What is DIN VDE 0472 Cable?

Complete Technical Guide to German Fire Performance Cable Testing Standard — Circuit Integrity, Flame Propagation & NHXH/NHXCH FE180 Cables

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
What is DIN VDE 0472 Cable? Fire Performance Testing Standard Guide | Feichun Cable

Anhui Feichun Special Cable Co., Ltd.

安徽飞纯特种电缆有限公司

What is DIN VDE 0472 Cable?

Complete Technical Guide to German Fire Performance Cable Testing Standard — Circuit Integrity, Flame Propagation & NHXH/NHXCH FE180 Cables

🇩🇪 DIN VDE 0472 🔥 Fire Performance ⏱️ FE60/90/120/180 🛡️ Circuit Integrity 📋 IEC 60331 🇬🇧 BS 6387

1. Introduction to DIN VDE 0472 Standard

Germany’s standards agency DIN VDE originally set the parameters for circuit integrity for cables, wires, and flexible cords in the event of a fire in standard DIN VDE 0472. While this standard has now been superseded by German standard DIN VDE 0482, it remains widely referred to across the cable industry for fire performance testing and continues to be an important reference for specifying fire-resistant cables.

DIN VDE 0472 is similar to the British Standard BS 6387 Cat C and the International Standard IEC 60331 (FE). It assesses the resistance of single insulated cables and bunches of cables against vertical flame propagation, providing a comprehensive framework for evaluating cable behavior under fire conditions.

⚠️ Standard Transition Notice

DIN VDE 0472 has been superseded by DIN VDE 0482. However, references to VDE 0472 remain common in fire performance cable specifications, particularly for insulation integrity testing (Part 814). Many cable manufacturers continue to reference VDE 0472-814 for FE (Flame Exposure) ratings.

DIN VDE 0472

Historical Standard

SUPERSEDED
→

DIN VDE 0482

Current Standard

CURRENT

Source: Eland Cables – DIN VDE 0472 Standard Cable

EspañolIntroducción al Estándar DIN VDE 0472

La agencia de normas alemana DIN VDE estableció originalmente los parámetros para la integridad del circuito de cables, alambres y cordones flexibles en caso de incendio en la norma DIN VDE 0472. Aunque esta norma ha sido reemplazada por la norma alemana DIN VDE 0482, sigue siendo ampliamente referenciada en toda la industria del cable para pruebas de rendimiento contra incendios. DIN VDE 0472 es similar a la norma británica BS 6387 Cat C y a la norma internacional IEC 60331 (FE), evaluando la resistencia de cables aislados individuales y grupos de cables contra la propagación vertical de llamas.

繁體中文DIN VDE 0472 標準簡介

德國標準機構DIN VDE最初在DIN VDE 0472標準中設定了電纜、電線和軟線在發生火災時電路完整性的參數。雖然該標準現已被德國標準DIN VDE 0482取代,但它在電纜行業中仍被廣泛引用於防火性能測試。DIN VDE 0472類似於英國標準BS 6387 Cat C和國際標準IEC 60331(FE),用於評估單根絕緣電纜和成束電纜對垂直火焰傳播的抵抗力。該標準為評估火災條件下的電纜行為提供了全面的框架,並包含電路完整性測試和阻燃性的多個子部分。

2. FE Classification — Flame Exposure Duration

DIN VDE 0472 standard cables are categorized according to the length of time during which they can maintain their circuit integrity in the event of extended flame exposure under mechanically unstressed connection. The duration of time is referenced in their FE (Flame Exposure) classification:

🔥 FE Classification System

FE60

60 min
1 Hour Fire Resistance
FE60

FE90

90 min
1.5 Hours Fire Resistance
FE90

FE120

120 min
2 Hours Fire Resistance
FE120

FE180

180 min
3 Hours Fire Resistance
FE180

The fire test with circuit integrity (FE rating) shows how many minutes a mechanically unstressed connection at a flame exposure of minimum 750°C keeps minimum insulation efficiency (circuit integrity) in a dry environment. Similar standards include IEC 60331 (FE) and BS 6387 Cat C.

Source: Fireproof Cables – DIN VDE 0472-814 Circuit Integrity

3. DIN VDE 0472 Standard Parts & International Equivalents

DIN VDE 0472 encompasses multiple test standards for fire performance, each addressing specific aspects of cable behavior under fire conditions. These parts have been updated to newer DIN EN standards while maintaining backward compatibility references.

Old German StandardNew German StandardScope of StandardInternational Equivalent
VDE 0472 Part 804BDIN EN 60332-1
VDE 0482-332-1
Flammability of a single cableIEC 60332-1
VDE 0472 Part 804CDIN EN 60332-3
VDE 0482-332-3
Flammability of bunched cablesIEC 60332-3 Cat C
VDE 0472 Part 813DIN EN 60754-2
VDE 0482-754-3
Corrosiveness of gases emitted during fireIEC 60754-2
VDE 0472 Part 814DIN VDE 0472-814Insulation performance under fire (Circuit Integrity)IEC 60331
VDE 0472 Part 816DIN EN 61034-1
VDE 0482-1034-1
Measurement of smoke densityIEC 61034-1
VDE 0472 Part 815DIN EN 50267-2-1Non-halogen verificationIEC 60754-1

Source: EUROLAB – DIN VDE 0472 Testing

4. Test Procedures & Requirements

4.1 VDE 0472 Part 804 — Flame Propagation Test

According to DIN VDE 0472, the test requires the cable to be thermally stressed by the application of a propane-gas burner. The flame height shall be 125mm and/or 175mm in height. In order to achieve compliance to VDE 0472 Part 804, there should either be no flaming of the cable at all, or the flame should extinguish itself after the burner is removed before it reaches the upper end of the cable being tested.

🔥 VDE 0472 Part 804 — Flame Test Parameters
Test MethodPropane-gas burner application
Flame Height125mm and/or 175mm
Pass CriteriaNo flaming OR self-extinguishing before reaching upper cable end
Sample LengthApproximately 600mm (single cable)
Flame Application Time60 seconds (single) / 120 seconds (larger cables)

4.2 VDE 0472 Part 814 — Insulation Integrity Test (Circuit Integrity)

This is the critical fire resistance test for circuit integrity. The cable is energized at its rated voltage while being exposed to flame at minimum 750°C for the specified duration (FE60, FE90, FE120, or FE180). The test passes if the cable maintains electrical continuity throughout the test period without shorting.

⚡ VDE 0472 Part 814 — Circuit Integrity Test
StandardDIN VDE 0472-814 (Similar to IEC 60331, BS 6387 Cat C)
Test TemperatureMinimum 750°C flame exposure
Cable ConditionEnergized at rated voltage
Test Duration90 minutes flame application + 15 minutes cooling
Pass CriteriaNo fuse fails, no conductor rupture during entire test
EnvironmentDry, mechanically unstressed

Source: Eland Cables – Fire Performance Cable

4.3 BS 6387 Comparison — Enhanced Fire Testing

BS 6387 specifies performance requirements for cables required to maintain circuit integrity under fire conditions with multiple survival categories. Comparatively speaking, BS 6387 fire performance requirements are more demanding than DIN VDE 0472-814.

CategoryTest TemperatureDurationAdditional Stress
Cat A650°C3 hoursFire alone
Cat B750°C3 hoursFire alone
Cat C950°C3 hoursFire alone
Cat S950°C20 minutesFire + mechanical shock
Cat W650°C15+15 minFire + water spray

5. NHXH & NHXCH FE180 Fire Performance Cables

NHXH and NHXCH cables are European designation fire safety power cables with 0.6/1kV voltage rating, designed for circuit integrity and manufactured according to fire performance standards including DIN VDE 0472-814. These cables continue operating for set lengths of time in the event of a fire and are used for voice alarms, smoke alarms, and support for fire fighting and life saving efforts.

🟢 NHXH FE180 Cable Construction
Cable StandardDIN VDE 0266 HD 604 S1
Voltage Rating (U₀/U)0.6/1kV (600/1000V)
Test Voltage4kV AC
ConductorClass 1 Solid or Class 2 Stranded Copper
Fire BarrierHigh-performance Keram compound
InsulationXLPE compound DIX 3 (Cross-linked polymer, zero halogen)
SheathFRNC/LSZH compound HXM1
Temperature Range-30°C to +90°C (operating) / -35°C to +90°C (NHXH)
Short Circuit Temp+250°C
Min Bending RadiusSingle core: 15×OD | Multicore: 12×OD
Min Laying Temp-5°C

Source: Eland Cables – NHXH & NHXCH FE180 Cable

5.1 E30 & E90 Circuit Integrity Classifications

In addition to the FE (insulation integrity) rating, cables are also classified by their E (circuit integrity) rating per DIN 4102-12 system test. This tests the entire cable installation system including cable management for functional integrity in fire.

ClassificationMeaningStandardApplication
Insulation Integrity (FE)
FE180180 minutes insulation integrity at 750°CVDE 0472-814Cable material test
Circuit Integrity (E)
E3030 minutes system circuit integrityDIN 4102-12System test (cable + mounting)
E9090 minutes system circuit integrityDIN 4102-12System test (cable + mounting)

5.2 NHXH vs NHXCH Cable Comparison

ModelConstructionFire RatingApplication
NHXH FE180-E30Without concentric conductorFE180 E30Basic fire safety circuits
NHXH FE180-E90Without concentric conductorFE180 E90Extended fire safety circuits
NHXCH FE180-E30With copper wire/tape concentricFE180 E30Screened fire safety circuits
NHXCH FE180-E90With copper wire/tape concentricFE180 E90Extended screened circuits

Source: Halley Cables – NHXH FE180 E90

6. Fire Performance Standards Comparison

Test TypeDIN VDE StandardIEC StandardDescription
Flame Propagation Tests
Single Cable FlameVDE 0472-804B
VDE 0482-332-1
IEC 60332-1-2Single vertical cable flame test
Bunched Cable FlameVDE 0472-804C
VDE 0482-332-3
IEC 60332-3 Cat CVertical bunched cable flame test
Fire Resistance Tests
Circuit IntegrityVDE 0472-814IEC 60331Electrical integrity during fire
System IntegrityDIN 4102-12—Furnace test for functional integrity
Smoke & Gas Emission Tests
Smoke DensityVDE 0472-816
VDE 0482-1034-1
IEC 61034-1/23-meter cube smoke density test
Acid Gas EmissionVDE 0472-813
VDE 0482-754-3
IEC 60754-2Corrosiveness of combustion gases
Halogen FreeVDE 0472-815IEC 60754-1Non-halogen verification

7. Applications for VDE 0472 Fire Performance Cables

Safety cables tested to DIN VDE 0472 are used in all locations where a high degree of protection against fire and fire damage must be provided for human life and equipment, and where strict security requirements must be fulfilled. These cables are designed to continue operating in the event of fire, enabling critical safety systems to function.

🚨 Fire Alarm Systems

Voice alarms, smoke detectors
Fire detection circuits

🔦 Emergency Lighting

Evacuation lighting
Exit sign power supply

🛗 Evacuation Elevators

Firefighter lifts
Emergency elevator control

📢 PA & Announcement

Public address systems
Emergency broadcasting

🏥 Critical Facilities

Hospitals, data centres
Power stations

🏢 Public Buildings

Shopping centers, hotels
Airports, metro stations

⚠️ Important Installation Note

NHXH/NHXCH cables should not be laid on common cable trays but on fire-resistant trays which retain their geometry in case of fire. Keeping cables in the same position during fire enables additional protection of cable conductivity by means of the mineral layer discharged around the cable at increased temperature. These cables may not be installed directly into ground or water.

Source: TT Cables – NHXH FE180/E90

8. Key Technical Parameters

Voltage Rating

0.6/1kV
AC (U₀/U)

Test Voltage

4kV
AC

Fire Test Temp

750°C
Minimum flame exposure

Max Conductor Temp

+90°C
Continuous operation

Short Circuit Temp

+250°C
Maximum

FE180 Insulation

180 min
Insulation integrity

E90 Circuit

90 min
System circuit integrity

E30 Circuit

30 min
System circuit integrity

Authoritative External References

●
Eland Cables – DIN VDE 0472 Standard Cable
https://www.elandcables.com/…/vde0472-cable
●
Eland Cables – Fire Performance Cable
https://www.elandcables.com/…/fire-performance-cable
●
Eland Cables – NHXH & NHXCH FE180 Cable
https://www.elandcables.com/…/nhxh-nhxch
●
EUROLAB – DIN VDE 0472 Testing
https://www.eurolab.net/…/din-vde-0472
●
Fireproof Cables – DIN VDE 0472-814
http://www.fireproof-cables.com/…/VDE0472-814
●
Halley Cables – NHXH FE180 E90
https://halleycables.com/…/nhxh-fe180-e90
●
National Cable Factory – NHXH FE180-E30
https://nationalcablefactory.com/…/nhxh-fe180-e30
●
TT Cables – NHXH FE180/E90
https://www.ttcables.com/…/nhxh-fe180-e90
●
Datwyler IT Infra – (N)HXH FE180 E90
https://itinfra.datwyler.com/…/nhxh-fe180-e90
●
Keystone Cable – Flame Retardant Test Standards
https://www.keystone-cable.com/…/flame-retardant-test

Contact Feichun Cable

For technical support with DIN VDE 0472 fire performance cables, NHXH/NHXCH FE180-E30/E90 cables, or fire safety circuit integrity applications, please contact our engineering team.

📱
📧

Technical Support

[email protected]
👤

Sales – Mr. Zihao Yang

[email protected]
👤

Sales – Mr. Ziyu Huang

[email protected]

Anhui Feichun Special Cable Co., Ltd. | 安徽飞纯特种电缆有限公司

Professional Manufacturer of DIN VDE 0472 Fire Performance & Circuit Integrity Cables

© 2025 Feichun Cable. All rights reserved.