What is ENVIROLEX® 110°C MULTICORE Cable?

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
ENVIROLEX® 110°C MULTICORE | Feichun Cable

ENVIROLEX® 110°C MULTICORE Cable Technical Data

Low Smoke Zero Halogen (LSZH) Multicore Flexible Copper Conductor | 0.6/1kV | AS/NZS 5000.1, AS/NZS 4507 RHE

110°C
Continuous Temp
0.6/1kV
Voltage Rating
Class 5
Conductor Flex
LSZH
Fire Rating
1.5-300
mm² Range
▸ Product Overview

The ENVIROLEX® 110°C MULTICORE is a specialized power cable with X-HF-110 insulation and HFS-110-TP sheathing, engineered for demanding industrial environments requiring elevated temperature operation and enhanced fire safety. The halogen-free construction produces minimal smoke and no corrosive gases during fire events, meeting stringent requirements for public buildings, transit systems, and critical infrastructure.[1]

Key Feature: Light transmittance ≥60% per IEC 61034 during smoke testing; HCl emission <0.5% per IEC 60754-1.
▸ Cable Construction

Conductor: Flexible stranded copper, Class 5 per AS/NZS 1125. Multi-strand design for optimal flexibility in confined installations.

Insulation: X-HF-110 cross-linked halogen-free compound. Maintains dielectric stability at 110°C continuous operation.[2]

Sheath: HFS-110-TP halogen-free thermoplastic. UV, oil, and chemical resistant outer protection.

Configuration: 2C+E, 3C+E, 4C+E with integrated earth conductor for safety earthing requirements.

▸ Standards Compliance
Australian/NZ Standards:
• AS/NZS 5000.1 – Electric cables
• AS/NZS 1995 – Flexible cables
• AS/NZS 4507 – Reduced Halogen Emission
• AS/NZS 3013 – Wiring rules
• AS/NZS 1660.5.1–5.6 – Flame tests
International Standards:
• IEC 60332-1 – Single cable flame test
• IEC 60332-3 – Bunched cable flame test
• IEC 61034-2 – Smoke density test
• IEC 60754-1/2 – Halogen content
• IEC 60331.11 – Circuit integrity
▸ Fire Performance Comparison
ParameterENVIROLEX® LSZHStandard PVCImprovement
Continuous Temp110°C70°C+57%
Smoke Density≥60% transmittance<20%3× better
HCl Emission<0.5%up to 30%60× reduction
Gas pH≥4.3 (non-corrosive)<2.0 (acidic)Safe
Circuit IntegrityMaintainedCompromisedCritical

Data referenced from industry testing per IEC 61034 and IEC 60754 standards.[3]

▸ Technical Specifications
Configmm²Insul.
(mm)
Sheath
(mm)
OD
(mm)
Mass
(kg/100m)
Product CodeAvailability
2C+E1.50.71.810.317PTHR04AA002Stock
2C+E2.50.71.811.322PTHR05AA002Stock
2C+E40.71.811.925PTHR06AA002Stock
3C+E2.50.71.812.224PTHR05AA003Stock
3C+E40.71.813.029PTHR06AA003Stock
4C+E1.50.71.812.022PTHR04AA004Stock
4C+E2.50.71.813.128PTHR05AA004Stock
4C+E40.71.814.135PTHR06AA004Stock
4C+E60.71.815.245PTHR07AA004Stock
4C+E100.71.818.567PTHX01AA004Stock
4C+E160.81.821.496PTHX02AA004Stock
4C+E250.91.824.7133PTHX03AA004Stock
4C+E350.91.828.0178PTHX04AA004Stock
4C+E501.02.032.9256PTHX05AA004Stock
4C+E701.12.238.3356PTHX06AA004Order
4C+E951.12.242.1447PTHX07AA004Order
4C+E1201.22.448.2574PTHE87AA004Order
4C+E1501.42.653.7714PTHE88AA004Order
4C+E1851.62.659.8872PTHE89AA004Order
4C+E2401.73.067.91144PTHE90AA004Order
4C+E3001.83.087.21501PTHE91AA004Order

Made to Stock   Made to Order

▸ Application Environments
Commercial buildings, high-rise offices, hotels
Healthcare facilities, hospitals, aged care
Mass transit systems, railway stations
Industrial plants, power stations[4]
Mining operations (surface/underground)[5]
Marine & port facilities[6]
Crane & material handling systems[7]
Emergency lighting & fire alarm circuits
▸ Color Options & Installation

Standard Colors:

Black (Stock): CXHF/CXRJ/CXEM
Orange: OMHF/OMRJ/OMEM

Installation Parameters:

• Min. bending radius: 6× OD (fixed), 10× OD (flexing)
• Installation temp: >0°C ambient
• Storage: Heated 24h before cold installation
Previous Article

What is ENVIROLEX® 110°C  SINGLE CORE?

Next Article

What is Alsecure® Plus Mica Tape 110º C Cable?

Write a Comment