ÖPVC-JZ/OZ-YCY: screened, double-sheathed control cable with numbered cores

An engineering guide to a multicore control cable built for EMC: black PVC cores with white numerals, a PVC inner sheath, a tinned copper braid of approx. 85 % coverage and a transparent PVC outer sheath, for interference-free data and signal transmission.

Similar to EN 50525-2-51IEC 60228 class 5IEC 60332-1300/500 VTest voltage 4 kVCu braid ≈85 %2–50 coresRoHS · CE
Document FC-ART-JZYCY-2026-0FFEUpdated: 20 September 2026FeiChun Cable / 飞纯电缆
Engineer’s summary: JZ/OZ-YCY combines the numbered-core convenience of JZ/OZ with the EMC braid and inner sheath of YCY. It is the natural choice for multicore control circuits routed near drives and contactors. It is rated for fixed laying and free movement only — not drag chains, not burial.

1. Reading the designation

JZ = with GNYE and numbered cores (‘G’); OZ = without GNYE (‘x’). Y-C-Y = PVC inner sheath, copper braid, PVC outer sheath. The whole range is rated 300/500 V and tested at 4 kV.

51

Standard constructions, 2 × 0.5 to 4 G 50 mm².

50

Maximum core count (1 mm²).

≈85 %

Braid optical coverage.

4 kV

Test voltage.

2. Construction

In a single-sheathed CY cable, the braid sits directly on the core insulation, so every impact and tight bend is transferred through the braid wires into the cores. The PVC inner sheath of YCY cushions the cores, keeps the braid round so its coverage stays uniform, and adds a second barrier against moisture and chemicals.

Cross-section ÖPVC-JZ-YCY 7 G · numbered cores, inner sheath, Cu braidEngineering-drawing style · functional, not to scale · final dimensions per approved order drawingGNYE123456Ø d = 7.0 … 37.2 mm (see tables)1Bare Cu strand, IEC 60228 class 52PVC core insulation, black3White numerals (DIN VDE 0293)4GNYE protective conductor (JZ)5PVC inner sheath6Tinned Cu braid, approx. 85 %7Transparent PVC outer sheathDocumentRevisionProjectionFC-ART-JZYCY-2026-0FFEA · 2026-091st angle
Figure 1: Construction of the 7 G version; callouts match the Pos. column of the materials table.
Materials table (Pos. = callout numbers in Figure 1)
Pos.ElementMaterial / formEngineering function
1ConductorBare Cu, fine-wire, IEC 60228 cl. 5Flexibility for installation and free movement
2Core insulationPVC, black+70 °C continuous, +150 °C short-circuit
3Core markingWhite numerals per DIN VDE 0293Clear identification of many control circuits
4Protective conductorGNYE core in JZ (‘G’) versionsOZ (‘x’) versions have none
5Inner sheathPVCCushions the cores, keeps the braid round, second moisture barrier
6Overall screenTinned Cu braid, approx. 85 % optical coverageEMC screening; tinning resists corrosion and eases termination
7Outer sheathTransparent PVCIEC 60332-1; braid visible for inspection

3. Technical data

Technical data (complete)
ParameterValueEngineering note
Conductor materialBare copper strand
Conductor classIEC 60228 class 5
Core insulationPVC
Core identificationAcc. to DIN VDE 0293: black cores with white numerals; G: with GNYE
StrandingCores stranded in layers
Inner sheathPVCAdditional mechanical protection
Overall screenTinned copper braid, optical coverage approx. 85 %EMC-compliant; recommended for EMC applications
Outer sheathPVC
Sheath colourTransparent
Rated voltage U0/U300/500 VWhole range, 0.5–50 mm²
Test voltage4 kV
Conductor resistanceAcc. to IEC 60228 cl. 5
Insulation resistanceMin. 20 MΩ × km
Current carrying capacityAcc. to DIN VDE (technical guideline)
Min. bending radius fixed6 × dLarger than unscreened JZ/OZ (4 × d) because of the braid
Min. bending radius moved15 × d
Operating temp. fixed−40 °C / +80 °C
Operating temp. moved−15 °C / +70 °C
Conductor temperature+70 °C operation; +150 °C short-circuit
Burning behaviourSelf-extinguishing and flame-retardant acc. to IEC 60332-1Single-cable test
Chemical resistanceLargely resistant to acids, bases and specified oils
StandardSimilar to EN 50525-2-51
ComplianceRoHS; 2014/35/EU Low Voltage Directive (CE); LABS-/silicone-free during production

4. EMC: the braid only works if it is terminated

Recommended practice 1. Bond the braid 360° with EMC cable glands; avoid pigtails — a few centimetres of pigtail lose most of the high-frequency screening. 2. Keep the braid continuous up to the gland; do not open it further than necessary. 3. Segregate screened control cables from unscreened power cables on trays, or use a metal divider. 4. Bond both ends for drive and switching noise; for ground-loop-sensitive analogue signals, follow the equipment manufacturer.

5. Full dimension and weight tables

All 51 constructions are listed, grouped by cross-section. Bending radii are calculated from the nominal outer diameter (6 × d fixed, 15 × d moved).

Cross-section 0.5 mm² · 300/500 V · screened · 8 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 0.5OZ (without GNYE)10010937.041.070.042105
3 G 0.5JZ (with GNYE)10006817.346.080.044110
4 G 0.5JZ (with GNYE)10006917.955.095.047118
5 G 0.5JZ (with GNYE)10007118.466.0111.050126
7 G 0.5JZ (with GNYE)10007209.181.0140.055136
12 G 0.5JZ (with GNYE)100065911.5139.0217.069172
18 G 0.5JZ (with GNYE)100066513.6156.0295.082204
25 G 0.5JZ (with GNYE)100067115.3250.0384.092230
Cross-section 0.75 mm² · 300/500 V · screened · 8 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 0.75OZ (without GNYE)10010927.546.083.045112
3 G 0.75JZ (with GNYE)10006827.958.094.047118
4 G 0.75JZ (with GNYE)10006928.464.0115.050126
5 G 0.75JZ (with GNYE)10007129.177.0136.055136
7 G 0.75JZ (with GNYE)10007229.7102.0167.058146
12 G 0.75JZ (with GNYE)100066012.7177.0271.076190
18 G 0.75JZ (with GNYE)100066614.6243.0365.088219
25 G 0.75JZ (with GNYE)100067217.3307.0480.0104260
Cross-section 1 mm² · 300/500 V · screened · 10 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 1OZ (without GNYE)10010967.956.098.047118
3 G 1JZ (with GNYE)10006838.265.0110.049123
4 G 1JZ (with GNYE)10006938.878.0130.053132
5 G 1JZ (with GNYE)10007139.689.0160.058144
7 G 1JZ (with GNYE)100072310.4113.0194.062156
12 G 1JZ (with GNYE)100066113.6188.0330.082204
18 G 1JZ (with GNYE)100066715.5286.0444.093232
25 G 1JZ (with GNYE)100067317.9389.0560.0107268
34 G 1JZ (with GNYE)100067820.3505.0738.0122304
50 G 1JZ (with GNYE)100070923.6688.01,030.0142354
Cross-section 1.5 mm² · 300/500 V · screened · 8 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 1.5OZ (without GNYE)10010958.765.0122.052130
3 G 1.5JZ (with GNYE)10006849.083.0145.054135
4 G 1.5JZ (with GNYE)10006949.7100.0168.058146
5 G 1.5JZ (with GNYE)100071410.6125.0205.064159
7 G 1.5JZ (with GNYE)100072411.4196.0266.068171
12 G 1.5JZ (with GNYE)100066215.2280.0425.091228
18 G 1.5JZ (with GNYE)100066817.5389.0565.0105262
25 G 1.5JZ (with GNYE)100067420.5535.0850.0123308
Cross-section 2.5 mm² · 300/500 V · screened · 6 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
3 G 2.5JZ (with GNYE)100068510.5146.0197.063158
4 G 2.5JZ (with GNYE)100069911.5167.0254.069172
5 G 2.5JZ (with GNYE)100071712.5200.0302.075188
7 G 2.5JZ (with GNYE)100072614.0288.0395.084210
12 G 2.5JZ (with GNYE)100066318.2477.0622.0109273
18 G 2.5JZ (with GNYE)100066922.4598.0958.0134336
Cross-section 4 mm² · 300/500 V · screened · 3 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 4JZ (with GNYE)100070213.7237.0394.082206
5 G 4JZ (with GNYE)100071815.4280.0445.092231
7 G 4JZ (with GNYE)100072716.2388.0610.097243
Cross-section 6 mm² · 300/500 V · screened · 2 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 6JZ (with GNYE)100070515.8318.0485.095237
5 G 6JZ (with GNYE)100071917.0441.0609.0102255
Cross-section 10 mm² · 300/500 V · screened · 2 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 10JZ (with GNYE)100069519.4558.0735.0116291
5 G 10JZ (with GNYE)100071521.8714.01,105.0131327
Cross-section 16 mm² · 300/500 V · screened · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 16JZ (with GNYE)100069722.6804.01,165.0136339
Cross-section 25 mm² · 300/500 V · screened · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 25JZ (with GNYE)100070028.91,310.01,720.0173434
Cross-section 35 mm² · 300/500 V · screened · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 35JZ (with GNYE)100070135.61,610.02,120.0214534
Cross-section 50 mm² · 300/500 V · screened · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 50JZ (with GNYE)100278337.22,342.03,200.0223558

6. Application envelope

Power, control and connecting cable in electrical facilities, for interference-free data and signal transmission, in fixed laying and flexible applications with free movement, without tensile stress and without forced guidance. Suitable for dry, humid and wet rooms. Outdoor use only with UV protection; not for burial.

Application envelope of ÖPVC-JZ/OZ ✔ Drive to motor (VSD) 360° braid bonding at both ends ✔ Signals near power circuits Free movement ≥ 15 × d, no tension ✘ Not designed for • Drag chains / forced guidance• Tensile load, reels, festoons• Direct burial• Outdoors without UV protection• Pigtail braid terminations Use a PUR/TPE screened chain cablefor drag chains. Suitable for dry, humid and wet rooms. Suitable for dry, humid and wet rooms; the braid works only if terminated 360°.
Figure 2: Permitted duties and exclusions.

7. Comparison

JZ/OZ-YCY compared with related cables
TypeScreenSheathBending (fixed)CoresTypical use
ÖPVC-JZ/OZNoneSingle PVC, grey4 × d fixedNumbered coresGeneral control wiring
ÖPVC-JZ/OZ-YCYTinned Cu braid ≈85 %PVC inner + transparent outer6 × d fixedNumbered coresMulticore control with EMC needs
ÖPVC-JB/OB-YCYTinned Cu braid ≈85 %PVC inner + transparent outer6 × d fixedColoured cores (≤5), 0.6/1 kV from 25 mm²Power and drive cables
Single-sheath CYTinned Cu braidBraid under outer sheath onlyThinnerNumbered or colouredLight screened control
PUR chain cable, screenedHigh-coverage braidPUR/TPEChain-ratedVariousDrag chains, robots

8. Design calculations

Current rating: DIN VDE base value × f(ambient) × f(grouping) × f(loaded cores) Short-circuit (PVC 70 → 150 °C, Cu): I_k ≈ 115 × S / √t e.g. 4 G 50, t = 0.5 s → ≈ 8.1 kA Voltage drop: ΔU = √3 × I × L × (R cosφ + X sinφ) Bending: fixed R ≥ 6 × d · moved R ≥ 15 × d e.g. 25 G 1.5 (d = 20.5 mm): 123 mm / 308 mm Gland sizing: select EMC gland clamping range around the nominal outer Ø in the tables

9. Certification and traceability

This cable is RoHS-conform, CE-conform to the 2014/35/EU Low Voltage Directive and LABS-/silicone-free during production, with flame behaviour to IEC 60332-1. FeiChun Cable holds a complete export certification portfolio — including CE, UKCA, VDE, EAC, ATEX and IECEx — and every certificate supplied is checked against the exact type, voltage, factory and standard of the order.

Routine tests

Conductor resistance, 4 kV voltage test, insulation resistance, braid continuity, core numbering, dimensions and marking.

Type tests

IEC 60332-1 flame, sheath ageing, cold behaviour, oil resistance on request.

Delivery documents

Approved datasheet, test report per drum, batch number and length marking.

10. FAQ

JZ/OZ-YCY or JB/OB-YCY?

JZ/OZ-YCY has black numbered cores and many-core designs up to 50 cores for control circuits. JB/OB-YCY has coloured cores and goes to 185 mm² at 0.6/1 kV for power and drive leads.

Why a transparent sheath?

The braid stays visible, so crushed braid or poor terminations can be spotted during inspection.

Is 85 % coverage enough?

For typical industrial EMC, yes, if the braid is bonded 360° at both ends with EMC glands. Termination quality matters more than coverage.

Earth the braid at one or both ends?

Both ends for drives and high-frequency noise; for sensitive analogue signals with ground-loop problems, follow the equipment manufacturer’s instructions.

Can it go in a drag chain?

No: free movement only, without tensile stress or forced guidance.

Why 6 × d instead of 4 × d?

The braid and inner sheath add stiffness; a tighter radius would deform the braid and open gaps in its coverage.

FeiChun Cable / 飞纯电缆
Technical and project enquiries: [email protected]
Manufacturing in China, export support
+86 13855123218
FEICHUN CABLE

Numbered cores, inner sheath and EMC braid in one control cable

For control panels, drives, machinery and industrial installations.

[email protected]

+86 13855123218

Document FC-ART-JZYCY-2026-0FFE. Final values are governed by the approved datasheet, order drawing, batch test reports and certificate scope.