An engineering guide to the YSY construction: PVC inner sheath, oxidation-protected galvanised steel-wire braid and transparent PVC outer sheath — high resistance to transverse crushing and impact, plus a magnetically effective screen.

ÖPVC-JZ/OZ-YSY 300/500 V and ÖPVC-JB/OB-YSY 0.6/1 kV: triple-protected PVC cable
An engineering guide to the YSY construction: PVC inner sheath, oxidation-protected galvanised steel-wire braid and transparent PVC outer sheath — high resistance to transverse crushing and impact, plus a magnetically effective screen.
1. Reading the designation
Y-S-Y = PVC inner sheath, steel-wire braid (S = Stahl), PVC outer sheath. JZ/OZ = numbered black cores, 300/500 V, up to 16 mm²; JB/OB = coloured cores, 0.6/1 kV with 1 kV insulation walls, from 25 mm². J = with GNYE (‘G’), O = without (‘x’).
Standard constructions, 2 × 0.5 to 4 G 95 mm².
Protection layers: inner sheath, steel braid, outer sheath.
Test voltage.
JB/OB from 25 mm².
2. Construction
The inner sheath is essential here: galvanised steel wires are hard and, without a cushion, would press into the core insulation under load. The transparent outer sheath lets the installer inspect the braid for corrosion or damage.
| Pos. | Element | Material / form | Engineering function |
|---|---|---|---|
| 1 | Conductor | Bare Cu, fine-wire, IEC 60228 cl. 5 | Flexibility for installation and free movement |
| 2 | Core insulation | PVC; 1 kV wall thickness on JB/OB 0.6/1 kV | +70 °C continuous, +150 °C short-circuit |
| 3 | Core identification | JZ/OZ: black with white numerals; JB/OB: coloured (≤5 cores DIN VDE 0293-308) | Numbered for control, coloured for power |
| 4 | Protective conductor | GNYE core in ‘G’ versions | OZ/OB versions have none |
| 5 | Inner sheath | PVC | Protection layer 1: cushions the cores under the steel braid |
| 6 | Braid | Galvanised steel wire, oxidation-protected | Protection layer 2: transverse crush and impact; magnetically effective screening |
| 7 | Outer sheath | Transparent PVC | Protection layer 3; braid visible for inspection |
3. Technical data
| Parameter | Value | Engineering note |
|---|---|---|
| Conductor material | Bare copper strand | |
| Conductor class | IEC 60228 class 5 | |
| Core insulation | PVC | 1 kV wall thickness on the 0.6/1 kV type |
| Core identification | JZ/OZ: DIN VDE 0293 black cores with white numerals; JB/OB: coloured — up to 5 cores DIN VDE 0293-308, from 6 cores colour code per technical guideline; G: with GNYE | |
| Stranding | Cores stranded in layers | |
| Inner sheath | PVC | |
| Braid | Galvanised steel wire braid | Oxidation-protected; magnetic screen and mechanical armour |
| Outer sheath | PVC | |
| Sheath colour | Transparent | |
| Rated voltage U0/U | JZ/OZ: 300/500 V · JB/OB: 0.6/1 kV (from 25 mm²) | |
| Test voltage | 4 kV | |
| Conductor resistance | Acc. to IEC 60228 cl. 5 | |
| Insulation resistance | Min. 20 MΩ × km | |
| Current carrying capacity | Acc. to DIN VDE (technical guideline) | |
| Min. bending radius fixed | 6 × d | |
| Min. bending radius moved | 15 × d | |
| Operating temp. fixed | −30 °C / +80 °C | Note −30 °C, not −40 °C as on YCY types |
| Operating temp. moved | −15 °C / +70 °C | |
| Conductor temperature | +70 °C operation; +150 °C short-circuit | |
| Burning behaviour | Self-extinguishing and flame-retardant acc. to IEC 60332-1 | |
| Chemical resistance | Largely resistant to acids, bases and specified oils | |
| Storage | Not outdoors or in wet rooms | Protects the galvanised braid until installation |
| Standard | Similar to EN 50525-2-51; 0.6/1 kV type with 1 kV insulation thickness | |
| Compliance | RoHS; 2014/35/EU Low Voltage Directive (CE); LABS-/silicone-free during production |
4. Steel braid versus copper braid
| Property | Galvanised steel braid (YSY) | Tinned copper braid (YCY) |
|---|---|---|
| Magnetic permeability | High (ferromagnetic) | ≈1 (non-magnetic) |
| Low-frequency magnetic fields (50 Hz, transformers, busbars) | Effective attenuation | Limited |
| High-frequency electric interference (VSD switching) | Moderate — higher resistance | Very effective |
| Mechanical protection | High (hard wires) | Moderate |
| Suitability as PE | No | No (use GNYE core) |
| Corrosion | Galvanised; keep dry in storage | Tinned |
5. Full dimension and weight tables
All 61 constructions are listed, grouped by cross-section: JZ/OZ-YSY 300/500 V up to 16 mm², JB/OB-YSY 0.6/1 kV from 25 mm². Bending radii are calculated from the nominal outer diameter (6 × d fixed, 15 × d moved). The steel braid explains why weight is well above that of the copper-braided types.
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 2 x 0.5 | OZ (without GNYE) | 1001108 | 7.2 | 9.6 | 77.0 | 43 | 108 |
| 3 G 0.5 | JZ (with GNYE) | 1000801 | 7.7 | 14.4 | 86.0 | 46 | 116 |
| 4 G 0.5 | JZ (with GNYE) | 1002319 | 8.1 | 19.2 | 101.0 | 49 | 122 |
| 5 G 0.5 | JZ (with GNYE) | 1001717 | 8.6 | 24.0 | 116.0 | 52 | 129 |
| 7 G 0.5 | JZ (with GNYE) | 1000831 | 9.7 | 33.6 | 134.0 | 58 | 146 |
| 12 G 0.5 | JZ (with GNYE) | 1000770 | 11.6 | 58.0 | 204.0 | 70 | 174 |
| 21 G 0.5 | JZ (with GNYE) | 1000782 | 14.9 | 101.0 | 332.0 | 89 | 224 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 2 x 0.75 | OZ (without GNYE) | 1001109 | 7.8 | 14.4 | 88.0 | 47 | 117 |
| 3 G 0.75 | JZ (with GNYE) | 1000802 | 8.1 | 21.6 | 102.0 | 49 | 122 |
| 4 G 0.75 | JZ (with GNYE) | 1000809 | 8.6 | 28.8 | 135.0 | 52 | 129 |
| 5 G 0.75 | JZ (with GNYE) | 1000822 | 9.4 | 36.0 | 144.0 | 56 | 141 |
| 7 G 0.75 | JZ (with GNYE) | 1000832 | 10.3 | 50.4 | 168.0 | 62 | 154 |
| 12 G 0.75 | JZ (with GNYE) | 1000771 | 12.8 | 86.4 | 252.0 | 77 | 192 |
| 18 G 0.75 | JZ (with GNYE) | 1000778 | 14.8 | 130.0 | 330.0 | 89 | 222 |
| 21 G 0.75 | JZ (with GNYE) | 1003420 | 16.2 | 151.0 | 415.0 | 97 | 243 |
| 25 G 0.75 | JZ (with GNYE) | 1000786 | 17.0 | 180.0 | 435.0 | 102 | 255 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 2 x 1 | OZ (without GNYE) | 1001110 | 8.2 | 19.2 | 101.0 | 49 | 123 |
| 3 G 1 | JZ (with GNYE) | 1000803 | 8.5 | 28.8 | 112.0 | 51 | 128 |
| 4 G 1 | JZ (with GNYE) | 1000810 | 9.3 | 38.4 | 127.0 | 56 | 140 |
| 5 G 1 | JZ (with GNYE) | 1000823 | 9.8 | 48.0 | 153.0 | 59 | 147 |
| 7 G 1 | JZ (with GNYE) | 1000833 | 11.0 | 67.2 | 188.0 | 66 | 165 |
| 12 G 1 | JZ (with GNYE) | 1000772 | 13.6 | 115.0 | 285.0 | 82 | 204 |
| 18 G 1 | JZ (with GNYE) | 1000779 | 15.6 | 173.0 | 400.0 | 94 | 234 |
| 25 G 1 | JZ (with GNYE) | 1000787 | 18.1 | 240.0 | 520.0 | 109 | 272 |
| 34 G 1 | JZ (with GNYE) | 1000797 | 20.5 | 326.0 | 707.0 | 123 | 308 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 2 x 1.5 | OZ (without GNYE) | 1001111 | 8.9 | 28.8 | 117.0 | 53 | 134 |
| 3 G 1.5 | JZ (with GNYE) | 1000804 | 9.3 | 43.2 | 137.0 | 56 | 140 |
| 4 G 1.5 | JZ (with GNYE) | 1000811 | 9.9 | 58.0 | 167.0 | 59 | 148 |
| 5 G 1.5 | JZ (with GNYE) | 1000824 | 10.8 | 72.0 | 193.0 | 65 | 162 |
| 7 G 1.5 | JZ (with GNYE) | 1000834 | 11.9 | 101.0 | 228.0 | 71 | 178 |
| 8 G 1.5 | JZ (with GNYE) | 1000840 | 13.6 | 115.0 | 285.0 | 82 | 204 |
| 12 G 1.5 | JZ (with GNYE) | 1000773 | 15.1 | 173.0 | 378.0 | 91 | 226 |
| 18 G 1.5 | JZ (with GNYE) | 1000780 | 17.3 | 259.0 | 480.0 | 104 | 260 |
| 25 G 1.5 | JZ (with GNYE) | 1000788 | 20.3 | 360.0 | 685.0 | 122 | 304 |
| 34 G 1.5 | JZ (with GNYE) | 1000798 | 22.9 | 490.0 | 870.0 | 137 | 344 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 2 x 2.5 | OZ (without GNYE) | 1001112 | 10.4 | 48.0 | 157.0 | 62 | 156 |
| 3 G 2.5 | JZ (with GNYE) | 1000805 | 11.0 | 72.0 | 191.0 | 66 | 165 |
| 4 G 2.5 | JZ (with GNYE) | 1000814 | 11.9 | 96.0 | 224.0 | 71 | 178 |
| 5 G 2.5 | JZ (with GNYE) | 1000827 | 12.8 | 120.0 | 275.0 | 77 | 192 |
| 7 G 2.5 | JZ (with GNYE) | 1000837 | 14.3 | 168.0 | 329.0 | 86 | 214 |
| 12 G 2.5 | JZ (with GNYE) | 1000774 | 18.2 | 288.0 | 532.0 | 109 | 273 |
| 18 G 2.5 | JZ (with GNYE) | 1000781 | 21.1 | 432.0 | 790.0 | 127 | 316 |
| 25 G 2.5 | JZ (with GNYE) | 1000790 | 24.4 | 600.0 | 1,030.0 | 146 | 366 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 4 G 4 | JZ (with GNYE) | 1000817 | 13.9 | 154.0 | 318.0 | 83 | 208 |
| 5 G 4 | JZ (with GNYE) | 1000828 | 15.0 | 192.0 | 392.0 | 90 | 225 |
| 7 G 4 | JZ (with GNYE) | 1000838 | 16.4 | 269.0 | 486.0 | 98 | 246 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 4 G 6 | JZ (with GNYE) | 1000818 | 15.8 | 230.0 | 440.0 | 95 | 237 |
| 5 G 6 | JZ (with GNYE) | 1000829 | 17.2 | 288.0 | 545.0 | 103 | 258 |
| 7 G 6 | JZ (with GNYE) | 1000839 | 18.9 | 403.0 | 668.0 | 113 | 284 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 4 G 10 | JZ (with GNYE) | 1000812 | 19.4 | 384.0 | 699.0 | 116 | 291 |
| 5 G 10 | JZ (with GNYE) | 1000825 | 21.5 | 480.0 | 850.0 | 129 | 322 |
| 7 G 10 | JZ (with GNYE) | 1000835 | 23.4 | 672.0 | 1,189.0 | 140 | 351 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 4 G 16 | JZ (with GNYE) | 1000813 | 22.4 | 614.0 | 1,228.0 | 134 | 336 |
| 5 G 16 | JZ (with GNYE) | 1000826 | 24.6 | 768.0 | 1,322.0 | 148 | 369 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 4 G 25 | JB (with GNYE) | 1000435 | 28.9 | 960.0 | 2,020.0 | 173 | 434 |
| 5 G 25 | JB (with GNYE) | 1000444 | 31.8 | 1,200.0 | 2,465.0 | 191 | 477 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 4 G 35 | JB (with GNYE) | 1000437 | 32.2 | 1,344.0 | 2,570.0 | 193 | 483 |
| 5 G 35 | JB (with GNYE) | 1003416 | 36.0 | 1,680.0 | 3,185.0 | 216 | 540 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 4 G 50 | JB (with GNYE) | 1000438 | 38.2 | 1,920.0 | 3,515.0 | 229 | 573 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 4 G 70 | JB (with GNYE) | 1000439 | 43.8 | 2,688.0 | 4,810.0 | 263 | 657 |
| Dimension n × mm² | Version | Reference item no. | Outer Ø mm | Cu index kg/km | Weight kg/km | Min. bend radius fixed (6 × d) mm | Min. bend radius moved (15 × d) mm |
|---|---|---|---|---|---|---|---|
| 4 G 95 | JB (with GNYE) | 1000440 | 50.4 | 3,648.0 | 6,360.0 | 302 | 756 |
6. Application envelope
Power, control and connecting cable in electrical facilities, for fixed laying and flexible applications with free movement, without tensile stress and without forced guidance. Suitable for dry, humid and wet rooms. Outdoor use only with UV protection; not for burial. Do not store outdoors or in wet rooms.
7. Comparison
| Type | Braid / armour | Sheath | Mechanical protection | Screening strength | Typical use |
|---|---|---|---|---|---|
| ÖPVC-JZ/OZ | None | Single PVC | Low | None | General wiring |
| ÖPVC-JZ/OZ-YCY | Tinned Cu braid ≈85 % | PVC inner + outer | Medium | High-frequency EMC (electric/HF fields) | Drives, signals |
| ÖPVC-JZ/OZ-YSY / JB/OB-YSY | Galvanised steel-wire braid | PVC inner + transparent outer | High (triple protection) | Low-frequency magnetic fields | Rough routes, near transformers and busbars |
| SWA armoured (e.g. NYRY) | Steel wire armour | PVC | High, fixed only | Limited | Fixed power, some burial |
8. Design calculations
9. Certification and traceability
This cable is RoHS-conform, CE-conform to the 2014/35/EU Low Voltage Directive and LABS-/silicone-free during production, with flame behaviour to IEC 60332-1. FeiChun Cable holds a complete export certification portfolio — including CE, UKCA, VDE, EAC, ATEX and IECEx — and every certificate supplied is checked against the exact type, voltage, factory and standard of the order.
Routine tests
Conductor resistance, 4 kV voltage test, insulation resistance, braid continuity, dimensions and marking.
Type tests
IEC 60332-1 flame, sheath ageing, braid zinc coating check, oil resistance on request.
Delivery documents
Approved datasheet, test report per drum, batch number and length marking; drums supplied with sealed ends.
10. FAQ
Is YSY an EMC cable like YCY?
Different purpose. Copper braid (YCY) is effective against high-frequency electric interference; the steel braid of YSY is ferromagnetic and attenuates low-frequency magnetic fields, while also acting as mechanical armour. For drive EMC, YCY remains the reference.
What does ‘triple protection’ mean?
PVC inner sheath, galvanised steel-wire braid and PVC outer sheath: three layers against transverse crushing and impact.
Can the steel braid be used as the PE conductor?
No. Steel has a much higher resistance than copper. Use the GNYE core as PE and bond the braid to earth for safety.
Can it take tensile load?
No. The braid is armour against crushing, not a strain member; free movement only, without tension.
Why no outdoor storage?
Moisture ingress at cut ends can corrode the braid before installation; keep drums covered and ends sealed.
JZ/OZ or JB/OB?
JZ/OZ (300/500 V, numbered cores) up to 16 mm²; JB/OB (0.6/1 kV, coloured cores) from 25 mm².