What is NEK TS 606:2025 Cable Code Designation?

Comprehensive Guide to Norwegian Offshore & Marine Cable Standards

Marine Cable
Marine Cable
What is NEK TS 606:2025 Cable Code Designation? | Offshore & Marine Cable Standards Guide
Anhui Feichun Special Cable Co., Ltd.
安徽飞纯特种电缆有限公司

What is NEK TS 606:2025 Cable Code Designation?

Comprehensive Guide to Norwegian Offshore & Marine Cable Standards

NEK TS 606:2025 represents the most comprehensive technical specification for offshore and marine cables, developed by the Norwegian Electrotechnical Committee (NEK) to address the extreme demands of the oil and gas industry, offshore platforms, and marine vessels. This specification has become the global benchmark for cable performance in harsh offshore environments, superseding many regional standards through its rigorous requirements for fire resistance, halogen-free construction, and mud resistance.

According to Feichun Cable, NEK TS 606 cables are essential for critical safety systems on offshore installations where cable failure could result in catastrophic consequences. The standard mandates performance levels significantly exceeding IEC 60092-360:2014, particularly in oil resistance, mud resistance, and fire performance testing.

1. Understanding NEK TS 606: Purpose and Background

1.1 Historical Development

The NEK TS 606 specification originated from the “Recommended Practice for Specification of Cables” published by the Norwegian Oil Industry Association (OLF) in the late 1980s. The offshore industry recognized the critical need to standardize and limit cable types used in offshore operations, where cable diversity complicated maintenance, increased inventory costs, and created potential safety risks.

Evolution Timeline

  • 1980s: OLF develops initial cable specifications to address offshore industry needs
  • 1993: Norwegian Electrotechnical Committee (NEK) assumes responsibility and publishes first edition as NEK 606 national standard
  • 2009: Redesignated as Technical Specification (TS) to distinguish from IEC standards, becoming NEK TS 606
  • 2016: Major revision incorporating enhanced oil and mud resistance requirements
  • 2025: Current edition with expanded cable types and updated test methodologies

1.2 Primary Applications

Offshore Oil & Gas Platforms

  • Fixed production platforms (TLP, SPAR, jacket structures)
  • Floating production systems (FPSO, FSO)
  • Semi-submersible drilling rigs
  • Jack-up drilling platforms
  • Subsea production systems

Marine Vessels

  • Drilling ships and drillships
  • Oil tankers and chemical tankers
  • Supply vessels and accommodation vessels
  • Offshore construction vessels
  • Pipe-laying barges

Critical Systems

  • Emergency shutdown (ESD) systems
  • Fire and gas detection systems
  • Emergency lighting and alarms
  • Process control and SCADA
  • Power management systems

Industry leader Crane Cable emphasizes that NEK TS 606 compliance is increasingly specified by international oil companies and maritime regulatory bodies, making it a de facto requirement for offshore projects worldwide.

2. Key Characteristics and Performance Requirements

2.1 Fire Performance Classification

PropertyFire Resistant (BFOU)Flame Retardant (RFOU/TFOU)Test Standard
Fire Resistance Test✓ Required✗ Not RequiredIEC 60331-21, IEC 60331-31
Test Temperature750-800°C (1,000°C enhanced)N/AIEC 60331
Test DurationMinimum 120 minutes
(180 minutes for enhanced)
N/AIEC 60331
Circuit IntegrityMust maintain functionality during fireNot requiredIEC 60331-21
Water Spray Test90 min fire + 15 min water sprayN/AEN 50200 Annex E
Flame Propagation (Bundled)✓ Required✓ RequiredIEC 60332-3-22 (Category A)
Flame Propagation (Single)✓ Required✓ RequiredIEC 60332-1-2
Halogen Content≤ 5 mg/g≤ 5 mg/gIEC 60754-1, IEC 60754-2
Light Transmittance (Smoke)≥ 60%≥ 60%IEC 61034-1, IEC 61034-2
Acidity (pH)≥ 4.3≥ 4.3IEC 60754-2
Conductivity (μS/mm)≤ 10≤ 10IEC 60754-2

Source: NEK TS 606:2025, IEC 60331 series, IEC 60332 series, IEC 60754 series

Critical Distinction: Fire Resistant vs. Flame Retardant

BFOU (Fire Resistant): Contains mica glass tape fire barrier that maintains circuit integrity for minimum 2-3 hours during direct fire exposure at 750-830°C. The cable continues to function as an electrical circuit while burning, critical for emergency systems, evacuation alarms, and firefighting equipment.

RFOU/TFOU (Flame Retardant): Self-extinguishing cables that prevent fire propagation but do NOT maintain circuit functionality during fire. Suitable for non-critical power and control applications where circuit integrity during fire is not essential.

Application Rule: Emergency systems, fire detection, emergency lighting, and life safety circuits MUST use fire resistant (BFOU) cables. General power distribution and non-critical controls may use flame retardant (RFOU/TFOU) cables.

2.2 Oil and Mud Resistance Requirements

NEK TS 606 imposes significantly more stringent oil and mud resistance requirements compared to IEC 60092-360, reflecting real-world offshore conditions where cables are exposed to drilling mud, hydraulic fluids, and crude oil.

Test ParameterNEK 606 SHF2NEK 606 SHF2 MUD ResistantTest Method
Enhanced Oil Resistance Tests
Test Oil IRM902RequiredRequiredIEC 60092-360 SHF2
Temperature100°C ± 5°C100°C ± 5°C—
Duration168 hours (7 days)168 hours (7 days)—
Tensile Strength Change≤ ±25%≤ ±25%—
Elongation at Break Change≤ ±25%≤ ±25%—
Test Oil IRM903RequiredRequiredIEC 60092-360 Annex C
Temperature100°C ± 5°C100°C ± 5°C—
Duration168 hours (7 days)168 hours (7 days)—
Mud Resistance Tests (Mandatory for SHF2 MUD)
Base Oil EDC 95-11Not requiredRequiredNEK 606 proprietary
Temperature—100°C ± 5°C—
Duration—168 hours (7 days)—
Tensile Strength Change—≤ ±30%—
Elongation at Break Change—≤ ±30%—
Synthetic Drilling MudNot requiredRequiredNEK 606 proprietary
Temperature—80°C ± 5°C—
Duration—168 hours (7 days)—
Water-Based Drilling MudNot requiredRequiredNEK 606 proprietary
Temperature—80°C ± 5°C—
Duration—168 hours (7 days)—

Source: NEK TS 606:2025 Table 1a, 1b, 1c – Enhanced requirements compared to IEC 60092-360:2014

Field-Specific Mud Testing

When project-specific drilling mud formulations deviate from the standard NEK 606 test fluids (EDC 95-11, synthetic mud, or water-based mud), special evaluation or additional testing must be agreed between manufacturer and end user. Offshore operators should provide actual mud samples for qualification testing before cable procurement.

3. Material Structure and Construction

3.1 Conductor Specifications

ParameterPower Cables (0.6/1 kV and above)Instrumentation Cables (250V)
MaterialTinned copper (preferred) or bare copperTinned copper
Stranding ClassClass 2 (stranded) or Class 5 (flexible)Class 5 (flexible) or Class 6 (extra flexible)
Standard ReferenceIEC 60228IEC 60228
Conductivity≥ 100% IACS (annealed copper)≥ 100% IACS (annealed copper)
Tinning ThicknessMinimum 1 μm (ASTM B33)Minimum 1 μm (ASTM B33)
Typical Sizes (Power)1.5 mm² to 300 mm²—
Typical Sizes (Instrumentation)—0.75 mm², 1.0 mm², 1.5 mm², 2.5 mm²

Amplex Mining reports that tinned copper conductors are essential for NEK 606 applications due to superior corrosion resistance in marine environments and improved solderability during terminations.

3.2 Insulation Materials

EPR (Ethylene Propylene Rubber)

  • Type: Thermoset elastomer (EPDM)
  • Temperature Rating: -40°C to +90°C continuous
  • Dielectric Constant: 3.0-4.0 at 50/60 Hz
  • Dielectric Strength: ≥ 20 kV/mm
  • Tensile Strength: ≥ 12 MPa
  • Elongation at Break: ≥ 300%
  • Key Features: Excellent flexibility, ozone resistance, thermal aging resistance
  • Applications: RFOU power cables, instrumentation cables

XLPE (Cross-Linked Polyethylene)

  • Type: Thermoset polymer
  • Temperature Rating: -20°C to +90°C continuous
  • Dielectric Constant: 2.3 at 50/60 Hz
  • Dielectric Strength: ≥ 25 kV/mm
  • Tensile Strength: ≥ 15 MPa
  • Elongation at Break: ≥ 350%
  • Key Features: Superior electrical properties, moisture resistance, higher ampacity
  • Applications: TFOU power cables, medium/high voltage applications

Mica Glass Tape (Fire Barrier)

  • Composition: Mica flakes bonded to glass fabric with silicone
  • Thickness: Typically 0.08-0.15 mm per wrap
  • Application: Helically wrapped around conductor before insulation
  • Overlap: Minimum 50% coverage
  • Temperature Resistance: ≥ 1,000°C
  • Function: Maintains electrical integrity during fire by forming ceramic barrier
  • Applications: BFOU fire resistant cables only

3.3 Shielding and Armoring

ComponentDescriptionSpecificationsApplication
Bedding/Inner Covering (F)Halogen-free thermoplastic elastomer tape or extruded layerThickness 0.5-1.5 mm depending on cable size
SHF1 compound
Protects insulation from armor, provides cushioning
Tinned Copper Wire Braid (O)Woven mesh of tinned copper wiresWire size: 0.2-0.5 mm diameter
Coverage: ≥ 80% optical
Carriers: 16-32 depending on cable diameter
Electromagnetic shielding, mechanical protection, ground path
Galvanized Steel Wire Braid (C)Woven galvanized steel wiresWire size: 0.8-1.2 mm diameter
Coverage: ≥ 85%
Tensile strength: ≥ 1,400 N/mm²
Heavy mechanical protection, high tensile strength applications
Aluminum Laminate (L)Aluminum foil laminated to outer sheathThickness: 0.2-0.4 mm aluminum
Laminated to polymer film
Electromagnetic shielding, moisture barrier (lightweight)
Individual Screen (i)Copper/polyester tape with drain wire per pair/tripleCoverage: ≥ 90%
Drain wire: Tinned copper 0.5-1.0 mm²
Instrumentation cables requiring EMI protection per circuit
Collective Screen (c)Single copper/polyester tape over all coresCoverage: ≥ 90%
Drain wire: Tinned copper 1.5-2.5 mm²
Instrumentation cables with common ground reference

3.4 Sheathing Materials

SHF Compound Classifications

SHF1 (Thermoplastic Halogen-Free):

  • Polyolefin-based compounds (PE, PP blends)
  • Flame retardant additives (metal hydroxides)
  • Suitable for bedding and inner coverings
  • Temperature range: -20°C to +80°C
  • Shore A hardness: 85-95

SHF2 (Thermoset Halogen-Free):

  • EVA (Ethylene Vinyl Acetate) based elastomers
  • LSZH (Low Smoke Zero Halogen) compounds
  • Enhanced oil and chemical resistance
  • Temperature range: -40°C to +90°C
  • Shore A hardness: 80-90
  • Standard for NEK 606 outer sheaths

SHF2 MUD (Mud Resistant Thermoset):

  • Specially formulated EVA/elastomer blends
  • Must pass enhanced oil and mud resistance tests
  • Resistant to EDC 95-11, synthetic mud, water-based mud
  • Required for drilling operations exposure
  • Highest chemical resistance grade

4. NEK TS 606:2025 Cable Code Designation System

4.1 Code Structure Overview

NEK TS 606 employs a systematic 2-letter or 4-letter coding system to precisely describe cable construction. This standardized nomenclature enables rapid cable identification and ensures proper cable selection for specific applications.

Basic Code Format

2-Letter Code: Uses positions 1 and 4 only (Insulation + Outer Sheath)

4-Letter Code: Uses all positions (Insulation + Bedding + Armor/Screen + Outer Sheath)

Position: 1 2 3 4
Function: INSULATION BEDDING ARMOUR/SCREEN OUTER SHEATH

Example: R F O U
(EPR) (Bedding) (Cu Braid) (Thermoset)

4.2 Complete Code Letter Definitions

PositionLetter CodeMaterial/FunctionTechnical Details
Position 1: INSULATION TYPE
1BFire resistant tape + insulationMica glass tape (MGT) + EPR insulation. Fire resistant per IEC 60331
REthylene Propylene Rubber (EPR)EPDM elastomer, -40°C to +90°C, flame retardant
TCross-Linked Polyethylene (XLPE)Thermoset XLPE, -20°C to +90°C, superior electrical properties
IThermoplastic compoundPVC or halogen-free thermoplastic for low voltage applications
AFiber, tight bufferedOptical fiber with tight buffer coating (fiber optic cables)
QFiber in loose tubeOptical fiber in gel-filled loose tube (fiber optic cables)
Position 2: BEDDING / INNER COVERING
2FBedding / Inner covering or tapingSHF1 thermoplastic layer or tape separating core from armor
(blank)No bedding layerUsed for unarmored cables or cables with direct sheath over insulation
Position 3: ARMOUR / SCREEN TYPE
3LAluminum (laminated to outer jacket)Aluminum foil/polymer laminate for EMI shielding
XNo armorUnarmored construction for earth/bonding cables
OTinned copper wire braidStandard shielding for NEK 606 cables, ≥80% coverage
AStrength member of yarnAramid/glass fiber strength members (fiber optic cables)
CGalvanized steel wire braidHeavy-duty mechanical protection, high tensile applications
Position 4: OUTER SHEATH TYPE
4IThermoplastic compound SHF1Halogen-free thermoplastic, typically for instrumentation cables
UThermoset compound SHF2EVA-based elastomer, standard NEK 606 sheath, oil resistant
UMud resistant thermoset compound, SHF2 MUDEnhanced formulation passing all mud resistance tests, for drilling operations
Additional Abbreviations (Instrumentation Cables)
Suffix(c)Collective screenSingle shield over all pairs/triples with common drain wire
(i)Individual pair or triple screenEach pair/triple individually shielded with drain wire

4.3 Code Designation Examples

Example 1: RFOU

FLAME RETARDANT

  • R = EPR insulation
  • F = Bedding layer
  • O = Tinned copper wire braid
  • U = Thermoset outer sheath (SHF2)

Application: Most common NEK 606 power cable for offshore platforms. Flame retardant, halogen-free, oil resistant.

Example 2: BFOU

FIRE RESISTANT

  • B = Mica glass tape + EPR insulation
  • F = Bedding layer
  • O = Tinned copper wire braid
  • U = Thermoset outer sheath (SHF2)

Application: Fire resistant cable for emergency systems, fire alarms, emergency lighting. Maintains circuit integrity during fire.

Example 3: RFOU(i)

INSTRUMENTATION

  • R = EPR insulation
  • F = Bedding layer
  • O = Tinned copper wire braid
  • U = Thermoset outer sheath (SHF2)
  • (i) = Individual pair screening

Application: Instrumentation cable with individual pair shields for maximum EMI protection in process control systems.

Example 4: TFOU

FLAME RETARDANT

  • T = XLPE insulation
  • F = Bedding layer
  • O = Tinned copper wire braid
  • U = Thermoset outer sheath (SHF2)

Application: Medium voltage power cable with XLPE insulation for superior electrical performance at 6/10 kV and above.

Example 5: UX

EARTH CABLE

  • U = Thermoset sheath (direct on conductor)
  • X = No armor

Application: Earth/ground cable with single conductor, no insulation required, flame retardant sheath only.

Example 6: BFOU-HCF

HYDROCARBON FIRE

  • BFOU = Standard fire resistant construction
  • -HCF = Hydrocarbon Fire resistant qualification

Application: Enhanced fire resistant cable for hydrocarbon fire scenarios (pool fires). Maintains circuit integrity at 1,100°C per ISO 22899-1.

4.4 Complete Cable Marking Example

Typical Cable Marking

“FEICHUN CABLE” S101 RFOU(i) E-M 250V 2 PAIR 0.75 mm² 2025

Breakdown:
• Manufacturer: FEICHUN CABLE
• Cable Type Code: S101 (NEK 606 designation for instrumentation cable)
• Construction Code: RFOU(i) (EPR/Bedding/Cu Braid/Thermoset, Individual screening)
• Installation: E-M (Explosion risk and Mud resistant areas)
• Voltage Rating: 250V
• Configuration: 2 PAIR (4 conductors arranged as 2 twisted pairs)
• Conductor Size: 0.75 mm² per conductor
• Manufacturing Year: 2025

Installation Classification Codes:

  • E = Explosion risk areas (Zone 1, Zone 2 per IEC 60079)
  • M = Mud resistant (drilling operations exposure)
  • S = Safe areas (no explosion risk)

5. Complete NEK TS 606:2025 Cable Types List

5.1 Power Cables (P-Series)

Type CodeConstructionVoltage RatingKey Features
P101RFOU / TFOU0.6/1 (1.2) kVLow voltage power, flame retardant, most common offshore cable
P102RFOU / TFOU3.6/6 (7.2) kVMedium voltage power distribution
P103RFOU / TFOU6/10 (12) kVMedium voltage, common platform distribution voltage
P104RFOU / TFOU8.7/15 (17.5) kVMedium voltage for large platforms
P105BFOU0.6/1 kVFire resistant, emergency power systems
P106BFOU3.6/6 (7.2) kVFire resistant, medium voltage emergency systems
P107BFOU6/10 (12) kVFire resistant, critical MV systems
P108UX0.6/1 kVEarth/bonding cable, no armor, flame retardant
P109TFLI250 VLighting cable, thermoplastic insulation
P110BU0.6/1 kVFire resistant, unarmored, flexible installation
P111RU / TU0.6/1 kVFlame retardant, unarmored, lightweight
P112RFOU / TFOU12/20 (24) kVHigh voltage distribution
P113RFOU / TFOU18/30 (36) kVHigh voltage, large platform main feeders
P113RFOU / TFOU76/132 (145) kVExtra high voltage, platform-to-shore connections
P114RFOU-HCF / TFOU-HCF6/10 (12) kVHydrocarbon fire resistant, enhanced fire protection
P115RFOU-HCF / TFOU-HCF8.7/15 (17.5) kVHydrocarbon fire resistant, MV applications
P116RFOU-HCF / TFOU-HCF12/20 (24) kVHydrocarbon fire resistant, HV distribution
P117RFOU-HCF / TFOU-HCF18/30 (36) kVHydrocarbon fire resistant, HV feeders
P117RFOU / TFOU-HCF76/132 (145) kVHydrocarbon fire resistant, extra HV applications
P118BFOU-HCF0.6/1 kVFire + Hydrocarbon fire resistant, critical safety systems
P119RX / TX0.6/1 kVEarth cable with EPR/XLPE insulation, no armor
P120RFOU / TFOU – FIRE RESISTANT3.6/6 (7.2) kVSpecial fire resistant qualification (non-standard)
P121RFOU / TFOU – FIRE RESISTANT6/10 (12) kVSpecial fire resistant qualification
P122RFOU / TFOU – FIRE RESISTANT8.7/15 (17.5) kVSpecial fire resistant qualification
P123RFOU / TFOU – FIRE RESISTANT12/20 (24) kVSpecial fire resistant qualification
P124RFOU / TFOU – FIRE RESISTANT18/30 (36) kVSpecial fire resistant qualification
P125SFOU0.6/1 (1.2) kVSilicone fire resistant, extreme temperature applications

Source: NEK TS 606:2025 Annex A – Power Cable Specifications

5.2 Instrumentation Cables (S-Series)

Type CodeConstructionVoltageScreeningApplication
S101RFOU(i)250 VIndividual pairHigh EMI protection instrumentation
S102RFOU(i)c250 VIndividual + CollectiveMaximum EMI protection, dual screening
S103BFOU(i)250 VIndividual pairFire resistant instrumentation, emergency systems
S104BFOU(c)250 VCollectiveFire resistant, collective screen
S105RU(i)250 VIndividual pairUnarmored, individual screening, flexible
S106RU(c) / TU(c)250 VCollectiveUnarmored, collective screen
S107BU(i)250 VIndividual pairFire resistant, unarmored, individual screen
S108BU(c)250 VCollectiveFire resistant, unarmored, collective screen
S109BFOU-HCF(i)250 VIndividual pairHydrocarbon fire + fire resistant, individual screen
S110BFOU-HCF(c)250 VCollectiveHydrocarbon fire + fire resistant, collective screen
S111RX / TX250 VNoneSignal/control cable, no armor, no screening
S112SFOU(i)250 VIndividual pairSilicone fire resistant, individual screen
S113SFOU(c)250 VCollectiveSilicone fire resistant, collective screen

Reeling Cable specialists note that instrumentation cable selection depends on the noise environment, with individually screened pairs (i) providing superior EMI rejection for 4-20mA analog signals and thermocouple circuits.

5.3 Fiber Optic Cables (F-Series)

Type CodeConstructionFiber TypeApplication
F101QFCILoose tube, collective screen, thermoplastic sheathData communication, SCADA, general offshore networking
F102QFCI-HCFLoose tube, hydrocarbon fire resistantCritical communication systems requiring HCF protection
F103QFCBLoose tube, fire resistant (mica tape barrier)Emergency communication systems, fire detection networks
F104AICITight buffered, aramid strength memberCompact installations, harsh environment data links

5.4 DC Power Cables (D-Series)

Type CodeConstructionVoltage RatingApplication
D101RU / TU1500 V DCDC power distribution, battery systems, unarmored
D102RFOU / TFOU1500 V DCDC power distribution, armored, mechanical protection
D103BU1500 V DCFire resistant DC, emergency DC systems, unarmored
D104BFOU1500 V DCFire resistant DC, critical safety systems, armored

6. Compliance with International Standards

6.1 Primary Standards References

StandardTitleApplication in NEK 606
IEC 60092-350Shipboard power cables – general constructionBase standard for cable construction requirements
IEC 60092-353Shipboard power cables – single core non-radial field cablesConstruction requirements for BFOU, BU cables
IEC 60092-354Shipboard power cables – single and multicore screened cablesConstruction for RFOU, TFOU medium/high voltage cables
IEC 60092-360Shipboard insulated cables – materials and testsBase material specifications (NEK 606 requirements more stringent)
IEC 60092-376Instrumentation and telecommunication cablesRequirements for S-series instrumentation cables
IEC 60228Conductors of insulated cablesConductor sizing, stranding classes, resistance values
IEC 60331-21Fire resistance tests – cables ≥20mm diameterMandatory for BFOU fire resistant cables
IEC 60331-31Fire resistance tests – cables <20mm diameterMandatory for small diameter BFOU cables
IEC 60332-1-2Flame propagation – single vertical insulated wire/cableRequired for single core cables, earth cables
IEC 60332-3-22Flame propagation – bundled cables (Category A)Mandatory for all NEK 606 power and control cables
IEC 60754-1Halogen content determination – halogen acid gas contentRequired: ≤5 mg/g halogen for halogen-free claim
IEC 60754-2Halogen content determination – pH and conductivityRequired: pH ≥4.3, conductivity ≤10 μS/mm
IEC 61034-1, -2Smoke density measurementRequired: ≥60% light transmittance (low smoke)
EN 50200Fire resistance with water sprayEnhanced fire test for critical safety circuits
ISO 22899-1Hydrocarbon fire resistance test methodRequired for all -HCF designated cables

6.2 Third-Party Certification Bodies

DNV (Det Norske Veritas)

  • Norwegian classification society
  • Primary certification authority for NEK 606
  • Type approval designation: DNV-CP-0417
  • Factory production control audits
  • Sample testing program

Lloyd’s Register (LR)

  • UK-based classification society
  • Widely accepted in North Sea operations
  • Type approval for NEK 606 cables
  • Material approval program
  • Quality system certification

ABS (American Bureau of Shipping)

  • US classification society
  • Required for US flag vessels
  • NEK 606 recognition program
  • Quarterly production testing
  • Material traceability requirements

Anhui Feichun Special Cable Certifications

Feichun Cable maintains comprehensive third-party approvals for NEK TS 606 cables:

  • DNV Type Approval Certificate (CP-0417) for full NEK 606 product range
  • Lloyd’s Register Type Approval for BFOU and RFOU cables 0.6/1 kV to 35 kV
  • ABS Product Design Assessment for NEK 606 compliance
  • ISO 9001:2015 Quality Management System certification
  • ISO 14001:2015 Environmental Management System certification
  • In-house IEC 17025 accredited testing laboratory

7. Safety Thresholds and Operating Parameters

7.1 Temperature Ratings

Operating ConditionEPR InsulationXLPE InsulationSHF2 Sheath
Minimum Installation Temp-25°C-10°C-15°C
Minimum Operating Temp-40°C-20°C-40°C
Maximum Continuous Operating Temp+90°C+90°C+90°C
Emergency Overload Temp (100h/year)+130°C+130°C+105°C
Short Circuit Temp (5 seconds max)+250°C+250°CN/A

7.2 Voltage Ratings and Insulation Thickness

Voltage Rating U₀/U (Um)Insulation Thickness (mm)
EPR/XLPE
Test Voltage AC (5 min)Typical Applications
150/250 (300) V0.6 – 0.71.5 kVInstrumentation, control, signaling
0.6/1 (1.2) kV0.7 – 2.0 (size dependent)3.5 kVLow voltage power distribution, motors
3.6/6 (7.2) kV2.5 – 3.413 kVMedium voltage distribution, switchgear
6/10 (12) kV3.4 – 4.520 kVPrimary distribution voltage offshore
8.7/15 (17.5) kV4.5 – 5.530 kVLarge platform distribution
12/20 (24) kV5.5 – 6.542 kVHigh voltage platform feeders
18/30 (36) kV6.5 – 8.060 kVPlatform main incoming supply
76/132 (145) kV15 – 18220 kVSubsea transmission, platform interconnection

Voltage notation: U₀ = phase-to-earth voltage, U = phase-to-phase voltage, (Um) = maximum system voltage

7.3 Current-Carrying Capacity (Ampacity)

Ampacity Calculation Factors for NEK 606 Cables

NEK TS 606 cables follow IEC 60287 ampacity calculation methodology with the following considerations:

  • Conductor Temperature: 90°C maximum continuous for EPR and XLPE
  • Ambient Temperature: 45°C air, 25°C seawater (offshore platforms)
  • Grouping Factor: 0.80 for cables touching in trefoil, 0.70 for cables in ladder/tray
  • Armor Loss Factor: Tinned copper braid adds ~3-5% loss, steel braid ~8-12% loss
  • Sheath Loss Factor: Metallic shields/sheaths induce additional losses in AC applications

Example Ampacity (P101 RFOU 0.6/1 kV, 90°C conductor, 45°C ambient, single cable in air):

Conductor Size1-Core2-Core3-Core4-Core
1.5 mm²22 A20 A18 A16 A
2.5 mm²30 A27 A24 A22 A
4 mm²40 A36 A32 A28 A
10 mm²70 A63 A56 A50 A
25 mm²115 A104 A92 A82 A
50 mm²168 A152 A134 A120 A
95 mm²240 A217 A192 A172 A
150 mm²315 A285 A252 A225 A

Values are approximate and must be calculated for specific installation conditions per IEC 60287

8. Precautions for Use and Installation

8.1 Handling and Storage Requirements

Critical Pre-Installation Inspections

  • Drum Condition: Inspect for shipping damage, moisture ingress, or cable end seal integrity. Reject drums with visible damage to flanges or core barrel
  • Cable End Sealing: Verify factory-applied heat-shrink end caps are intact. Re-seal immediately if damaged. Moisture ingress voids warranty
  • Insulation Resistance Testing: Perform IR test using 1000V DC megger before installation. Minimum acceptable: 100 MΩ·km at 20°C. Values <50 MΩ·km indicate moisture contamination
  • Conductor Continuity: Verify continuity of all conductors, screens, and ground paths before pulling
  • Identification: Confirm cable marking matches specification, voltage rating, and construction code
  • Storage Duration: Cables stored >6 months require re-testing before installation. Maximum storage: 24 months in controlled conditions

8.2 Installation Guidelines

According to Mining Cable Chile, proper installation technique is critical for NEK 606 cable longevity in harsh offshore environments.

Installation ParameterRFOU/TFOU CablesBFOU CablesNotes
Minimum Bending Radius (Installation)8 × Cable OD10 × Cable ODDuring pulling only
Minimum Bending Radius (Fixed)6 × Cable OD8 × Cable ODAfter installation
Maximum Pulling Tension50 N/mm² conductor area40 N/mm² conductor areaCalculate per conductor CSA
Maximum Sidewall Pressure300 N per meter of bend radius250 N per meter of bend radiusIn conduit bends
Installation Temperature (Minimum)-10°C-5°CWarm cables if below minimum
Cable LubricantWater-based, non-corrosiveWater-based, non-corrosiveVerify compatibility with sheath
Support Spacing (Vertical)Every 1.0 meterEvery 0.8 meterUse non-metallic cleats
Support Spacing (Horizontal)Every 0.3-0.5 meterEvery 0.3 meterPrevent sagging

8.3 Termination Requirements

Low Voltage (≤1 kV)

  • Strip sheath and armor using appropriate tools
  • Remove 40-60 mm armor, 80-100 mm sheath
  • Bond tinned copper braid to ground terminal
  • Use compression or mechanical lugs rated for tinned copper
  • Apply shrink boots over termination for IP protection
  • Minimum creepage distance: 10 mm per kV

Medium Voltage (>1 kV)

  • Use only manufacturer-approved termination kits
  • Clean insulation surface with 99% isopropanol
  • Score semiconductor shield circumferentially before removal
  • Apply stress control cone/boot per kit instructions
  • Verify cone position aligns with shield termination ±5 mm
  • Ground metallic shield at both cable ends
  • Minimum strike distance per voltage rating

Instrumentation Cables

  • Preserve pair twist to termination point
  • Terminate drain wires to dedicated ground terminal
  • Individual screens: ground one end only (signal reference)
  • Collective screen: ground both ends
  • Maintain shield continuity through connectors
  • Use numbered ferrules matching cable identification

8.4 Testing After Installation

Mandatory Commissioning Tests

Before Energization:

  1. Insulation Resistance Test: 1000V DC megger, 1 minute soak time. Minimum IR: 100 MΩ·km
  2. Conductor Continuity: <1.0 Ω end-to-end for all conductors, screens, grounds
  3. Phase Identification: Verify correct phasing using phase rotation meter
  4. High Voltage Test (if specified): 80% of factory test voltage for 1 minute. Note: Not recommended for aged cables
  5. Functional Test: Energize at reduced voltage, verify connected equipment operates correctly

Annual Maintenance Testing:

  • Insulation resistance (trending program, compare to baseline)
  • Infrared thermography of terminations under load
  • Visual inspection for mechanical damage, corrosion, jacket deterioration
  • Partial discharge testing for MV cables (offline or online)

9. Common Problems and Troubleshooting

9.1 Installation-Related Failures

ProblemSymptomsRoot CausePrevention/Solution
Low Insulation ResistanceIR <50 MΩ·km, may trip ground fault protectionMoisture ingress through damaged end seal or damaged sheathInspect end seals before installation, replace cable if IR cannot be restored by drying
Jacket AbrasionSurface wear, exposed armor/bedding, reduced jacket thicknessImproper pulling technique, sharp cable tray edges, excessive frictionUse adequate lubrication, inspect cable path, apply protective sleeving at wear points
Armor Braid DamageBroken braid wires, loss of screen continuity, EMI issuesExceeding minimum bending radius, kinking during handlingVerify bending radius compliance, use appropriate pulling equipment, train personnel
Conductor BreakageOpen circuit, intermittent connection during vibrationExcessive pulling tension, sharp bends, conductor fatigueMonitor pulling tension with load cell, respect minimum bend radii, replace damaged section
Shield Termination ErrorsCirculating currents, overheating, ground loops, EMI problemsIncorrect grounding scheme (both ends grounded when should be single-point)Follow manufacturer grounding diagram, use insulated glands when required, ground shields correctly

9.2 Service-Related Issues

ProblemSymptomsDiagnostic MethodCorrective Action
Mud Attack on SheathSheath softening, swelling, cracking, loss of mechanical propertiesVisual inspection, Shore A hardness test, tensile/elongation testingVerify cable has SHF2 MUD rating, replace if severely degraded, prevent mud contact with protective measures
Oil-Induced DegradationSheath swelling, plasticizer extraction, brittlenessMeasure sheath diameter change, conduct oil resistance test per IEC 60092-360Confirm cable meets enhanced oil resistance requirements, replace with properly rated cable
UV Degradation (Exposed Cables)Surface chalking, color fading, embrittlement, crackingVisual examination, elongation at break test (should be >300%)Install cables in conduit/tray, apply UV-resistant paint or tape, replace if mechanically compromised
Overheating at TerminationsDiscoloration, melting of components, tripped overload protectionInfrared thermography (hot spots >15°C above ambient suspect), contact resistance measurementDe-energize, re-torque connections, clean oxidation, replace damaged lugs, verify proper conductor preparation
Partial Discharge ActivityAudible noise, ozone smell, progressive insulation degradation, eventual failureOnline or offline PD testing, locate discharge source, measure magnitude in pCInvestigate termination quality, check for moisture ingress, consider cable replacement if PD >50 pC
Ground FaultGround fault relay operation, loss of power, visible arcingIR testing (phase-to-ground), time domain reflectometry for fault locationLocate fault using TDR or tracer, excavate/expose cable, cut out damaged section and splice, or replace cable

9.3 Fire Performance Concerns

Post-Fire Cable Assessment

After a fire incident on an offshore platform, all cables in the affected zone must be assessed before returning to service:

Visual Inspection:

  • Discoloration, charring, or melting of jacket material
  • Deformation or sagging indicating excessive heat exposure
  • Exposed conductor or insulation
  • Damage to support systems or cable trays

Electrical Testing:

  • Insulation resistance: must meet new cable standards (>100 MΩ·km)
  • Dielectric withstand test at 80% factory voltage (consult with manufacturer)
  • Continuity verification of all conductors and grounds
  • Partial discharge testing to detect insulation damage

Decision Criteria:

  • Replace: Any cable showing visible damage, IR <50 MΩ·km, or PD >10 pC
  • Monitor: Cables passing electrical tests but in fire zone – implement enhanced surveillance program
  • Return to Service: Only cables completely outside fire/smoke zone with normal test results

Critical Note: Fire resistant BFOU cables that maintained circuit integrity during fire should still be replaced after incident, as mica tape barrier may be compromised even if cable functioned during emergency.

10. Selecting the Correct NEK 606 Cable Type

10.1 Selection Decision Tree

Step-by-Step Cable Selection Process

Step 1: Determine Fire Performance Requirement

  • Question: Must the cable maintain circuit integrity during fire?
  • YES → Use BFOU (fire resistant) for: Emergency shutdown systems, fire/gas detection, emergency lighting, public address, fire pump power, life safety systems
  • NO → Use RFOU/TFOU (flame retardant) for: General power distribution, non-critical instrumentation, lighting in safe areas

Step 2: Determine Voltage Level

  • Instrumentation & Control: 250V (S-series)
  • Low Voltage Power: 0.6/1 kV (P101, P105)
  • Medium Voltage: 3.6/6 kV to 18/30 kV (P102-P104, P106-P107, P112-P113)
  • High Voltage: 76/132 kV (P113)

Step 3: Assess Environmental Exposure

  • Drilling Mud Exposure: Specify SHF2 MUD resistant sheath (all drilling areas)
  • Hydrocarbon Pool Fire Risk: Specify -HCF designation (process areas, wellhead)
  • Mechanical Damage Risk: Consider galvanized steel braid armor (C) instead of copper braid (O)
  • Weight Constraints: Consider unarmored types (RU, BU, TU) where mechanical protection not essential

Step 4: Select Insulation Material

  • EPR (R): Superior low-temperature flexibility (-40°C), preferred for instrumentation and arctic applications
  • XLPE (T): Better electrical properties, higher ampacity, preferred for medium/high voltage power

Step 5: Determine Screening Requirements (Instrumentation Only)

  • Individual (i): Each pair/triple separately screened, maximum EMI protection, 4-20mA analog signals
  • Collective (c): Single screen over all pairs, adequate for digital signals, lower cost
  • Combination (i+c): Individual plus collective screening, maximum protection in extreme EMI environments

10.2 Application-Specific Recommendations

ApplicationRecommended TypeRationale
Emergency Shutdown (ESD) SystemS103 BFOU(i) 250VFire resistant, individual screening, maintains function during fire
Fire & Gas DetectionS103 BFOU(i) 250VFire resistant, EMI protected, life safety critical
Emergency LightingP105 BFOU 0.6/1 kVFire resistant power cable, maintains lighting during evacuation
Process Control (4-20mA)S101 RFOU(i) 250VIndividual screening prevents signal interference, adequate fire performance
DCS Digital I/OS102 RFOU(c) 250V or S102 RFOU(i)c 250VCollective screening adequate for digital, double screening for noisy areas
Main Platform Power (10 kV)P103 TFOU 6/10 kVXLPE offers best electrical performance and ampacity for power feeders
Drilling Equipment PowerP101 RFOU 0.6/1 kV (SHF2 MUD)Mud resistant rating essential, EPR flexibility advantage
Variable Frequency Drive (VFD)P101 RFOU 0.6/1 kV + additional copper braidStandard power cable with enhanced screening for VFD noise
Thruster Motor PowerP102 TFOU 3.6/6 kVMV power, seawater environment, XLPE moisture resistance
Wellhead Control PanelS101 RFOU(i) 250V (SHF2 MUD)Instrumentation cable, mud resistant, hydrocarbon exposure
Helideck LightingP105 BFOU 0.6/1 kVFire resistant for life safety, outdoor UV exposure
Telecommunications/DataF101 QFCI or F103 QFCBFiber optic, QFCB if fire resistance required for critical data
Cathodic ProtectionD102 RFOU 1500V DCDC rated, suitable for impressed current systems
UPS Battery StringsD103 or D104 BFOU 1500V DCFire resistant DC cable for emergency power backup

Expert Cable Selection Service

Feichun Cable provides comprehensive technical support for NEK TS 606 cable selection:

  • Application-specific cable recommendations based on project specifications
  • Ampacity calculations for actual installation conditions
  • Cable schedule review and optimization
  • Third-party certification coordination (DNV, LR, ABS)
  • Factory acceptance testing witness services
  • Installation supervision and commissioning support

Contact our technical team:

11. Conclusion

NEK TS 606:2025 represents the pinnacle of cable specifications for offshore and marine applications, providing comprehensive requirements that ensure safety, reliability, and performance in the world’s most challenging environments. The systematic code designation system enables precise cable identification and selection, while the rigorous testing requirements guarantee that cables will perform as expected when lives depend on them.

Understanding the NEK 606 cable code designation is essential for engineers, procurement specialists, and installation personnel working in the offshore oil and gas industry. The distinction between fire resistant (BFOU) and flame retardant (RFOU/TFOU) cables is particularly critical, as incorrect selection can compromise life safety systems during emergencies.

The 2025 edition of NEK TS 606 continues to evolve, incorporating lessons learned from decades of offshore operations and advancing cable technology. The addition of hydrocarbon fire resistant (-HCF) designations and enhanced mud resistance requirements reflects the industry’s commitment to continuous improvement in safety and reliability.

Key Takeaways

  • NEK TS 606 is more stringent than IEC 60092 series, particularly for oil/mud resistance
  • The 4-letter code system (e.g., RFOU, BFOU) precisely describes cable construction
  • Fire resistant (B) cables must maintain circuit integrity for 2-3 hours during fire
  • Flame retardant (R/T) cables prevent fire propagation but do not maintain circuit function
  • All NEK 606 cables are halogen-free, low smoke, and either oil resistant or mud resistant
  • Third-party certification (DNV, LR, ABS) is essential for offshore applications
  • Proper installation technique and post-installation testing are critical for reliability
  • Cable selection must consider application criticality, environmental exposure, and voltage requirements

12. References and Additional Resources

Standards and Specifications

  • NEK TS 606:2025 – Cables for Offshore Installations (Norwegian Electrotechnical Committee)
  • IEC 60092 series – Electrical installations in ships (Parts 350, 353, 354, 360, 376)
  • IEC 60331-21, -31 – Fire resistance tests for electric cables
  • IEC 60332-1-2, -3-22 – Flame propagation tests
  • IEC 60754-1, -2 – Halogen content determination
  • IEC 61034-1, -2 – Smoke density measurement
  • IEC 60228 – Conductors of insulated cables
  • IEC 60287 series – Calculation of current rating
  • ISO 22899-1 – Determination of the resistance to fire of cables – Hydrocarbon fire
  • EN 50200 – Method of test for resistance to fire for cables with water spray

Technical content compiled from NEK TS 606:2025, IEC standards, DNV certification guidelines, and manufacturer technical documentation

Previous Article

Mining Cable: Comprehensive Glossary of Cable Terms

Next Article

HD 626 S1 Type 9F Cable Code Designation: Comprehensive Technical Guide