ÖPVC-JZ/OZ-YCY 0.6/1 kV black: screened 1 kV cable with a UV-proofed sheath

An engineering guide to a multicore control cable built for EMC: black PVC cores with white numerals, 1 kV insulation walls, a PVC inner sheath, a tinned copper braid of approx. 85 % coverage and a UV-proofed black RAL 9005 PVC sheath, for interference-free transmission indoors and outdoors.

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
ÖPVC-JZ/OZ-YCY 0.6/1 kV black screened cable | FeiChun Cable
FEICHUN CABLE · 0.6/1 kV SCREENED CABLE FOR INDOOR AND OUTDOOR USE

ÖPVC-JZ/OZ-YCY 0.6/1 kV black: screened 1 kV cable with a UV-proofed sheath

An engineering guide to a multicore control cable built for EMC: black PVC cores with white numerals, 1 kV insulation walls, a PVC inner sheath, a tinned copper braid of approx. 85 % coverage and a UV-proofed black RAL 9005 PVC sheath, for interference-free transmission indoors and outdoors.

Similar to EN 50525-2-51IEC 60228 class 5IEC 60332-10.6/1 kV+160 °C short-circuitUV · black RAL 9005Test voltage 4 kVCu braid ≈85 %2–25 coresRoHS · CE
Document FC-ART-YCY1K-2026-9234Updated: 20 September 2026FeiChun Cable / 飞纯电缆
Engineer’s summary: this is the 1 kV, outdoor-capable version of JZ/OZ-YCY: 1 kV insulation walls, a 160 °C short-circuit limit and a UV-proofed black sheath, with the same inner sheath and 85 % copper braid. It can feed motors on 400/690 V drives and run outdoors, but not underground, in drag chains or under tension.

1. Reading the designation

JZ = with GNYE and numbered cores (‘G’); OZ = without GNYE (‘x’). Y-C-Y = PVC inner sheath, copper braid, PVC outer sheath. The whole range is rated 0.6/1 kV, tested at 4 kV, and sheathed in UV-proofed black PVC.

63

Standard constructions, 2 × 0.5 to 4 G 120 mm².

0.6/1 kV

Rated voltage, whole range.

≈85 %

Braid optical coverage.

4 kV

Test voltage.

2. Construction

In a single-sheathed CY cable, the braid sits directly on the core insulation, so every impact and tight bend is transferred through the braid wires into the cores. The PVC inner sheath of YCY cushions the cores, keeps the braid round so its coverage stays uniform, and adds a second barrier against moisture and chemicals.

Cross-section ÖPVC-JZ-YCY 0.6/1 kV 7 G · inner sheath, Cu braid, black UV sheathEngineering-drawing style · functional, not to scale · final dimensions per approved order drawingGNYE123456Ø d = 8.1 … 58.1 mm (see tables)1Bare Cu strand, IEC 60228 class 52PVC core insulation, 1 kV wall3White numerals (DIN VDE 0293)4GNYE protective conductor (JZ)5PVC inner sheath6Tinned Cu braid, approx. 85 %7Black PVC sheath RAL 9005, UV-proofedDocumentRevisionProjectionFC-ART-YCY1K-2026-9234A · 2026-091st angle
Figure 1: Construction of the 7 G version; callouts match the Pos. column of the materials table.
Materials table (Pos. = callout numbers in Figure 1)
Pos.ElementMaterial / formEngineering function
1ConductorBare Cu, fine-wire, IEC 60228 cl. 5Flexibility for installation and free movement
2Core insulationPVC, black, 1 kV wall thickness+70 °C continuous, +160 °C short-circuit
3Core markingWhite numerals per DIN VDE 0293Clear identification of many control circuits
4Protective conductorGNYE core in JZ (‘G’) versionsOZ (‘x’) versions have none
5Inner sheathPVCCushions the cores, keeps the braid round, second moisture barrier
6Overall screenTinned Cu braid, approx. 85 % optical coverageEMC screening; tinning resists corrosion and eases termination
7Outer sheathPVC, black RAL 9005, UV-proofedOutdoor use; IEC 60332-1

3. Technical data

Technical data (complete)
ParameterValueEngineering note
Conductor materialBare copper strand
Conductor classIEC 60228 class 5
Core insulationPVC1 kV insulation wall thickness
Core identificationAcc. to DIN VDE 0293: black cores with white numerals; G: with GNYE
StrandingCores stranded in layers
Inner sheathPVCAdditional mechanical protection
Overall screenTinned copper braid, optical coverage approx. 85 %EMC-compliant; recommended for EMC applications
Outer sheathPVCUV-proofed
Sheath colourBlack, RAL 9005
Rated voltage U0/U0.6/1 kVWhole range, 0.5–120 mm²
Test voltage4 kV
Conductor resistanceAcc. to IEC 60228 cl. 5
Insulation resistanceMin. 20 MΩ × km
Current carrying capacityAcc. to DIN VDE (technical guideline)
Min. bending radius fixed6 × dLarger than unscreened JZ/OZ (4 × d) because of the braid
Min. bending radius moved15 × d
Operating temp. fixed−40 °C / +80 °C
Operating temp. moved−15 °C / +70 °C
Conductor temperature+70 °C operation; +160 °C short-circuit
Burning behaviourSelf-extinguishing and flame-retardant acc. to IEC 60332-1Single-cable test
Chemical resistanceLargely resistant to acids, bases and specified oils
StandardSimilar to EN 50525-2-51, with insulation wall thickness for 1 kV
ComplianceRoHS; 2014/35/EU Low Voltage Directive (CE); LABS-/silicone-free during production

4. EMC: the braid only works if it is terminated

Recommended practice 1. Bond the braid 360° with EMC cable glands; avoid pigtails — a few centimetres of pigtail lose most of the high-frequency screening. 2. Keep the braid continuous up to the gland; do not open it further than necessary. 3. Segregate screened control cables from unscreened power cables on trays, or use a metal divider. 4. Bond both ends for drive and switching noise; for ground-loop-sensitive analogue signals, follow the equipment manufacturer.

5. Full dimension and weight tables

All 63 constructions are listed, grouped by cross-section. Bending radii are calculated from the nominal outer diameter (6 × d fixed, 15 × d moved).

Cross-section 0.5 mm² · 0.6/1 kV · screened · black UV sheath · 8 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 0.5OZ (without GNYE)10030168.138.0117.049122
3 G 0.5JZ (with GNYE)10034768.445.0135.050126
4 G 0.5JZ (with GNYE)10034779.254.0150.055138
5 G 0.5JZ (with GNYE)10034789.962.0173.059148
7 G 0.5JZ (with GNYE)100347911.976.0198.071178
12 G 0.5JZ (with GNYE)100348014.4131.0313.086216
18 G 0.5JZ (with GNYE)100348117.0175.0408.0102255
25 G 0.5JZ (with GNYE)100348220.2223.0638.0121303
Cross-section 0.75 mm² · 0.6/1 kV · screened · black UV sheath · 8 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 0.75OZ (without GNYE)10034838.546.0135.051128
3 G 0.75JZ (with GNYE)10034848.956.0149.053134
4 G 0.75JZ (with GNYE)10030039.767.0169.058146
5 G 0.75JZ (with GNYE)100300811.078.0197.066165
7 G 0.75JZ (with GNYE)100348512.897.0315.077192
12 G 0.75JZ (with GNYE)100348615.6168.0410.094234
18 G 0.75JZ (with GNYE)100348717.7229.0560.0106266
25 G 0.75JZ (with GNYE)100196421.7296.0762.0130326
Cross-section 1 mm² · 0.6/1 kV · screened · black UV sheath · 8 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 1OZ (without GNYE)10018789.252.0150.055138
3 G 1JZ (with GNYE)10031999.766.0163.058146
4 G 1JZ (with GNYE)100322810.679.0198.064159
5 G 1JZ (with GNYE)100322112.493.0239.074186
7 G 1JZ (with GNYE)100319813.7117.0335.082206
12 G 1JZ (with GNYE)100306416.4204.0522.098246
18 G 1JZ (with GNYE)100349419.4280.0628.0116291
25 G 1JZ (with GNYE)100322222.6369.0855.0136339
Cross-section 1.5 mm² · 0.6/1 kV · screened · black UV sheath · 8 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 1.5OZ (without GNYE)100324310.169.0181.061152
3 G 1.5JZ (with GNYE)100319011.187.0205.067166
4 G 1.5JZ (with GNYE)100324412.6102.0240.076189
5 G 1.5JZ (with GNYE)100283413.5125.0286.081202
7 G 1.5JZ (with GNYE)100312815.3180.0383.092230
12 G 1.5JZ (with GNYE)100186819.2281.0690.0115288
18 G 1.5JZ (with GNYE)100301122.2391.0806.0133333
25 G 1.5JZ (with GNYE)100349925.1518.01,180.0151376
Cross-section 2.5 mm² · 0.6/1 kV · screened · black UV sheath · 8 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 2.5OZ (without GNYE)100350011.3112.0191.068170
3 G 2.5JZ (with GNYE)100068612.7123.0298.076190
4 G 2.5JZ (with GNYE)100300914.2168.0345.085213
5 G 2.5JZ (with GNYE)100301215.0204.0457.090225
7 G 2.5JZ (with GNYE)100350117.5265.0561.0105262
12 G 2.5JZ (with GNYE)100350221.7421.0857.0130326
18 G 2.5JZ (with GNYE)100350325.5598.01,053.0153382
25 G 2.5JZ (with GNYE)100350429.4848.01,373.0176441
Cross-section 4 mm² · 0.6/1 kV · screened · black UV sheath · 5 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 4OZ (without GNYE)100350514.1120.0247.085212
3 G 4JZ (with GNYE)100078915.1191.0391.091226
4 G 4JZ (with GNYE)100165016.0238.0527.096240
5 G 4JZ (with GNYE)100350717.3302.0661.0104260
7 G 4JZ (with GNYE)100350819.0396.0828.0114285
Cross-section 6 mm² · 0.6/1 kV · screened · black UV sheath · 3 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 6JZ (with GNYE)100301817.7318.0715.0106266
5 G 6JZ (with GNYE)100319519.0419.0832.0114285
7 G 6JZ (with GNYE)100350922.1559.01,205.0133332
Cross-section 10 mm² · 0.6/1 kV · screened · black UV sheath · 2 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 10JZ (with GNYE)100301921.7574.0864.0130326
5 G 10JZ (with GNYE)100351023.8714.01,020.0143357
Cross-section 16 mm² · 0.6/1 kV · screened · black UV sheath · 2 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 16JZ (with GNYE)100301025.2809.01,184.0151378
5 G 16JZ (with GNYE)100350627.61,053.01,402.0166414
Cross-section 25 mm² · 0.6/1 kV · screened · black UV sheath · 2 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 25JZ (with GNYE)100317329.81,165.01,792.0179447
5 G 25JZ (with GNYE)100351232.71,446.02,209.0196491
Cross-section 35 mm² · 0.6/1 kV · screened · black UV sheath · 2 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 35JZ (with GNYE)100310432.71,683.02,495.0196491
5 G 35JZ (with GNYE)100351438.71,975.02,736.0232580
Cross-section 50 mm² · 0.6/1 kV · screened · black UV sheath · 2 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 50JZ (with GNYE)100302039.62,368.04,094.0238594
5 G 50JZ (with GNYE)100097344.92,880.05,118.0269674
Cross-section 70 mm² · 0.6/1 kV · screened · black UV sheath · 2 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 70JZ (with GNYE)100351546.03,261.05,467.0276690
5 G 70JZ (with GNYE)100097450.44,032.06,834.0302756
Cross-section 95 mm² · 0.6/1 kV · screened · black UV sheath · 2 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 95JZ (with GNYE)100351651.04,055.05,849.0306765
5 G 95JZ (with GNYE)100096456.55,264.07,720.0339848
Cross-section 120 mm² · 0.6/1 kV · screened · black UV sheath · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 120JZ (with GNYE)100351758.15,225.07,509.0349872

6. Application envelope

Power, control and connecting cable in electrical facilities, for interference-free data and signal transmission, in fixed laying and flexible applications with free movement, without tensile stress and without forced guidance. Suitable for dry, humid and wet rooms. Outdoor use permitted (UV-proofed sheath); not for burial.

Application envelope of ÖPVC-JZ/OZ ✔ Drive to motor (VSD) 360° braid bonding at both ends ✔ Signals near power circuits Free movement ≥ 15 × d, no tension ✘ Not designed for • Drag chains / forced guidance• Tensile load, reels, festoons• Direct burial• Direct burial• Pigtail braid terminations Use a PUR/TPE screened chain cablefor drag chains. Suitable for dry, humid and wet rooms. Suitable for dry, humid and wet rooms and outdoors (UV); the braid works only if terminated 360°.
Figure 2: Permitted duties and exclusions.

7. Comparison

JZ/OZ-YCY compared with related cables
TypeScreenSheathBending (fixed)CoresTypical use
ÖPVC-JZ/OZNoneSingle PVC, grey4 × d fixedNumbered coresGeneral control wiring
ÖPVC-JZ/OZ-YCY (300/500 V)Tinned Cu braid ≈85 %PVC inner + transparent outer6 × d fixedNumbered cores; indoorMulticore control with EMC needs
ÖPVC-JZ/OZ-YCY 0.6/1 kV blackTinned Cu braid ≈85 %PVC inner + black UV outer6 × d fixedNumbered cores; 0.6/1 kV; outdoorVSD motor feeds, outdoor screened runs
ÖPVC-JB/OB-YCYTinned Cu braid ≈85 %PVC inner + transparent outer6 × d fixedColoured cores (≤5), 0.6/1 kV from 25 mm²Power and drive cables
Single-sheath CYTinned Cu braidBraid under outer sheath onlyThinnerNumbered or colouredLight screened control
PUR chain cable, screenedHigh-coverage braidPUR/TPEChain-ratedVariousDrag chains, robots

8. Design calculations

Current rating: DIN VDE base value × f(ambient) × f(grouping) × f(loaded cores) Short-circuit (PVC 70 → 160 °C, Cu): I_k ≈ 119 × S / √t e.g. 4 G 120 (PVC 70 → 160 °C, k ≈ 119), t = 0.5 s → ≈ 20.2 kA Voltage drop: ΔU = √3 × I × L × (R cosφ + X sinφ) Bending: fixed R ≥ 6 × d · moved R ≥ 15 × d e.g. 25 G 1.5 (d = 25.1 mm): 151 mm / 377 mm Gland sizing: select EMC gland clamping range around the nominal outer Ø in the tables

9. Certification and traceability

This cable is RoHS-conform, CE-conform to the 2014/35/EU Low Voltage Directive and LABS-/silicone-free during production, with flame behaviour to IEC 60332-1. FeiChun Cable holds a complete export certification portfolio — including CE, UKCA, VDE, EAC, ATEX and IECEx — and every certificate supplied is checked against the exact type, voltage, factory and standard of the order.

Routine tests

Conductor resistance, 4 kV voltage test, insulation resistance, braid continuity, core numbering, dimensions and marking.

Type tests

IEC 60332-1 flame, sheath ageing, cold behaviour, oil resistance on request.

Delivery documents

Approved datasheet, test report per drum, batch number and length marking.

10. FAQ

Which YCY to choose?

Transparent 300/500 V JZ/OZ-YCY for indoor control; this black 0.6/1 kV version for motor feeds on 400/690 V drives and outdoor runs; JB/OB-YCY when coloured cores are preferred.

Why a black sheath?

Carbon-black RAL 9005 PVC is UV-proofed, so the cable can run outdoors without extra UV protection.

Is 85 % coverage enough?

For typical industrial EMC, yes, if the braid is bonded 360° at both ends with EMC glands. Termination quality matters more than coverage.

Earth the braid at one or both ends?

Both ends for drives and high-frequency noise; for sensitive analogue signals with ground-loop problems, follow the equipment manufacturer’s instructions.

Can it go in a drag chain?

No: free movement only, without tensile stress or forced guidance.

Why 6 × d instead of 4 × d?

The braid and inner sheath add stiffness; a tighter radius would deform the braid and open gaps in its coverage.

FeiChun Cable / 飞纯电缆
Technical and project enquiries: [email protected]
Manufacturing in China, export support
+86 13855123218
FEICHUN CABLE

Screened 1 kV cable with a UV-proofed sheath for indoor and outdoor runs

For control panels, drives, machinery and industrial installations.

[email protected]

+86 13855123218

Document FC-ART-YCY1K-2026-9234. Final values are governed by the approved datasheet, order drawing, batch test reports and certificate scope.

Previous Article

ÖPVC-JZ/OZ 0.6/1 kV black: flexible 1 kV PVC cable with numbered cores for indoor and outdoor use

Next Article

2YSL(St)CY-J 0.6/1 kV EMV: low-capacitance, double-screened cable for frequency converters

Write a Comment

Leave a Comment

您的邮箱地址不会被公开。 必填项已用 * 标注