Drive (VFD) controlled systems. These cables address one of the most significant challenges in modern industrial power distribution: electromagnetic compatibility in high-frequency switching environments.

Variable Frequency Drives have revolutionized motor control in mining, construction, and industrial applications by providing precise speed regulation and energy efficiency. However, VFDs also introduce unique electrical challenges. As noted by cable engineering specialists, VFDs require specialized cabling to ensure reliable operation, minimize electromagnetic interference, and maintain safety for the system as a whole, because selecting the right cables and proper installation directly impact performance and equipment longevity (source: KEB America).

The PROTOMONT EMV-FC series specifically addresses these challenges through its EMC-optimized concentric braid screen design, making it the ideal choice for frequency converter controlled drives in the mining industry, on construction sites, and similar applications with heavy mechanical stresses.

Why EMC Shielding Matters for VFD Applications

Variable frequency drives operate using high-frequency Pulse Width Modulation (PWM), typically at switching frequencies of 2-16 kHz. This creates electromagnetic noise that can interfere with nearby control systems, communication cables, and sensitive electronic equipment. The EMC-optimized shield in the PROTOMONT EMV-FC cable contains this electromagnetic interference (EMI) within the cable, protecting both the surrounding environment and the motor system from harmful electrical noise.

Purpose and Primary Applications

The PROTOMONT EMV-FC (N)SSHCOEU 1 kV cable is purpose-engineered for powering motors controlled by variable frequency converters (inverters) in demanding industrial environments. Its unique construction combines the mechanical durability required for mining applications with the electromagnetic shielding necessary for VFD systems.

Primary Application Environments

This cable excels in multiple demanding scenarios where both mechanical stress and EMC performance are critical. For fixed installation applications, it provides permanent motor connections in processing plants, conveyor systems, and pump stations. In flexible operation applications, it serves mobile equipment including cable booms and connections between upper and lower cars on material handling systems. The cable is specifically designed for mining industry applications including underground mining equipment, coal cutting machines, and material transport systems. It also supports construction site applications where mobile cranes, concrete pumps, and drilling equipment require VFD-controlled motors.

EMC VFD cable has been specially designed for Variable Frequency Drive Motors and installations where it is necessary to limit the effects of electromagnetic interference (EMI), as documented by industry sources (source: Belcom Cables).

Continuous Movement Applications

A distinctive feature of the PROTOMONT EMV-FC cable is its suitability for continuous movement applications. The cable is specifically designed for laying on material handling equipment, even with continuous movement such as in cable booms or as connection between upper and lower cars. This makes it ideal for automated mining systems and robotic material handling where cables must flex continuously while maintaining both electrical integrity and EMC performance.

Submersion Capability

The cable is rated for submersion in water up to 40°C at depths of approximately 10 meters. This feature is particularly valuable in mining operations where groundwater, flooding, or dewatering pump applications may expose cables to water. The combination of water resistance and EMC shielding makes this cable unique in its ability to serve VFD-controlled submersible pumps and similar equipment.

Key Characteristics and Features

The PROTOMONT EMV-FC (N)SSHCOEU cable incorporates several advanced features that distinguish it from standard mining cables and conventional VFD cables.

EMC-Optimized Shielding System

The cable features a concentric braid of tinned copper wires specifically optimized for electromagnetic compatibility. This shield design is critical for VFD applications because it provides a low-impedance path for high-frequency common mode currents generated by the inverter’s PWM switching.

For effective noise containment, shielded VFD cables should include a copper braid, foil shield, or both, and ideally symmetrical grounds to cancel out high-frequency emissions. Copper braid provides low impedance at high frequencies (source: KEB America).

Shield Performance Parameters

The tinned copper braid screen provides excellent coverage (typically 85%+) and low transfer impedance, ensuring effective containment of electromagnetic emissions across the frequency range generated by modern VFDs. The tinning of the copper wires provides corrosion resistance essential for long-term performance in mining environments.

Split Protective Earth Conductor Design

A unique feature of the PROTOMONT EMV-FC design is the arrangement of three power cores laid up with protective earth conductors split into three in the outer interstices. This configuration serves multiple purposes. The split earth conductors provide symmetrical grounding essential for EMC performance in VFD applications. The arrangement maintains cable balance and reduces electromagnetic asymmetry. It provides adequate cross-sectional area for fault current carrying capacity while enabling optimal cable geometry for both mechanical flexibility and electrical performance.

Dual Voltage Rating Flexibility

The cable carries a rated voltage of U₀/U = 0.6/1 kV and is also specifically permitted for U₀/U = 640/1140V systems. This dual rating provides flexibility for different mining electrical system configurations commonly found worldwide.

Table 1: Key Characteristics Summary
FeatureSpecificationBenefit
EMC ShieldConcentric tinned copper braidHigh-frequency noise containment
Earth ConductorSplit into 3 in outer intersticesSymmetrical grounding, EMC optimization
Installation TypeFixed & Flexible operationVersatile deployment options
Water Resistance10m depth at 40°CSubmersible pump applications
CertificationsMSHA P-189-3, EACGlobal mining compliance
Flame RetardanceIEC 60332-1-2Underground safety compliance

Material Structure and Construction

The construction of the PROTOMONT EMV-FC (N)SSHCOEU cable represents a carefully engineered multi-layer system where each component serves specific functional purposes for both mechanical performance and electromagnetic compatibility.

Cable Cross-Section Layer Structure

1 Finely stranded tinned copper conductor (Class 5)
2 PROTOLON EPR insulation (3GI3 compound)
3 Three power cores + split PE conductors
4 EMC-optimized concentric tinned copper braid screen
5 EPR inner sheath (GM1B vulcanized rubber)
6 PROTOFIRM CR outer sheath (5GM5 compound) – Yellow

Conductor Design

The conductor core utilizes finely stranded tinned copper conforming to Class 5 flexibility standards per DIN EN 60228. The tinning provides several advantages over bare copper. The tin coating prevents oxidation and corrosion of the copper strands, ensuring long-term electrical integrity. Tinned conductors provide more reliable and lower-resistance connections at termination points. The tin layer reduces galvanic corrosion when exposed to moisture or dissimilar metals, and Class 5 stranding enables the cable to withstand repeated flexing without conductor fatigue.

Table 2: Conductor Specifications per DIN EN 60228
ParameterSpecificationIndustry Standard
MaterialElectrolytic copper, tinnedDIN EN 60228
Flexibility ClassClass 5 (finely stranded)IEC 60228
Strand ConfigurationMultiple fine wiresVDE 0295
Surface TreatmentHot-dip or electroplated tinCorrosion protection

Insulation System: PROTOLON EPR Technology

The insulation layer employs PROTOLON, a specialized Ethylene Propylene Rubber (EPR) compound designated as type 3GI3. This insulation material is specifically formulated for high-frequency applications and provides excellent dielectric properties across the frequency range encountered in VFD motor circuits.

EPR insulation is widely recognized as the optimal choice for VFD applications. EPR insulation combines flexibility with chemical resistance for portable mining equipment cables, offering excellent resistance to ozone, chemicals, and temperature extremes common in mining environments (source: TOT Cables).

Core identification follows a standardized system using natural coloring with black figures, enabling rapid and reliable circuit identification during installation and maintenance operations.

EMC Shield Construction

The EMC-optimized shield consists of a concentric braid of tinned copper wires applied over the assembled cores. This construction is critical for VFD applications because the braided structure provides excellent high-frequency shielding effectiveness. The concentric application ensures uniform coverage around the entire cable assembly. Tinned copper provides both excellent conductivity and corrosion resistance. The braid construction allows the cable to maintain flexibility while providing effective shielding.

Sheath System

The dual-sheath system provides both mechanical protection and environmental resistance. The inner sheath uses vulcanized EPR rubber compound type GM1B, providing mechanical protection over the EMC braid and maintaining cable geometry. The outer sheath employs PROTOFIRM synthetic elastomer compound (e.g., CR – chloroprene rubber) designated as type 5GM5, with the characteristic yellow color for visibility. This outer sheath delivers exceptional abrasion resistance for trailing and dragging applications, resistance to oils, chemicals, and ozone, flame retardance per IEC 60332-1-2, and weather resistance for outdoor installations.

Electrical Parameters and Specifications

The electrical characteristics of the PROTOMONT EMV-FC (N)SSHCOEU cable are optimized for both power transmission and EMC performance in VFD applications.

Voltage Ratings

Table 3: Complete Electrical Specifications
ParameterValueNotes
Rated Voltage U₀/U0.6/1 kV (600/1000V)Primary rating
Alternative Rating640/1140VAlso permitted
Max. Operating Voltage AC0.7/1.2 kVMaximum continuous AC
Max. Operating Voltage DC0.9/1.8 kVMaximum continuous DC
AC Test Voltage (Main Cores)5 kV (5 min.)Factory acceptance test

The 5 kV test voltage for main cores is notably higher than standard 1 kV rated cables, providing an additional safety margin important for VFD applications where voltage spikes can occur. A key advantage of VFD cables is their ability to withstand high voltage spikes, often in excess of the voltage rating of the cable, under the normal operating conditions of high-frequency applications (source: Eland Cables).

VFD-Specific Electrical Considerations

The cable’s electrical design addresses several VFD-specific challenges. The PWM output from VFDs creates high dV/dt (rate of voltage change) that can cause voltage doubling at the motor terminals, particularly with long cable runs. The PROTOLON insulation system is specifically formulated to withstand these voltage transients. The symmetrical arrangement of power cores and split earth conductors helps minimize circulating currents and common-mode noise. The EMC braid provides a low-impedance path for high-frequency currents generated by the inverter’s switching, essential for meeting EMC requirements and protecting nearby equipment.

Cable Length Considerations for VFD Applications

The maximum cable length between VFD and motor affects system performance. Longer cables increase reflected wave voltage and ground fault currents. Consult the VFD manufacturer’s guidelines for maximum cable length recommendations. In general, cables exceeding 50-100 meters may require output filters or reactors to protect the motor.

Thermal Parameters and Operating Conditions

Temperature management is critical in VFD applications where cables may be subject to both ambient temperature extremes and heat generated by high-frequency currents.

Table 4: Thermal Performance Specifications
ParameterValueApplication Consideration
Max. Conductor Operating Temperature90°CContinuous operation limit
Max. Short Circuit Temperature250°CTransient fault condition
Ambient Temperature (Fixed Installation)-40°C to +80°CStatic mounting conditions
Ambient Temperature (Flexible Operation)-25°C to +60°CDynamic/moving applications
Max. Water Temperature (Submersion)40°CFor 10m depth rating

Temperature Range Analysis

The difference between fixed installation (-40°C to +80°C) and flexible operation (-25°C to +60°C) temperature ranges reflects the mechanical stress considerations at temperature extremes. At very low temperatures, rubber compounds become stiffer, and repeated flexing could cause damage. The flexible operation range ensures the cable materials remain sufficiently pliable for safe dynamic use.

Temperature variations present another significant challenge, with underground environments potentially ranging from near-freezing conditions in some mines to elevated temperatures approaching 85°C in deep, geothermally active locations. Surface operations may experience even greater temperature extremes (source: Amplex Mining Australia).

Mechanical Parameters and Performance

The mechanical specifications of the PROTOMONT EMV-FC (N)SSHCOEU cable are designed to withstand the demanding conditions of mining and construction site applications while maintaining EMC shield integrity.

Table 5: Mechanical Performance Specifications
ParameterSpecificationIndustry Standard Reference
Max. Tensile Load on Conductor15 N/mm²DIN VDE 0298-3
Torsional Stress Tolerance±25°/mCable twisting allowance
Minimum Bending RadiusPer DIN VDE 0298-3Typically 6-8× cable diameter
Max. Submersing Depth~10 metersAt water temp ≤40°C

Torsional Stress Considerations

The ±25°/m torsional stress specification is particularly important for EMC-shielded cables. Excessive twisting can damage the concentric copper braid, compromising its shielding effectiveness. Mining operations using this cable on reeling systems or in cable boom applications must ensure that cable routing and handling procedures remain within this tolerance.

This cable is designed for torsional stress of ±25°/m, ensuring excellent durability in reeling drum applications commonly used in industrial and mining environments (source: Reeling Cable Technical Resources).

Mechanical Protection for EMC Shield

The dual-sheath construction provides critical protection for the EMC braid. The inner EPR sheath cushions the braid from internal cable movements during flexing, while the PROTOFIRM outer sheath protects against external abrasion and impact. This protection is essential for maintaining long-term EMC performance in demanding applications.

Standards Compliance and Certifications

The PROTOMONT EMV-FC (N)SSHCOEU cable meets comprehensive international standards ensuring safety and performance in global mining operations.

Table 6: Applicable Standards and Certifications
Certification/StandardDescriptionApplication
DIN VDE 0250 part 812Base construction standardMining cable specifications
MSHA P-189-3Mine Safety and Health AdministrationUS mining approval
EAC CertificateEurasian Conformity markRussia, Belarus, Kazakhstan, etc.
DIN EN 60228 / IEC 60228Conductor requirementsClass 5 flexible conductors
IEC 60332-1-2Flame retardance testingFire safety
IEC 60811-404Oil resistance testingChemical resistance

MSHA Certification Significance

The MSHA P-189-3 certification is crucial for mining operations in the United States. This certification indicates that the cable has been tested and approved by the Mine Safety and Health Administration for use in underground and surface mining applications. MSHA approval requires rigorous testing of flame resistance, mechanical properties, and electrical safety parameters.

In the US, trailing cables for use in underground coal mines must meet MSHA flame-resistance standards and undergo periodic inspections to verify continued compliance (source: Amplex Mining Cable Selection Guide).

EAC Certificate for Eurasian Markets

The EAC (Eurasian Conformity) certificate demonstrates compliance with the technical regulations of the Eurasian Economic Union, covering Russia, Belarus, Kazakhstan, Armenia, and Kyrgyzstan. This certification is essential for mining operations in the extensive mineral extraction industries of these regions.

Safety Thresholds and Critical Limits

Understanding and respecting the safety thresholds of the PROTOMONT EMV-FC (N)SSHCOEU cable is essential for safe operation of VFD motor systems.

Critical Safety Thresholds for VFD Applications

VFD systems introduce unique safety considerations beyond standard motor circuits. The combination of high-frequency switching, potential voltage spikes, and electromagnetic fields requires careful attention to cable specifications and installation practices.

Table 7: Critical Safety Thresholds
ParameterMaximum LimitConsequence of Exceeding
Conductor Temperature90°CInsulation degradation, EMC shield damage
Short-Circuit Temperature250°C (transient)Permanent damage if exceeded
Operating Voltage AC1.2 kVInsulation breakdown risk
Operating Voltage DC1.8 kVInsulation breakdown risk
Tensile Stress15 N/mm²Conductor/shield damage
Torsional Stress±25°/mEMC braid damage, shield failure
Submersion Depth~10 metersWater ingress, electrical failure

EMC-Specific Safety Considerations

Beyond standard electrical safety, EMC-shielded VFD cables have additional safety considerations. Proper shield grounding is essential for both EMC performance and personnel safety. The shield must be bonded to ground at both the VFD and motor ends using 360° bonding methods for optimal high-frequency performance. The EMC shield can carry significant high-frequency currents. If the shield becomes damaged or poorly connected, these currents can find alternative paths that may create interference or safety hazards. The combination of motor cable and its EMC shield creates a transmission line that must be properly terminated. Improper termination can result in standing waves, voltage reflections, and electromagnetic emissions.

Installation and Usage Precautions

Proper installation is critical for achieving both the mechanical performance and EMC effectiveness of the PROTOMONT EMV-FC (N)SSHCOEU cable.

EMC-Specific Installation Requirements

VFD cable installations require attention to electromagnetic compatibility considerations beyond standard cable installation practices. The cable shield must be connected at both ends (VFD and motor) using EMC cable glands that provide 360° contact with the shield braid. Standard cable glands with pigtail ground connections do not provide adequate high-frequency grounding. Standard separation distances must be maintained between VFD motor cables and sensitive signal or control cables. Parallel runs of unshielded signal cables should be avoided, and crossings should be made at 90° angles when separation is not possible. Both the VFD and motor should be mounted on a common grounding plane, with the cable shield bonded to this plane at both ends. The grounding system must provide low impedance at high frequencies.

Good EMC practices such as 360° bonding of the shields are recommended, in order for low impedance for high frequency to be provided. Cable shield must be grounded at both ends, motor and variable frequency drive (source: Variable Frequency Drive Organization).

EMC Cable Gland Requirements

The VFD EMC Cable Gland provides a low impedance path at high frequency for common mode current created by the drive to the inverter via the shield. Standard compression glands with pigtail ground connections are NOT suitable for EMC applications and will result in degraded shielding performance.

Mechanical Installation Guidelines

Installation guidelines for mechanical performance remain consistent with standard mining cable practices. Always maintain minimum bending radius as specified in DIN VDE 0298-3, typically 6-8 times the cable outside diameter for fixed installation, and up to 10× for flexible applications. Implement tension control devices to prevent exceeding the 15 N/mm² maximum tensile load specification. Where the cable is subject to continuous movement (cable booms, reeling systems), ensure that routing remains within the ±25°/m torsional stress limit. At transition points between fixed and moving sections, provide adequate support and strain relief to prevent stress concentration.

Submersion Applications

For applications involving water exposure, additional precautions apply. Verify water temperature remains below 40°C for rated submersion depth. Use appropriate waterproof terminations rated for the submersion depth. Implement enhanced inspection schedules for submerged cable sections. Ensure EMC gland terminations maintain their sealing integrity under water pressure.

VFD Cable Comparison and Selection

Understanding how the PROTOMONT EMV-FC compares to other VFD cable options helps engineers make informed selection decisions.

Table 8: VFD Cable Type Comparison
FeaturePROTOMONT EMV-FCStandard VFD CableStandard Mining Cable
EMC ShieldOptimized copper braidFoil + drain wireNone or basic
Mechanical RatingHeavy duty miningLight/medium dutyHeavy duty
Flexible OperationYes (continuous)LimitedYes
Water Resistance10m submersionWet locations onlyVaries
Mining CertificationsMSHA, EACGenerally noYes
Typical ApplicationMining VFD motorsIndustrial VFD motorsNon-VFD mining loads

Selecting the right VFD cable is essential to reducing noise emissions, voltage reflection, and cable failure. This requires identifying the construction that provides the lowest impedance ground path for the application (source: Eland Cables).

Frequently Asked Questions

What does “EMV-FC” mean in the cable designation?
“EMV-FC” stands for Elektromagnetische Verträglichkeit (EMC in German) for Frequenzumrichter (Frequency Converter). This designation indicates the cable is specifically designed with electromagnetic compatibility features optimized for variable frequency drive (inverter) applications. The EMC-optimized shield construction provides effective containment of the high-frequency electromagnetic emissions generated by VFD switching.
Why is EMC shielding necessary for VFD motor cables?
VFDs use Pulse Width Modulation (PWM) switching at frequencies typically between 2-16 kHz to control motor speed. This high-frequency switching creates electromagnetic interference (EMI) that can disrupt nearby control systems, communication cables, and electronic equipment. The EMC shield contains this interference within the cable, protecting both the surrounding environment and ensuring reliable motor operation. Without proper shielding, VFD installations may fail EMC compliance testing and can cause operational problems with other equipment.
How should the EMC shield be grounded?
The EMC shield must be grounded at both ends (VFD and motor) using 360° bonding methods. This requires EMC-rated cable glands that make continuous contact around the entire circumference of the shield braid. Simple pigtail ground connections are inadequate for high-frequency EMC performance. The shield connections should be as short as possible and bonded to a common grounding plane that includes both the VFD enclosure and motor frame.
What is the maximum cable length for VFD applications?
Maximum cable length depends on the VFD characteristics and motor type, not just the cable itself. As a general guideline, cables longer than 50-100 meters may require output reactors or filters to limit voltage reflections at the motor terminals. High-frequency switching in VFDs causes voltage doubling effects that become more pronounced with longer cables. Always consult the VFD manufacturer’s specifications for maximum cable length recommendations for your specific drive model.
Can this cable be used for non-VFD motor applications?
Yes, the PROTOMONT EMV-FC (N)SSHCOEU can be used for direct-on-line (DOL) or soft-starter motor applications. The cable provides excellent performance for any motor power supply application in mining environments. The EMC shield, while not necessary for DOL starters, does not negatively affect performance and provides additional protection against external electromagnetic interference. However, for pure cost efficiency in non-VFD applications, standard PROTOMONT (N)SSHOEU cables without EMC optimization may be more economical.
What is the difference between 0.6/1 kV and 640/1140V ratings?
Both ratings are acceptable for this cable. The 0.6/1 kV rating (600V phase-to-earth, 1000V phase-to-phase) is the standard international designation. The 640/1140V rating is commonly used in mining electrical systems, particularly in European and Australian operations. The cable is designed and tested to meet both rating requirements, providing flexibility for different power system configurations encountered in global mining operations.

Conclusion

The PROTOMONT EMV-FC (N)SSHCOEU 1 kV cable represents a specialized engineering solution that bridges the demanding requirements of mining cable durability with the electromagnetic compatibility needs of modern VFD motor control systems. Its unique combination of heavy-duty mechanical construction, EMC-optimized copper braid shielding, and split protective earth conductor design makes it the definitive choice for frequency converter controlled drives in mining, construction, and similar heavy-duty applications.

The cable’s compliance with DIN VDE 0250-812, MSHA P-189-3 certification, and EAC approval demonstrates its suitability for global mining operations where both safety and electromagnetic compatibility are paramount. The ability to operate in both fixed installations and continuous movement applications, combined with water resistance to 10 meters depth, provides exceptional versatility for the diverse requirements of modern mining operations.

As mining operations increasingly adopt VFD-controlled motors for improved energy efficiency and process control, the importance of properly specified EMC-shielded cables becomes ever more critical. The PROTOMONT EMV-FC series ensures that the benefits of variable frequency drive technology can be realized without compromising electromagnetic compatibility or operational safety.

For mining operations seeking reliable power transmission for VFD-controlled equipment, the PROTOMONT EMV-FC (N)SSHCOEU cable offers proven performance backed by international certifications and engineering excellence specifically targeted at the unique challenges of frequency converter applications in demanding environments.

References and Further Reading

  1. DIN VDE 0250-812: German standard for mining cables – German Institute for Standardization
  2. DIN EN 60228 / IEC 60228: International Standard for Conductors of Insulated Cables
  3. IEC 60332-1-2: Tests on electric and optical fibre cables under fire conditions
  4. IEC 60811-404: Test methods for non-metallic materials – Oil resistance testing
  5. PROTOMONT Mining Cable Technical Documentation – Reeling Cable Technical Resources
  6. Mining Cable Selection Guide – Amplex Mining Cable Guide
  7. Chilean Mining Cable Standards – Mining Cable Chile Technical Resources
  8. VFD Cable Applications – Crane Cable VFD Technical Information
  9. Feichun Special Cable Product Catalog – Feichun Cable Official Website
  10. EN 61800-3: Variable speed electrical power drive systems – EMC requirements
Previous Article

What is PROTOMONT(MT) (N)SSHOEU 1 kV? Complete Technical Guide

Next Article

What is PROTOMONT EMV-FC (N)SSHCOEU (-45°C) 1 kV for Variable Frequency Converter?

Write a Comment

Leave a Comment

您的邮箱地址不会被公开。 必填项已用 * 标注