Galvanized Steel Pliable Wire Armoured Trailing Cable for Excavating and Crushing Machinery in Explosive Atmosphere Mining Applications — A Comprehensive Technical Reference

What is Type 20 BS 6708 Mining Cable?
Galvanized Steel Pliable Wire Armoured Trailing Cable for Excavating and Crushing Machinery in Explosive Atmosphere Mining Applications — A Comprehensive Technical Reference
Introduction to BS 6708 Type 20 Mining Cable
The BS 6708 Type 20 mining cable represents a specialized category of galvanized steel pliable wire armoured flexible cables engineered for the most demanding mining and quarrying applications. This cable type is characterized by its robust construction featuring three unscreened cores laid up around an elastomeric cradle without contacting each other, protected by galvanized steel pliable armour that provides exceptional mechanical protection while maintaining the flexibility essential for mobile mining equipment applications.
According to BS 6708:1998 standard documentation, Type 20 and Type 21 cables are specifically categorized as cables with galvanized steel pliable wire armouring having unscreened cores and a rated voltage of 640/1100V. This classification distinguishes them from screened cable types (such as Types 7, 201, 211) that incorporate individual metallic screens around each core, and positions them as the preferred choice for applications requiring maximum mechanical protection without the electromagnetic interference shielding requirements.
The development of Type 20 cables reflects the mining industry’s need for cables that can withstand severe mechanical abuse while maintaining reliable electrical performance in potentially explosive atmospheres. As detailed by AmplexMining.com.au’s comprehensive mining cable guide, mining cables must possess exceptional ruggedness to survive crushing forces from heavy equipment, abrasion from constant contact with rough surfaces, and the mechanical stress of being dragged, twisted, and flexed thousands of times during their service life. The galvanized steel pliable armour in Type 20 cables specifically addresses these requirements while maintaining sufficient flexibility for trailing cable applications.
The unscreened core design of Type 20 cables offers distinct advantages in applications where electromagnetic interference shielding is not critical. This construction results in reduced cable weight and diameter compared to equivalent screened cables, important considerations for mobile equipment where every kilogram of cable weight affects operational efficiency. According to Cleveland Cable Company specifications, Type 20 cables are manufactured with conductor sizes ranging from 2.5mm² to 150mm², enabling power delivery for applications ranging from auxiliary equipment to major excavating machinery.
Purpose and Primary Applications
Core Application Areas
BS 6708 Type 20 mining cables serve as critical power transmission lifelines for heavy-duty mining equipment operating in the most challenging environments. Their primary applications include:
Excavating Machinery
- Electric Shovels: Requiring power delivery up to 320A (150mm² configuration) for digging operations
- Draglines: Large-scale earthmoving equipment with substantial power requirements
- Bucket-wheel Excavators: Continuous mining operations demanding reliable power transmission
- Face Shovels and Hydraulic Excavators: Mobile earth-moving equipment in surface mining
Crushing and Processing Equipment
- Primary Jaw Crushers: High-power motors requiring cables with excellent mechanical protection
- Secondary Cone Crushers: Continuous operation machinery in aggressive environments
- Mobile Crushing Plants: Relocatable equipment requiring trailing cable configurations
- Screening and Sizing Equipment: Processing machinery with variable power demands
Ancillary Mining Equipment
- Conveyor Drive Systems: Material transport infrastructure requiring robust power supply
- Pumping Stations: Dewatering equipment in underground and surface operations
- Ventilation Systems: Critical safety equipment in underground mining
- Loading Equipment: Material handling machinery at mining faces
Operating Environments
The operating environments for Type 20 cables span both underground and surface mining operations:
Underground Mining Applications
In underground coal mines, Type 20 cables power equipment in development headings, longwall panels, and roadway installations. The cables must withstand:
- Methane concentrations up to 5% by volume (Lower Explosive Limit)
- Coal dust accumulation creating explosive atmospheres
- High humidity levels (often exceeding 95% RH)
- Roof convergence and ground movement stresses
- Temperature ranges from 15°C to 45°C in deep mines
Surface Mining Operations
Surface applications present different but equally challenging conditions:
- Extreme temperature variations (-20°C to +85°C ambient)
- UV radiation exposure from solar radiation
- Mechanical damage from mobile equipment operations
- Chemical exposure from mineral processing operations
- Abrasion from rocky terrain and material handling
According to ReelingCable.com technical specifications, professional mining cables for heavy-duty mobile equipment must provide fire retardancy, oil resistance, and temperature performance ranging from -50°C to +80°C. Type 20 cables achieve comparable performance characteristics through their EPR insulation and chloroprene sheath combination, making them suitable for both underground mining, surface mining, and quarry operations.
Quarrying Applications
Quarrying operations utilize Type 20 cables for:
- Dimension Stone Extraction: Granite, marble, and limestone quarries
- Aggregate Production: Sand, gravel, and crushed stone facilities
- Mineral Extraction: Industrial minerals and chemical feedstock production
Cable Construction and Material Structure
The Type 20 cable construction represents sophisticated engineering where each layer serves specific protective and functional purposes. The multi-layer design provides the mechanical robustness essential for mining applications while maintaining electrical performance under adverse conditions.
Electrolytic, stranded, tinned copper wire conforming to IEC 60228 Class 5 specifications. Class 5 conductors represent the most flexible stranding classification, utilizing fine-wire construction with high strand counts. For example, the 2.5mm² conductor employs 50 strands × 0.25mm diameter wires, while the 150mm² conductor uses 740 strands × 0.50mm diameter wires.
• Electrical Conductivity: ≥58 MS/m (100% IACS reference)
• Tinning Process: Hot-dip or electroplating for corrosion protection
• Strand Configuration: Concentric or rope-lay stranding for maximum flexibility
• Breaking Strength: Maintains circuit integrity even with partial strand damage
EPR insulation provides exceptional electrical and thermal performance essential for mining applications. According to Eland Cables technical documentation, EPR offers high dielectric strength with thermal ranges from -55°C to 150°C, excellent ozone and weathering resistance, and superior flexibility compared to XLPE insulation.
• Dielectric Strength: >20 kV/mm
• Maximum Conductor Temperature: 90°C (continuous operation)
• Short-Circuit Temperature: 200°C (maximum 5 seconds)
• Volume Resistivity: >10¹⁴ Ω·cm
• Dielectric Constant (εr): 2.5-3.5 at 1 kHz
• Dissipation Factor (tan δ): <0.01 at 1 kHz
EPR insulation maintains its properties even after prolonged exposure to the harsh conditions found in mining environments. The cross-linked molecular structure resists partial discharge degradation, ensuring long-term dielectric reliability. Unlike thermoplastic insulations, EPR does not soften at elevated temperatures, maintaining mechanical integrity throughout the rated temperature range.
Three unscreened cores are laid up around an elastomeric cradle without contacting each other. This specific configuration provides several critical advantages:
- Thermal Management: Air gaps between cores enhance heat dissipation, allowing higher current loading
- Electrical Balance: Symmetrical positioning ensures balanced inductance and capacitance per phase
- Mechanical Flexibility: Individual core movement reduces internal stress during flexing
- Fault Isolation: Physical separation minimizes risk of inter-phase faults
The elastomeric cradle, typically made from the same EPR compound as the insulation, maintains consistent core spacing while accommodating differential movement during cable bending. This design is critical for trailing cable applications where repeated flexing occurs.
Rubber-based bedding compound serves as a protective barrier between the cable cores and the metallic armour. This layer performs multiple functions:
• Mechanical cushioning to prevent armour wires from damaging core insulation
• Accommodation of differential thermal expansion between polymeric and metallic components
• Moisture barrier preventing water migration along cable length
• Load distribution during cable bending and mechanical stress
• Fire barrier retarding flame propagation along cable core
The galvanized steel pliable wire armour represents the defining characteristic of Type 20 cables, providing exceptional mechanical protection while maintaining flexibility. According to Tratos Group armoured cable specifications, pliable wire armour (PWA) cables are specifically designed for mining and quarrying applications where cables require armoured protection but also need to be moved infrequently.
• Material: Low-carbon steel wires with zinc galvanization
• Galvanization: Hot-dip zinc coating ≥40 g/m² for corrosion protection
• Wire Configuration: Multiple steel wires wound helically with close coverage
• Tensile Strength: 350-550 N/mm² (wire material)
• Armour Resistance: 0.41-4.2 Ω/km (dependent on cable size)
• Coverage: ≥85% mechanical coverage for protection
The armour resistance values (ranging from 4.2 Ω/km for 2.5mm² to 0.41 Ω/km for 150mm²) provide essential earth fault current path capability. This armour serves as the primary protective earth conductor, providing low-impedance fault current path for protective device operation. Some mining regulations require armour conductivity to be at least 50% of the main conductor conductivity, which may necessitate incorporating tinned copper wires within the armour construction for larger cable sizes.
The heavy-duty chloroprene (polychloroprene/neoprene) outer sheath provides the cable’s primary environmental protection. According to Tratos Cable Academy polymeric materials reference, chloroprene offers self-extinction properties after fire exposure, reasonable resistance to solvents and oils, and excellent weathering characteristics—qualities specifically specified for colliery trailing cables due to their superior abrasion and oil resistance.
• Tensile Strength: 10-15 MPa (minimum)
• Elongation at Break: 300-400% (minimum)
• Abrasion Resistance: Superior to natural rubber compounds
• Temperature Range: -40°C to +120°C (intermittent)
• Oil Resistance: Good resistance to mineral oils and greases
• Ozone Resistance: Excellent (critical for surface installations)
• Flame Retardance: Self-extinguishing, compliant with EN 60332-1-2
• Chemical Resistance: Resistant to acids, alkalis, and many industrial chemicals
The “heavy duty” designation indicates enhanced thickness and formulation for severe mechanical service. This sheath must withstand continuous abrasion against rock surfaces, impact from falling debris, and exposure to mining chemicals while maintaining protective integrity throughout the cable’s service life.
Dimensional Specifications and Physical Parameters
The dimensional specifications of BS 6708 Type 20 cables reflect careful optimization for mining applications, balancing mechanical protection with practical installation requirements. The following comprehensive table presents the complete dimensional data across the full range of available conductor sizes:
| CCC Code | Conductor Size (mm²) | No. of Phase Cores | Conductor Stranding (mm) | Min. Bending Radius (mm) | Weight (kg/km) | Max. Overall Diameter (mm) |
|---|---|---|---|---|---|---|
| TYPE203X2/5 | 2.5 | 3 | 50/0.25 | 243 | 990 | 26.9 |
| TYPE203X4 | 4 | 3 | 56/0.30 | 254 | 1,150 | 28.2 |
| TYPE203X6 | 6 | 3 | 84/0.30 | 329 | 2,000 | 36.5 |
| TYPE203X10 | 10 | 3 | 80/0.40 | 346 | 2,350 | 38.4 |
| TYPE203X16 | 16 | 3 | 126/0.40 | 368 | 2,750 | 40.8 |
| TYPE203X25 | 25 | 3 | 196/0.40 | 423 | 3,350 | 47.0 |
| TYPE203X35 | 35 | 3 | 276/0.40 | 456 | 4,300 | 50.6 |
| TYPE203X50 | 50 | 3 | 396/0.40 | 511 | 5,320 | 56.7 |
| TYPE203X70 | 70 | 3 | 360/0.50 | 565 | 6,750 | 62.7 |
| TYPE203X95 | 95 | 3 | 475/0.50 | 649 | 8,750 | 72.1 |
| TYPE203X120 | 120 | 3 | 629/0.50 | 693 | 10,650 | 77.0 |
| TYPE203X150 | 150 | 3 | 740/0.50 | 786 | 12,500 | 87.3 |
Dimensional Analysis and Engineering Implications
Minimum Bending Radius
The minimum bending radius specifications range from 243mm (2.5mm²) to 786mm (150mm²), representing approximately 9× the overall cable diameter. This ratio is critical for:
- Preventing conductor strand breakage during installation
- Avoiding armour wire damage and distortion
- Maintaining bedding compound integrity
- Ensuring outer sheath does not crack or deform permanently
Cable Weight Considerations
Cable weights ranging from 990 kg/km (2.5mm²) to 12,500 kg/km (150mm²) have significant implications for installation and operation:
• 100m of 50mm² cable weighs approximately 532 kg
• 100m of 120mm² cable weighs approximately 1,065 kg
• Support structure design must account for static and dynamic loading
• Equipment pulling capacity must exceed cable weight plus friction forces
• Vertical installations require armour load-bearing calculations
Strand Configuration Optimization
The conductor stranding progression demonstrates careful engineering optimization:
- Small conductors (2.5-4mm²): 0.25-0.30mm diameter wires for maximum flexibility
- Medium conductors (6-35mm²): 0.30-0.40mm diameter wires balancing flexibility and manufacturing
- Large conductors (50-150mm²): 0.40-0.50mm diameter wires maintaining practical strand counts
The transition to 0.50mm wires at 70mm² and above keeps strand counts manageable (360-740 strands) while maintaining Class 5 flexibility requirements.
Electrical Characteristics and Performance Parameters
The electrical performance of BS 6708 Type 20 cables is meticulously specified to ensure reliable power transmission in demanding mining applications. The following comprehensive table presents the critical electrical parameters:
| CCC Code | Conductor Size (mm²) | Continuous Current Rating (A) | Conductor Resistance (Ω/km) | Armour Resistance (Ω/km) | 3-Phase Voltage Drop (mV/A/m) |
|---|---|---|---|---|---|
| TYPE203X2/5 | 2.5 | 28 | 8.21 | 4.2 | — |
| TYPE203X4 | 4 | 37 | 5.09 | 3.9 | 10 |
| TYPE203X6 | 6 | 46 | 3.39 | 2.0 | 6.8 |
| TYPE203X10 | 10 | 63 | 1.95 | 1.9 | 6.8 |
| TYPE203X16 | 16 | 85 | 1.24 | 1.7 | 2.5 |
| TYPE203X25 | 25 | 110 | 0.795 | 1.5 | 1.65 |
| TYPE203X35 | 35 | 135 | 0.565 | 1.1 | 1.20 |
| TYPE203X50 | 50 | 170 | 0.393 | 0.96 | 0.84 |
| TYPE203X70 | 70 | 205 | 0.277 | 0.80 | 0.61 |
| TYPE203X95 | 95 | 250 | 0.210 | 0.73 | 0.47 |
| TYPE203X120 | 120 | 295 | 0.164 | 0.47 | 0.38 |
| TYPE203X150 | 150 | 320 | 0.132 | 0.41 | 0.30 |
Voltage Drop Analysis and System Design
The three-phase voltage drop values (mV/A/m) provide critical information for electrical system design in mining applications. For extended cable runs, voltage drop calculations determine equipment performance:
Equipment: Mobile crusher with 75kW motor at 1000V, 3-phase
Cable: TYPE203X50 (50mm²), Length: 200 meters
Motor Full Load Current: IFL = 75,000 ÷ (√3 × 1000 × 0.85) ≈ 51A
ΔV = 0.84 mV/A/m × 51A × 200m = 8,568 mV = 8.57V
Percentage Voltage Drop = (8.57 ÷ 1000) × 100 = 0.86%
This is well within typical mining regulations requiring <5% voltage drop for motor circuits.
Conductor Resistance Compliance
The conductor resistance values comply with IEC 60228 Class 5 requirements for tinned copper conductors. The resistance values account for:
- Reference temperature of 20°C
- Tinning process resistance increase (typically 2-3%)
- Stranding factor for fine-wire construction
Temperature correction for conductor resistance at operating temperatures:
Where α₂₀ = 0.00393 /°C for copper
• At 50°C: R = 0.210 × [1 + 0.00393 × 30] = 0.235 Ω/km (+11.8%)
• At 70°C: R = 0.210 × [1 + 0.00393 × 50] = 0.251 Ω/km (+19.5%)
• At 90°C: R = 0.210 × [1 + 0.00393 × 70] = 0.268 Ω/km (+27.6%)
Armour Earth Fault Current Capability
The armour resistance values are critical for earth fault protection coordination. The armour must carry fault current long enough for protective devices to operate. For a phase-to-armour fault:
Where Zloop includes source impedance, phase conductor resistance, and armour resistance.
Cable: TYPE203X70 (70mm²), 150m length
Conductor Resistance: 0.277 Ω/km × 0.15 km = 0.0416 Ω
Armour Resistance: 0.80 Ω/km × 0.15 km = 0.120 Ω
Total Loop Resistance (one-way): 0.0416 + 0.120 = 0.162 Ω
Assuming phase voltage 640V and source impedance 0.05Ω:
Ifault = 640 ÷ (0.162 + 0.05) ≈ 3,019A
This fault current level ensures rapid operation of protective devices (typically <0.4s for 5× rated current).
Current Carrying Capacity Derating
The continuous current ratings assume specific installation conditions. Derating factors must be applied for:
| Ambient Temperature (°C) | Derating Factor | 120mm² Adjusted Rating (A) |
|---|---|---|
| 25 (reference) | 1.00 | 295 |
| 35 | 0.94 | 277 |
| 45 | 0.87 | 257 |
| 55 | 0.79 | 233 |
| 65 | 0.71 | 209 |
| 75 | 0.61 | 180 |
Standards Compliance and Certification Requirements
Primary Standard: BS 6708
BS 6708:1998 “Flexible cables for use at mines and quarries” provides the comprehensive framework for Type 20 cables. According to Standards.ie BS 6708:1998 documentation, this standard specifies requirements for cables with galvanized steel pliable wire armouring rated at various voltages up to 3800/6600V, with Types 20, 21, 62, 63, 70, 71, 201, 211, 321 and 331 falling under Section 7 of the standard.
• Section 7: Cables with galvanized steel pliable wire armouring
• Subsection: Unscreened cores, rated voltage 640/1100V
• Annexes provide supplementary information:
– Annex A: Approved codes of practice and conductivities
– Annex B: Recommended current ratings
– Annex C: Short-circuit current carrying capability of flexible cable screens/armour
Referenced International Standards
| Standard | Title | Application to Type 20 |
|---|---|---|
| IEC 60228 | Conductors of insulated cables | Class 5 flexible conductor specifications |
| IEC 60724 | Short-circuit temperature limits | 200°C maximum for EPR @ 5 seconds |
| BS 7655-1.2 | Cross-linked elastomeric insulating compounds | EPR compound specifications |
| BS 7655-2.3 | Cross-linked elastomeric sheathing compounds | Chloroprene sheath requirements |
| EN 60332-1-2 | Flame propagation test | Single cable vertical flame test |
| BS 5467 | Electric cables with thermosetting insulation | Armoured cable construction practices |
Testing Requirements
• Conductor resistance measurement (IEC 60228 compliance)
• Voltage test: 3kV AC for 5 minutes (phase-to-phase and phase-to-armour)
• Insulation resistance: ≥100 MΩ·km at 20°C
• Partial discharge test: <10 pC at 1.5× U₀
• Bending test: Minimum bending radius compliance
• Tensile strength and elongation (EPR and chloroprene)
• Hot set test for cross-linked EPR
• Armour wire galvanization thickness (≥40 μm)
• Flame retardance test (EN 60332-1-2)
• Conductor resistance per length
• Voltage withstand test at 3kV AC
• Insulation resistance measurement
• Armour continuity verification
• Dimensional compliance check
• Visual inspection for defects
Comparison with VDE 0250-812 German Standard Mining Cables
Understanding the relationship between BS 6708 Type 20 and German VDE 0250 Part 812 mining cables provides valuable insight into international mining cable specifications and enables proper cable selection for global mining operations.
BS 6708 Type 20
- ✓ Rated Voltage: 640/1100V
- ✓ Core Configuration: 3 unscreened cores
- ✓ Insulation: EPR (Ethylene Propylene Rubber)
- ✓ Protection: Galvanized steel pliable armour
- ✓ Sheath: Heavy-duty chloroprene
- ✓ Temperature Range: -20°C to +85°C
- ✓ Short-Circuit Temp: 200°C (5 sec)
- ✓ Test Voltage: 3kV
- ✓ Primary Use: Excavating/crushing machines
- ✓ Earth System: Via armour conductivity
VDE 0250-812 NSSHÖU
- ✓ Rated Voltage: Up to 450/750V
- ✓ Core Configuration: Multiple core options
- ✓ Insulation: EPR (compound 3GI3)
- ✓ Protection: Optional armour configurations
- ✓ Sheath: Chloroprene (compound 5GM5)
- ✓ Temperature Range: -40°C to +80°C
- ✓ Short-Circuit Temp: 250°C
- ✓ Test Voltage: 2-3kV
- ✓ Primary Use: Trailing/reeling applications
- ✓ Earth System: Dedicated PE conductor
Key Technical Differences
Voltage Rating and Power Capacity
BS 6708 Type 20 cables operate at 640/1100V, providing higher voltage capability compared to standard VDE 0250-812 cables rated at 450/750V. This higher voltage rating enables:
- Reduced current for equivalent power transfer (P = √3 × V × I × pf)
- Smaller conductor sizes for same power capacity
- Extended cable run lengths with acceptable voltage drop
- Direct connection to 1000V mining distribution systems
At 750V (VDE): I = 100,000 ÷ (1.732 × 750 × 0.85) = 90.5A
At 1100V (BS 6708): I = 100,000 ÷ (1.732 × 1100 × 0.85) = 61.8A
Result: 31.7% current reduction enables smaller conductor sizing or longer cable runs.
Mechanical Protection Philosophy
Type 20 cables feature galvanized steel pliable wire armour as mandatory construction, providing:
- Superior impact and crush resistance
- Protection against cable cuts and abrasion
- Rodent and vermin protection
- Integrated earth fault current path
VDE 0250-812 cables may or may not include armour, with unarmoured variants (NSSHÖU) optimized for maximum flexibility in trailing applications. The DIN VDE 0250 Part 812 standard, according to DIN Media, specifies requirements for rubber insulated flexible cables NSSHÖU, focusing on elastomeric flexibility rather than armoured protection.
Earth Fault Protection Strategy
| Parameter | BS 6708 Type 20 | VDE 0250-812 |
|---|---|---|
| Earth Path | Steel wire armour | Dedicated PE conductor |
| Earth Continuity Monitoring | Via armour resistance | Pilot conductor monitoring |
| Fault Current Capacity | Limited by armour cross-section | Full copper conductor capacity |
| Installation Verification | Armour bonding at both ends | Conductor continuity test |
Temperature Performance
Both cable types utilize EPR insulation with similar thermal characteristics. However, notable differences exist:
BS 6708 Type 20:
• Operating: -20°C to +85°C (fixed installation)
• Installation: +5°C to +60°C
• Short-Circuit: 200°C (5 seconds maximum)
VDE 0250-812 NSSHCGEÖU:
• Operating: -40°C to +80°C (ambient)
• Conductor Maximum: 90°C (continuous)
• Short-Circuit: 250°C
VDE cables offer better cold flexibility (-40°C vs -20°C) due to optimization for outdoor surface operations, while BS 6708 Type 20 emphasizes mechanical protection over extreme temperature flexibility.
Application Suitability
Choose BS 6708 Type 20 when:
- Maximum mechanical protection is required
- Cable will be subject to impact, crushing, or severe abrasion
- Installation in rocky terrain or areas with falling debris
- Higher voltage distribution (1000V systems) is utilized
- Armoured cable is mandated by local mining regulations
Choose VDE 0250-812 when:
- Maximum flexibility for continuous reeling/trailing is needed
- Dedicated earth continuity monitoring is required
- Extreme cold temperature operation (-40°C) is anticipated
- Weight minimization is critical
- European regulatory compliance is mandatory
Safety Thresholds and Critical Precautions
BS 6708 Type 20 cables operate in potentially explosive atmospheres where improper installation, operation, or maintenance can result in ignition of flammable gases, fires, electrical shock fatalities, or catastrophic equipment damage. All work must be performed by competent persons in accordance with applicable mining safety legislation and manufacturer specifications.
Electrical Safety Parameters
Voltage Withstand and Testing
The 3kV test voltage provides safety margins for the 640/1100V operating voltage:
• Test Voltage: 3,000V
• Maximum Operating Voltage: 1,100V
• Safety Factor: 3,000 ÷ 1,100 = 2.73×
This margin accommodates:
• Switching transients (up to 2× nominal voltage)
• Lightning-induced surges
• Motor starting inrush effects
• Insulation degradation over service life
• Manufacturing tolerances
Current Overload Protection
The maximum conductor temperature of 90°C continuous must not be exceeded. Overload conditions cause:
- Accelerated insulation aging (Arrhenius equation: every 10°C increase halves insulation life)
- Thermal expansion stresses on terminations
- Risk of fire initiation in cable trays
- Softening of bedding compound
Overcurrent protection must be sized to disconnect supply before conductor temperature exceeds 90°C. For typical EPR-insulated cables, protection must operate within:
• 120% rated current: <2 hours
• 150% rated current: <30 minutes
• 200% rated current: <2 minutes
• 500% rated current: <10 seconds
Short-Circuit Thermal Limits
The 200°C (maximum 5 seconds) short-circuit temperature limit defines the permissible let-through energy (I²t):
Where K = 143 for EPR copper cables (90°C to 200°C)
| Conductor Size (mm²) | Maximum I²t (A²s) | Maximum 1-sec Fault Current (A) |
|---|---|---|
| 25 | 12,782,500 | 3,575 |
| 50 | 51,130,000 | 7,150 |
| 95 | 184,508,750 | 13,585 |
| 120 | 294,494,400 | 17,160 |
| 150 | 460,147,500 | 21,450 |
Mechanical Safety Thresholds
Minimum Bending Radius Compliance
- Immediate: Conductor strand breakage, armour wire distortion, sheath cracking
- Progressive: Water ingress, insulation failure, increased resistance hot spots
- Catastrophic: Phase-to-armour faults, cable fires, electrical explosions
The minimum bending radii (243mm to 786mm depending on size) must be respected during:
- Drum winding and storage
- Installation pulling operations
- Route planning around obstructions
- Termination box entry points
- Operational flexing during equipment movement
Armour Integrity Requirements
The galvanized steel pliable armour must maintain:
- Continuous electrical bonding for earth fault protection
- Mechanical integrity for crush and impact protection
- Corrosion resistance through zinc coating preservation
- Proper termination bonding at both cable ends
Environmental Safety Precautions
Explosive Atmosphere Compliance
Type 20 cables for use in potentially explosive atmospheres must comply with:
- Zone classification requirements (Zone 1, Zone 2 for gas; Zone 21, Zone 22 for dust)
- Temperature class limitations (T1-T6 classifications)
- Equipment protection concepts (Ex d, Ex e, Ex ia/ib)
- Cable gland and termination requirements for hazardous areas
Maximum surface temperature of cable in service must not exceed ignition temperature of surrounding atmosphere:
• T1: 450°C (hydrogen)
• T2: 300°C (ethylene)
• T3: 200°C (gasoline)
• T4: 135°C (ethyl ether)
• T5: 100°C (carbon disulfide)
• T6: 85°C
Type 20 cables with 90°C maximum conductor temperature typically satisfy T4 classification with appropriate derating.
Installation Temperature Restrictions
- Below 5°C: EPR and chloroprene become brittle, risking cracking during handling
- Above 60°C: Materials become too soft, causing permanent deformation under installation tension
Installation Best Practices and Guidelines
Pre-Installation Verification
☐ Verify cable drum for transport damage
☐ Check outer sheath for cuts, abrasions, or deformation
☐ Confirm armour continuity with low-resistance ohmmeter
☐ Measure insulation resistance (minimum 100 MΩ @ 1000V DC)
☐ Verify ambient temperature within 5°C-60°C range
☐ Confirm cable specification matches design requirements
☐ Review route for bending radius compliance
☐ Ensure proper equipment for cable weight handling
Cable Handling and Pulling
Drum Handling
- Cable drums must be stored and transported with axis horizontal
- Never roll drum in direction that would loosen outer wraps
- Use appropriate lifting equipment for drum weights (750 kg for small drums to 5,000+ kg for large cables)
- Provide adequate braking during payout to maintain controlled tension
Pulling Force Limitations
Maximum pulling force calculations must consider conductor strength and pulling method:
Where:
- k = safety factor (typically 0.5 for pulling)
- n = number of conductors (3 for Type 20)
- S = conductor cross-section (mm²)
- σ = conductor tensile strength (approximately 200 N/mm² for copper)
• 35mm² cable: F = 0.5 × 3 × 35 × 200 = 10,500 N
• 70mm² cable: F = 0.5 × 3 × 70 × 200 = 21,000 N
• 120mm² cable: F = 0.5 × 3 × 120 × 200 = 36,000 N
Termination and Bonding Procedures
Armour Bonding Requirements
The galvanized steel armour must be properly terminated to provide earth fault current path:
- Strip outer chloroprene sheath (150-250mm depending on gland size)
- Clean armour wires of bedding compound residue
- Install appropriate cable gland with armour retention cone
- Ensure metallic contact between armour and gland body
- Bond gland to earth bar with minimum 10mm² copper conductor
- Verify armour resistance is within specified limits
Conductor Termination
- Use compression or mechanical lugs rated for tinned copper
- Strip EPR insulation without damaging conductor strands
- Apply anti-oxidant compound to conductor surface (prevents surface oxidation)
- Torque connections to manufacturer specifications
- Apply heat-shrink boots for moisture sealing
- Maintain phase identification throughout termination
Post-Installation Testing
1. Visual Inspection: Verify route compliance, gland tightness, identification
2. Continuity Test: Phase conductors and armour bond verification
3. Insulation Resistance: Phase-to-phase and phase-to-earth at 1000V DC
• Minimum acceptable: 1 MΩ
• Typical new cable: 100-1000 MΩ
4. Earth Loop Impedance: Verify protective device operation capability
5. Phase Rotation Test: Confirm correct phase sequence for motor loads
6. High-Voltage Test (if required): 80% of factory test = 2.4kV for 1 minute
Common Problems and Frequently Asked Questions
Q1: What is the difference between Type 20 and Type 21 BS 6708 cables?
Answer: Both Type 20 and Type 21 are galvanized steel pliable wire armoured cables with unscreened cores rated at 640/1100V. The primary difference lies in the number of cores:
- Type 20: 3 power cores (three-phase supply without separate earth core)
- Type 21: 4 cores (three-phase supply plus dedicated fourth core, typically earth)
According to Demka Electrical Suppliers, both types feature maximum operating temperature of 90°C and maximum short-circuit temperature of 200°C (max. 5 sec), with three or four unscreened cores laid up around an elastomeric cradle without contacting each other. Type 21 is preferred when a dedicated earth conductor is required by regulations or design specifications.
Q2: Why does Type 20 use armour as the earth conductor instead of a dedicated core?
Answer: The armour-as-earth approach offers several advantages:
- Large cross-sectional area: Steel armour provides substantial fault current capacity
- 360° protection: Armour surrounds all cores, providing comprehensive mechanical shield
- Weight optimization: No additional copper for earth conductor reduces cable mass
- Cost efficiency: Steel armour serves dual purpose (mechanical and electrical)
However, armour resistance (0.41-4.2 Ω/km) is higher than equivalent copper conductors. For long runs or high fault current requirements, verify that armour resistance allows adequate fault current for protective device operation. Some installations may require supplementary earth conductors.
Q3: Can Type 20 cables be used for continuous trailing (reeling) applications?
Answer: Type 20 cables are not optimized for continuous reeling applications. The galvanized steel pliable armour, while providing excellent mechanical protection, has limitations for repeated flexing:
- Armour wires may fatigue after extensive flexing cycles
- Weight (990-12,500 kg/km) increases reeling equipment stress
- Armour adds stiffness compared to unarmoured cables
- Bending radius requirements (243-786mm) limit drum sizing
For continuous reeling applications, consider BS 6708 Type 7 (screened, non-armoured) or VDE 0250-812 NSSHCGEÖU cables specifically designed for repeated flexing. Type 20 is suitable for semi-permanent installations where cables are relocated infrequently.
Q4: What maintenance schedule is recommended for Type 20 installations?
Answer: Recommended maintenance intervals based on operating environment severity:
| Inspection Type | Normal Environment | Severe Environment |
|---|---|---|
| Visual inspection | Monthly | Weekly |
| Termination temperature check | Quarterly | Monthly |
| Insulation resistance test | Annually | Quarterly |
| Armour continuity verification | Annually | Semi-annually |
| Complete electrical testing | Every 3 years | Annually |
Q5: How do I calculate voltage drop for extended cable runs?
Answer: Use the three-phase voltage drop values from the electrical specifications table:
Example: 95mm² cable, 200m run, 180A load
ΔV = 0.47 × 180 × 200 ÷ 1000 = 16.92V
Percentage = (16.92 ÷ 1100) × 100 = 1.54%
Most mining regulations require voltage drop <5% for motor circuits. This example is well within limits.
Q6: What causes premature armour corrosion and how can it be prevented?
Answer: Armour corrosion causes include:
- Moisture ingress: Water entering through damaged sheath or poor terminations
- Chemical attack: Acidic mine water or processing chemicals
- Galvanic corrosion: Contact with dissimilar metals (copper terminations)
- Zinc coating damage: Mechanical abrasion removing protective layer
Prevention measures:
- Use IP68-rated cable glands for water ingress protection
- Apply corrosion-inhibiting compounds at terminations
- Install cables above expected water levels where possible
- Perform regular visual inspections for sheath damage
- Replace cables showing signs of armour corrosion before failure
Q7: Can Type 20 cables be spliced or repaired in the field?
Answer: Field splicing of Type 20 cables is strongly discouraged due to:
- Difficulty achieving equivalent armour protection at splice
- Risk of moisture ingress at joint location
- Reduced mechanical strength at splice point
- Regulatory restrictions in hazardous areas
- Warranty and liability implications
If splicing is absolutely necessary (due to cable damage), use only approved armoured cable joint kits specifically designed for mining applications, and ensure compliance with local mining electrical regulations. Many mining operations mandate complete cable replacement rather than field repair.
Contact Anhui Feichun Special Cable Co., Ltd.
For technical inquiries, product specifications, quotations, and custom cable requirements for BS 6708 Type 20 mining cables and other specialized mining cable solutions, please contact our expert engineering team:
[email protected]
[email protected]
+86 138 5512 3218
Anhui Feichun Special Cable Co., Ltd. (安徽飞纯特种电缆有限公司) specializes in manufacturing high-quality mining cables, armoured trailing cables, and specialty cables for demanding industrial applications. Our products comply with international standards including BS 6708, AS/NZS 2802, VDE 0250, and SANS 1520, serving mining operations worldwide.
References and External Technical Resources
- BS 6708:1998 – Flexible cables for use at mines and quarries – British Standards Institution
- IEC 60228: Conductors of insulated cables – International Electrotechnical Commission
- DIN VDE 0250-812: Rubber insulated flexible cable NSSHÖU – DIN Media
- AmplexMining.com.au – Comprehensive Cable Guide for the Mining Industry
- ReelingCable.com – Professional Mine Reeling Cable Technical Specifications
- Cleveland Cable Company – BS 6708 Mining Cable product specifications
- Üntel Mining Cables – Type 20/21 technical data sheets
- Tratos Group – Pliable Wire Armour cable construction practices
- Eland Cables – EPR insulation benefits technical documentation