PLUS MICA TAPE MULTICORE Low Smoke Fire Cable

PLUS MICA TAPE MULTICORE – Fire resistant multicore cable with mica tape, AS/NZS 3013 WS52W circuit integrity. Technical specifications by Anhui Feichun Special Cable Co., Ltd.

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
ALSECURE® PLUS MICA TAPE MULTICORE | Feichun Cable

ALSECURE® PLUS MICA TAPE MULTICORE🔥 FIRE RATEDMULTICORE

Multicore Flexible Copper Conductors | Mica Taped | 0.6/1kV | AS/NZS 3013 WS52W Circuit Integrity | 110°C

WS52W
Fire Rating
120min
Circuit Integrity
0.6/1kV
Voltage Rating
110°C
Continuous Temp
2C-4C
Core Config
2.5-50
mm² Range
▸ Product Overview

The ALSECURE® PLUS MICA TAPE MULTICORE extends the proven fire-resistant technology of the ALSECURE® range into multicore configurations, providing a complete solution for three-phase power distribution and control circuits in life-safety applications. Each conductor is individually wrapped with glass mica tape, creating independent fire barriers that ensure circuit integrity is maintained even when the cable is subjected to direct flame exposure at temperatures exceeding 830°C.[1]

The multicore construction with integrated earth conductor (+E configuration) simplifies installation while maintaining full compliance with AS/NZS 3013 WS52W fire performance requirements. This cable is specifically engineered for applications where continued three-phase power supply during fire events is critical, including fire pump motors, smoke extraction fans, and emergency lift systems.[2]

Multicore Advantage: Individual mica tape wrapping on each conductor ensures that even if one core is damaged during a fire event, the remaining cores maintain their circuit integrity for the full 120-minute rated period.
▸ Multicore vs Single Core Fire Cables

Understanding the differences between multicore and single core fire-resistant cables helps engineers specify the optimal solution for each application. The ALSECURE® PLUS range offers both configurations to address varying installation requirements.[3]

Key Advantages of Multicore Configuration

✓ Reduced installation time & labor costs
✓ Single cable run for 3-phase + earth
✓ Smaller conduit/trunking requirements
✓ Balanced phase impedance
✓ Simplified cable management
✓ Consistent fire performance all cores
ParameterALSECURE® MulticoreALSECURE® Single Core
Installation ComplexityLower (single cable)Higher (multiple cables)
Conductor Size Range2.5 – 50 mm²10 – 630 mm²
Core Configurations2C+E, 4C+ESingle core only
Fire RatingWS52W (120 min)WS52W (120 min)
Typical ApplicationMotors, 3-phase loadsMains, sub-mains
FlexibilityClass 5 (most sizes)Class 5
▸ WS52W Fire Rating Classification

The WS52W classification per AS/NZS 3013 defines the fire and mechanical performance characteristics of wiring system elements. Both single core and multicore ALSECURE® PLUS cables achieve the same WS52W rating, ensuring consistent fire performance across the product range.[4]

WS52W Rating Breakdown

5
120 min Circuit Integrity
under Fire Conditions
2
Moderate Impact
Protection Level
W
Water Spray
Resistant

The “W” suffix is particularly important for multicore cables used in fire pump and sprinkler system applications, as it indicates the cable will continue to function even when subjected to water spray from firefighting operations or sprinkler activation during a fire event.

▸ Cable Construction

Conductors: Multiple flexible stranded plain annealed copper conductors, Class 5 per AS/NZS 1125 for sizes 4mm² and above. The 2.5mm² 2C+E variant uses non-flexible (Class 2) conductors as noted in specifications.

Fire Barrier: Each individual conductor is wrapped with glass mica tape providing independent fire protection. Mica maintains insulating properties at temperatures exceeding 1000°C.[5]

Insulation: X-HF-110 cross-linked halogen-free polyolefin compound applied over each mica-wrapped conductor. Rated for 110°C continuous operation with excellent thermal aging characteristics.

Sheath: HFS-110-TP halogen-free thermoplastic sheath providing mechanical protection, UV resistance, and low smoke emission compliant with AS/NZS 4507 RHE requirements.

Note: Product code PDGP07AA002* (2C+E 2.5mm²) utilizes non-flexible Class 2 conductors. All other sizes feature flexible Class 5 conductors suitable for installations requiring repeated movement during installation.
▸ Standards Compliance
Australian/NZ Standards:
• AS/NZS 5000.1 – Electric cables
• AS/NZS 4507 – Reduced Halogen Emission (RHE)
• AS/NZS 3013 – Fire & Mechanical Performance (WS52W)
• AS/NZS 1125 – Conductor specifications
• AS/NZS 3000 – Wiring Rules compliance
International Standards:
• IEC 60331-21 – Fire resistance test (0.6/1kV)
• IEC 60332-1 – Single cable flame test
• IEC 60332-3 – Bunched cable flame test
• IEC 61034-2 – Smoke density test
• IEC 60754-1/2 – Halogen content test
▸ Technical Specifications
ConfigConductor
(mm²)
Insulation
(mm)
Sheath
(mm)
OD
(mm)
Mass
(kg/100m)
Product CodeStatus
2C+E2.50.71.814.227PDGP07AA002*Stock
4C+E100.71.821.180PDGX01AA004Stock
4C+E160.81.823.9110PDGX02AA004Stock
4C+E251.01.827.7175PDGX03AA004Stock
4C+E351.01.831.5230PDGX04AA004Stock
4C+E501.02.035.9312PDGX05AA004Stock

Made to Stock    * Non-flexible conductor (Class 2)

▸ Electrical Parameters
ConfigConductor
(mm²)
DC Resistance
@ 20°C (Ω/km)
Current Rating
Free Air (A)
Voltage Drop
3-Phase (mV/A/m)
2C+E2.57.412816
4C+E101.83574.0
4C+E161.15762.5
4C+E250.7271011.55
4C+E350.5241251.15
4C+E500.3871510.84

Current ratings based on multicore cable in free air at 30°C ambient. Installation method corrections per AS/NZS 3008.1.1 required. Voltage drop values for balanced 3-phase loads.

▸ Fire Performance Comparison
ParameterALSECURE® MulticoreStandard LSZH MultiPVC/PVC Multicore
Circuit Integrity (Fire)120 minutes0 min (fails)0 min (fails)
Fire Test Temperature830-950°CN/AN/A
Mica Tape (per core)Yes (individual)NoNo
Smoke Density≥60% transmittance≥60%<20%
HCl Emission<0.5%<0.5%up to 30%
Water Spray (W rating)YesNoNo
Green Star CompatibleYes (PVC-free)YesNo

Data referenced from AS/NZS 3013 and IEC 60331 testing standards.[6]

▸ Critical Application Environments

The multicore configuration is particularly suited for three-phase motor loads and control circuits in life-safety systems. The integrated earth conductor (+E) simplifies installation while ensuring protective earthing continuity is maintained during fire conditions.[7]

Fire pump motors (3-phase supply)
Smoke extraction fan motors
Stairwell pressurization fans
Emergency lift motor supply
Fire damper control circuits
Sprinkler booster pump supply
Emergency generator distribution
Hospital essential services (motors)
Data center HVAC fire circuits
Tunnel ventilation systems
Airport baggage handling (fire zones)
Green Star rated building services
▸ Color Options & Installation

Sheath Color (4-character code):

Red (Standard): JBNA

Example: PDGX01AA004JBNA = 4C+E 10mm² Red sheath

Core Identification:

• 2C+E: Brown, Blue + Green/Yellow Earth
• 4C+E: Brown, Black, Grey, Blue + G/Y Earth

Installation Requirements:

• Min. bending radius: 6× overall diameter
• Install in metal conduit/trunking for max fire rating
• Ambient temp during installation: >0°C
• Terminations: Use fire-rated glands & accessories
• Support spacing per AS/NZS 3000 Table 3.3