Feichun YXC7VY2V 20.3/35 kV — Single-Core XLPE Copper Cable with Round Aluminium Wire Armour
A full-English engineering guide to the supplied YXC7VY2V 20.3/35 kV record and its printed international designation N2XSYR(AL)Y. The article keeps the national title, product construction, official 1×240/25 mm² row, source dates and project-level calculation boundaries distinct.
Contents
- Engineering position
- Designation and construction logic
- Standard and evidence review
- Complete source specification
- Technical matrix
- Published-data limitations
- Derived installation checks
- Layer-by-layer cross-section
- Electrical, screen and armour system
- Thermal, voltage-drop and short-circuit design
- Fire and PVC performance boundary
- Fixed-route applications
- Handling and termination
- Selection comparison
- Failure mode analysis
- Feichun certification scope
- Source and revision audit
1. Engineering position: a high-voltage single-core armoured cable with explicit data boundaries
20.3/35 kV Uo/U is a high-voltage distribution class. Insulation coordination, test voltage, terminations and joints must be released for the exact project system.
The product row is one 240 mm² cable with one copper screen and one aluminium-wire armour layer. A three-phase circuit arrangement is not the same thing as a three-core cable.
Round aluminium wires provide armour against route handling and mechanical exposure. Armour bonding, cleats, pulling loads and minimum-radius instructions remain installation controls.
The article separates user-supplied family values, official product dimensions and route calculations. A dash is retained as a dash rather than being replaced with a value from another family.
2. Designation and construction logic
| Designation / field | Engineering reading | Design consequence | Evidence status |
|---|---|---|---|
| YXC7VY2V | National product title shown by the supplied family record. | Keep this title in the purchase schedule and match it to the exact 1×240/25 mm² product row. | Supplied / official family record |
| N2XSYR(AL)Y | International designation printed in the official product PDF. | Use the printed designation as a document cross-reference; do not infer additional letter meanings beyond the controlled construction. | Official product PDF |
| 20.3/35 kV | Rated voltage class; the source also prints 20,3/35 kV with a comma. | Use one consistent notation in the project schedule and accessory selection. | Supplied / official record |
| 1×240/25 mm² | One 240 mm² copper conductor and a 25 mm² copper screen. | Do not read 25 mm² as a second phase conductor or armour cross-section. | Official product row |
| R(AL) | Construction record identifies round aluminium wire armour. | Check aluminium armour treatment, bonding, cleats and earth-fault assumptions separately. | Construction-based reading |
Conductor screen, XLPE insulation and insulation screen form the radial dielectric system. The copper metallic screen provides the external reference and bonding interface.
The source states concentric copper wires plus copper tape and the official product row states 25 mm² screen section. The screen fault current remains a separate design input.
PVC separation sheath isolates the screened core from the single layer of round aluminium wires. PVC outer sheath protects the armour and route interface.
53.0 mm is the nominal outer diameter; 18.3 mm is the conductor diameter; 8.5 mm and 2.7 mm are the published insulation and outer-sheath thicknesses.
3. Standard and evidence review
| Reference | Role in this article | Engineering interpretation | Boundary |
|---|---|---|---|
| National TSEK | Standard printed by the supplied and official family record. | Use the released TSEK certificate, edition and test file for the ordered product. | No edition or certificate number is supplied here. |
| IEC 60332-3 Cat. C | Flame-retardant reference listed by the source. | IEC 60332-3-24:2018 describes Category C vertical flame-spread testing for vertically mounted bunched wires or cables. | The product source gives the standard number without an edition; do not turn it into a CPR class. |
| IEC 60502-2 | Related engineering reference only. | The IEC publication covers extruded-insulation cables from 6 kV up to 30 kV for fixed installations. | The YXC7VY2V source lists National TSEK, not IEC 60502-2; no IEC conformity is claimed. |
| PVC material system | PVC separation sheath and PVC outer sheath. | Review smoke, corrosive gas, halogen, fire stopping, oil and local building requirements using the actual product dossier. | No LSZH or halogen-free claim is supplied for this record. |
| Product evidence | Family PDF plus product-specific PDF/page. | Use the product-specific 1×240/25 mm² values for dimensions, screen section, DCR, ampacity and conductor fault duty. | Do not generalise the row to other sizes. |
4. Complete source specification
| Specification field | Reference value | Engineering interpretation | Evidence status |
|---|---|---|---|
| Family title | YXC7VY2V 20.3/35 kV | The national product title used by the supplied record and official family page. | Supplied / official family record |
| International designation | N2XSYR(AL)Y | The product PDF prints this as the international designation. It is retained separately from the YXC7VY2V title. | Official product PDF |
| Product description | 20,3/35 kV XLPE insulated single core armoured cables with copper conductor | Single-core medium-voltage cable with a copper conductor, XLPE insulation, concentric copper screen, aluminium wire armour and PVC outer protection. | Supplied / official family PDF |
| Standard | National TSEK | The source lists National TSEK. Do not silently rewrite this product record as IEC 60502-2 without a matching conformity file. | Supplied / official family PDF |
| Application | These are cables with low dielectric losses used in energy network with sudden load changes. Laid in residental or industrial areas, underground or in ducts. | Fixed energy-network application in residential or industrial areas, underground routes or ducts; route conditions still require engineering review. | Supplied / official family PDF |
| Conductor material | Copper | The phase conductor is copper. | Supplied / official product page |
| Conductor flexibility | Class 2 | Stranded Class 2 construction is stated in the source. | Supplied source |
| Type of conductor | Circular, stranded, class 2 | The source identifies a circular stranded conductor; the official product page also labels it Circular stranded (RM). | Supplied / official product page |
| Number of cores | 1 | One single-core cable unit; a three-phase circuit may require three separately installed units according to the system design. | Supplied source |
| Conductor cross-section | 240 mm² | The ordered family/product row is 1×240/25 mm²; the 25 mm² is the published metallic screen section, not a second phase conductor. | Supplied / official product PDF |
| Rated Voltage Uo/U (Um) | 20.3 / 35 kV | Use the exact decimal notation in the project schedule. The source title also uses 20,3/35 kV comma notation. | Supplied source |
| Operating temperature, range | -20 … 90 °C | Usage range stated by the source; ambient, installation, accessory and sheath limits remain project controls. | Supplied / official family PDF |
| Short-circuit max. conductor temperature | 250 °C | Use with I²t, protection clearing time, conductor area, screen design and accessory capability. | Official family PDF / product PDF |
| Bending factor when laying | 12 (xD) | A laying factor, not a repeated-flex, reeling or energy-chain qualification. | Supplied source |
| Max. conductor temperature in service | 90 °C | Continuous conductor-temperature limit stated in the source; route ampacity still depends on formation and environment. | Supplied source |
| Flame retardant | IEC 60332-3 Cat. C | The source gives a bunched-cable vertical flame-spread reference; it is not by itself a CPR class. | Supplied source |
| Conductor screen | Semi-conducting compound (XLPE) | Controls the electric-field transition at the copper conductor / XLPE interface. | Supplied source |
| Insulation | XLPE | Cross-linked polyethylene primary insulation for the stated voltage class. | Supplied source |
| Insulation screen | Semi-conducting compound (XLPE) | Controls the outer electric-field interface of the XLPE insulation. | Supplied source |
| Semi-conducting tape | Crape tape | The source wording is preserved; confirm the released material and dimensions in the controlled drawing. | Supplied source |
| Metallic screen | Concentric / Copper wires + copper tape | The official product row reports a 25 mm² screen section; bonding and fault duty still require a project earthing design. | Supplied / official product page |
| Separation sheath | PVC | Separates the copper-screened core from the aluminium wire armour. | Supplied source |
| Armour | Round aluminium wires | Single layer of aluminium wires provides mechanical protection around the separated cable core. | Supplied source |
| Armour type | Single layer of aluminium wires | The exact released wire diameter, lay, coverage, joints and bonding remain drawing-controlled. | Official family PDF / product page |
| Outer sheath | PVC | PVC external protection; the source does not provide a halogen-free or LSZH claim for this product record. | Supplied / official product page |
| Sheath colour | Red | Official product page characteristic. | Official product page / product PDF |
| Average insulation thickness | 8.5 mm | Published dimensional characteristic. | Supplied source |
| Nominal outer sheath thickness | 2.7 mm | Published dimensional characteristic. | Supplied source |
| Nominal outer diameter | 53.0 mm | Use for installation planning and the clearly marked 12 x D screening calculation. | Official product page / product PDF |
| Conductor diameter | 18.3 mm | Published product dimension; do not substitute it for the overall cable diameter. | Official product page / product PDF |
| Approximate weight | 4710 kg/km | Use for drum, lifting, support and route-load planning; actual delivery mass remains product-controlled. | Official product page / product PDF |
| Screen section | 25 mm² | Published copper-screen section for the 1×240/25 mm² row. | Official product page / product PDF |
| Max. DC resistance at 20 °C | 0.0754 Ohm/km | Conductor resistance value for the specific 240 mm² product row. | Official product page / product PDF |
| Perm. current rating, buried 20 °C — flat | – A | A dash is retained exactly; do not replace it with the trefoil value. | Official product page / product PDF |
| Perm. current rating, buried 20 °C — trefoil | 469 A | Published rating under the stated buried trefoil basis; not a universal ampacity. | Official product page / product PDF |
| Perm. current rating, air 30 °C — flat | 641 A | Published rating under the stated air flat basis; formation, spacing and ambient must be confirmed. | Official product page / product PDF |
| Perm. current rating, air 30 °C — trefoil | – A | A dash is retained exactly; do not replace it with the air-flat value. | Official product page / product PDF |
| Permissible short-circuit current, conductor 1 s | 34.3 kA | Published conductor short-circuit value for the 240 mm² row. | Official product page / product PDF |
| Permissible short-circuit current, screen 1 s | – kA | Screen short-circuit duty is not numerically supplied in the product row; close it in the earthing/protection dossier. | Official product page / product PDF |
| Nexans reference | 10563489 | Product reference for YXC7VY2V 1×240/25 mm². | Official product page / product PDF |
| Country reference | TR | Product-page country reference. | Official product page / product PDF |
| EAN 13 | 8680969138826 | Product identifier, not an electrical design value. | Official product page / product PDF |
| Packaging | Drum (1000 m) | Family page packaging field; final drum schedule must follow the confirmed ordered length. | Official family page |
| Delivery reel size for 1000 m | – cm | The official product page leaves this field as a dash; no reel dimensions are invented. | Official product page / product PDF |
| Product row name | YXC7VY2V 1×240/25mm2 | Official product-row name for the 240 mm² conductor and 25 mm² screen. | Official product page / product PDF |
| Source record — page 1 | Generated 8/4/26 — www.nexans.com.tr — Page 1 / 2 | Preserved as supplied; the first page contains the family title, application and construction sequence. | Supplied / official source metadata |
| Source record — page 2 | YXC7VY2V 20.3/35 kV — Generated 8/4/26 — www.nexans.com.tr — Page 2 / 2 | Preserved as supplied; the second page contains the characteristics and product row. | Supplied / official source metadata |
| Source disclaimer | All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans. | Dimensions, weights and technical particulars are treated as indicative until the controlled Feichun release is approved. | Supplied source disclaimer |
5. Technical matrix — YXC7VY2V 1×240/25 mm²
The official product row is reproduced without changing its basis. The ratings are formation-specific: buried trefoil at 20 °C and air flat at 30 °C. The dashes for buried flat, air trefoil and screen 1 s fault current are intentionally retained.
| Conductor cross-section | Nominal outer diameter | Approx. weight | Max. DC resistance at 20 °C | Screen section | Buried 20 °C — flat | Buried 20 °C — trefoil | Air 30 °C — flat | Air 30 °C — trefoil | Conductor short-circuit 1 s | Screen short-circuit 1 s | Product reference |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 240 mm² | 53.0 mm | 4710 kg/km | 0.0754 Ohm/km | 25 mm² | – A | 469 A | 641 A | – A | 34.3 kA | – kA | 10563489 |
The values above belong to the official 1×240/25 mm² product row. Final Feichun dimensions, mass, electrical values, installation ratings and accessory compatibility must be released for the ordered construction.
Published-data limitations and design closure
| Required design input | Source state | Why it matters | Required Feichun release action |
|---|---|---|---|
| System voltage | 20.3 / 35 kV | High-voltage accessory coordination, insulation testing and protection settings must match the ordered system. | Confirm project voltage withstand and accessory file. |
| Conductor selection | 240 mm² | The supplied product row is fixed; no alternative cross-sections are inferred. | Release the exact Feichun size and conductor drawing. |
| Continuous current | 469 A buried trefoil; 641 A air flat | These are basis-specific values, not universal ampacity. Buried-flat and air-trefoil fields are dashes. | Recalculate for soil, spacing, depth, ambient, grouping and bonding. |
| Bending control | 12 (xD) | With 53.0 mm nominal outer diameter, 636.0 mm is an arithmetic screening radius; the controlled method statement governs. | Confirm drum, entry, roller and accessory radii. |
| Conductor fault duty | 34.3 kA for 1 s | Protection clearing time and the actual I²t duty must be coordinated with the conductor and termination. | Verify protection and joint/termination capability. |
| Screen fault duty | – kA for 1 s | The screen section is 25 mm², but the product row does not publish a numerical screen short-circuit current. | Release screen bonding, earthing and I²t design. |
| Voltage drop | No product X/route length/load profile supplied | DCR alone does not close AC impedance, power factor, load profile or route voltage drop. | Calculate with the actual installation and operating point. |
| Dynamic service | Not stated | 12 (xD) is a laying factor, not evidence for reeling, festoon, drag-chain or repeated-torsion service. | Use a qualified dynamic cable family for moving equipment. |
| Fire classification | IEC 60332-3 Cat. C only | Do not upgrade the record to Eca, Cca, B2ca or s/d/a qualifiers without a matching declaration. | Review the project fire strategy and current product report. |
6. Derived installation checks
| Product row | Published outer diameter | Calculation | Derived laying-radius screening value | Published mass | Derived mass per 100 m |
|---|---|---|---|---|---|
| 240 mm² | 12 × 53.0 mm | 636.0 mm | 4710 kg/km | 471.0 kg/100 m |
7. Layer-by-layer cross-section
The diagram follows the supplied sequence. It is intentionally a single-core section: the three-phase system, if required, is assembled from separate single-core units and must not be represented as one three-core cable.
8. Electrical, screen and armour system
The 240 mm² circular stranded copper conductor carries the phase current. The semiconducting conductor screen, XLPE and insulation screen maintain a controlled radial electric field.
The 25 mm² copper screen is a published dimensional value. Continuity, bonding, induced-current control and earth-fault duty require the project earthing design.
Round aluminium wires provide mechanical protection, but armour behaviour is not automatically equivalent to the copper screen or a dedicated protective conductor.
For a three-phase circuit, phase spacing, trefoil/flat formation, bonding arrangement and permissible current must be calculated for the actual route.
9. Thermal, voltage-drop and short-circuit design
The official row gives 469 A for buried trefoil at 20 °C and 641 A for air flat at 30 °C. The buried-flat and air-trefoil fields are dashes. These values cannot be copied to another formation.
90 °C is the stated maximum conductor temperature in service and 250 °C is the short-circuit maximum conductor temperature. Ambient, grouping, soil, sheath and accessory limits still apply.
For a three-phase set of single-core cables, use the actual AC resistance, reactance, spacing, formation, power factor, load profile and route length. The supplied DCR is not a complete voltage-drop answer.
34.3 kA for conductor 1 s is published. Screen 1 s current is a dash, so screen bonding and fault-return coordination cannot be closed from the product row alone.
10. Fire and PVC performance boundary
The source lists a Category C bunched-cable flame-spread reference. It is not a CPR Eca/Cca/B2ca declaration and does not establish fire resistance.
The construction lists PVC separation sheath and PVC outer sheath. No LSZH, halogen-free, smoke-density or corrosive-gas performance is added to this product record.
Confirm cable grouping, penetrations, barriers, supports, enclosures, ventilation, emergency access and local construction requirements.
Aluminium wire armour with PVC has a different mechanical, electrical and fire profile from LSZH or steel-armoured constructions. Selection must follow the actual project priority.
11. Fixed-route applications
The source identifies low dielectric losses and networks with sudden load changes. Final selection needs load profile, conductor area, protection and route design.
Review soil thermal resistance, depth, water exposure, drainage, backfill, mechanical impact and joint access.
Check duct fill, pulling load, sidewall pressure, entry geometry, bends, heat dissipation, water and installation temperature.
Review public access, fire strategy, induced voltage, earthing, support spacing, maintenance clearance and the consequences of PVC sheath selection.
12. Handling and termination
- Confirm the exact YXC7VY2V 1×240/25 mm² reference, drum length, source revision, nominal diameter, mass and end seals before unloading.
- Use the stated 12 (xD) laying factor only as a screening input; confirm the controlled minimum-radius and accessory method statement.
- Align the drum and pay off in the marked direction. Prevent reverse winding, flange impact, uncontrolled twist and local PVC sheath damage.
- Use rollers and supports that protect the round aluminium wires and prevent excessive sidewall pressure at bends and entries.
- Prepare the single-core termination with the correct copper screen continuity, armour treatment, phase identification, gland and accessory dimensions.
- Bond the copper screen and aluminium armour according to the approved earthing design. Record continuity, torque, phase identity and test results.
- Before energisation, complete conductor resistance, screen continuity, insulation/sheath tests, specified MV withstand or partial-discharge tests, phase identification, accessory inspection and as-built records.
13. Selection comparison for engineers
| Requirement | YXC7VY2V reference | What must be verified | Engineering decision |
|---|---|---|---|
| 20.3/35 kV fixed feeder | Single-core copper / XLPE; 240 mm²; 20.3/35 kV. | System insulation coordination, accessories, phase arrangement and protection. | Candidate after project design. |
| High-current route | 641 A air flat; 469 A buried trefoil under published bases. | Actual formation, spacing, ambient, soil, grouping and thermal resistivity. | Use only after route recalculation. |
| Mechanically exposed fixed route | Single layer round aluminium wire armour; PVC outer sheath. | Impact, compression, pulling load, bending, cleats, armour bonding and sheath protection. | Potentially suitable subject to mechanical design. |
| Screen/fault coordination | 25 mm² copper screen; 34.3 kA conductor 1 s; screen 1 s dash. | Earthing, bonding, screen fault duty, protection clearing time and accessory capability. | Do not release without screen-duty closure. |
| Fire-sensitive building | IEC 60332-3 Cat. C; PVC sheath system. | Current product declaration, smoke/corrosive-gas evidence and local fire requirements. | Do not assume LSZH or CPR class. |
| Reeling / festoon / drag chain | 12 (xD) laying factor; fixed energy-network application. | Cycles, speed, torsion, acceleration, rollers and dynamic bend radius. | Select a dedicated dynamic cable family. |
14. Failure mode and effects analysis
15. Feichun certification and project assurance
Certification capability does not make every YXC7VY2V size automatically TSEK, IECEx, ATEX, EAC or fire-certified. The exact conductor, screen, PVC compounds, aluminium armour, voltage class and documentation must match.
Confirm conductor flexibility, conductor and screen area, DCR, outer diameter, mass, current ratings, short-circuit values, screen bonding, armour treatment, bending instructions and accessory compatibility.
For 20.3/35 kV service, the termination and joint system must be selected with the exact insulation diameter, screen preparation, sheath, armour and test requirements.
Feichun can develop the copper / XLPE / copper-screen / PVC / aluminium-wire-armoured architecture around the actual route, protection system and market documentation without copying incomplete data.
16. Source and revision audit
| Source | Use in this article | Status and limitation |
|---|---|---|
| Nexans YXC7VY2V 20.3/35 kV family page | Family title, National TSEK, application, construction, product row, packaging and family description. | Official family source; use the exact ordered product reference. |
| Nexans two-page family PDF | Generated 8/4/26, page labels, source disclaimer, 20.3/35 kV, 240 mm², 8.5 mm insulation, 2.7 mm sheath and flame reference. | Family-level record; preserve the supplied source date and page distinction. |
| Nexans YXC7VY2V 1×240/25 mm² product page | Official product reference 10563489, outer diameter, mass, conductor diameter, screen section, DCR, current ratings, sheath colour and fault values. | Product-specific record; do not generalise its values to other sizes. |
| Nexans product PDF 10563489 | International designation N2XSYR(AL)Y, construction and the 1×240/25 mm² technical row. | Official product-specific PDF generated 8/4/26. |
| IEC 60332-3-24:2018 | Related official context for Category C vertical flame spread of vertically mounted bunched cables. | The YXC7VY2V record lists IEC 60332-3 Cat. C without an edition; product documentation controls the applicable test basis. |
| IEC 60502-2 consolidated record | General reference for extruded-insulation MV cable scope and fixed-installation engineering context. | The supplied YXC7VY2V source lists National TSEK, not IEC 60502-2; no IEC conformity is claimed here. |
| User-supplied source text | All supplied values, construction sequence, source metadata and page labels. | Preserved; dashes are not filled from another cable. |