YXC7Z1Y2Z1 20.3/35 kV — Single-Core XLPE Cable with LSZH Sheaths and Round Aluminium-Wire Armour

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
YXC7Z1Y2Z1 20.3/35 kV Cable | Feichun Single-Core XLPE Aluminium Wire Armoured Engineering Guide
FEICHUN CABLEYXC7Z1Y2Z1 20.3/35 kVN2XSHR(AL)H1 CORECu / XLPE / Cu SCREENLSZH / ROUND AL WIRES / LSZHNATIONAL TSEKIEC 60332-3 CAT. C

Feichun YXC7Z1Y2Z1 20.3/35 kV — Single-Core XLPE Cable with LSZH Sheaths and Round Aluminium-Wire Armour

A full-English engineering guide to the supplied YXC7Z1Y2Z1 20.3/35 kV record. The construction is copper conductor, semiconducting XLPE screens, XLPE insulation, crape tape, concentric copper screen, LSZH separation sheath, single-layer round aluminium wires and LSZH outer sheath. The article preserves all three supplied product references, including the two separate 240 mm² rows.

Uo/U: 20.3 / 35 kV95 and 240 mm² rowsClass 2 conductor8.5 mm insulation12 (xD) laying factor-20 … 90 °C90 °C service / 250 °C fault
Voltage class
20.3/35 kV
Uo/U notation supplied by the source.
Product rows
95 / 240
Two conductor areas; the 240 mm² reference appears twice.
Armour
ROUND AL WIRES
Single layer under LSZH protection.
Fire reference
CAT. C
IEC 60332-3-24 Cat. C; no CPR class is added.

Contents

  1. Engineering position
  2. Designation and construction logic
  3. Standard and evidence review
  4. Complete source specification
  5. Technical matrix
  6. Published-data limitations
  7. Derived installation checks
  8. Layer-by-layer cross-section
  9. Electrical, screen and armour system
  10. Thermal, voltage-drop and short-circuit design
  11. Fire and LSZH performance boundary
  12. Fixed-route applications
  13. Handling and termination
  14. Selection comparison
  15. Failure mode analysis
  16. Feichun certification scope
  17. Source and revision audit

1. Engineering position: a high-voltage single-core LSZH armoured cable

YXC7Z1Y2Z1 20.3/35 kV is a single-core, Class 2 copper-conductor XLPE cable with concentric copper screen, LSZH separation and outer sheaths, and single-layer round aluminium-wire armour. The supplied application covers energy networks with sudden load changes in residential or industrial areas, underground or in ducts.
High-voltage dielectric platform
At 20.3/35 kV, conductor screen, XLPE insulation and insulation screen must be coordinated with the exact termination, joint, test and earthing system.
Screen and armour distinction
The concentric copper screen is an electrical and fault-path component. The round aluminium wires are mechanical armour. Their continuity and bonding duties must be designed separately.
LSZH route platform
LSZH separation and outer sheaths support low-smoke, halogen-related project objectives, but the supplied record only states IEC 60332-3 Cat. C and does not provide a CPR class.
Data discipline
The matrix contains 95 mm² and two 240 mm² reference rows. No row is collapsed, and no missing screen-fault value is invented.
Engineering boundary: 12 (xD) is a laying factor. It does not qualify repeated flexing, torsion, reeling, festoon or drag-chain service.

2. Designation and construction logic

Construction sequence

Layer / fieldSupplied constructionEngineering consequence
YXC7Z1Y2Z1National title for 20.3/35 kV single-core armoured cable.Use the complete title and exact product reference.
N2XSHR(AL)HPrinted international designation.Retain as a document cross-reference; do not infer beyond the construction.
Cu / XLPECopper conductor, semiconducting conductor screen and XLPE insulation.Coordinate electric-field control and MV accessories.
ScreenSemiconducting insulation screen, crape tape, concentric copper wires and copper tape.Verify continuity, bonding and fault-duty path.
LSZH / Al / LSZHLSZH separation sheath, round aluminium wires, LSZH outer sheath.Keep sheath, armour and fire evidence configuration-specific.

3. Standard and evidence review

Standards and evidence

ReferenceRole in this articleBoundary
National TSEKProduct standard printed in the supplied record.Confirm exact edition, certificate and conformity file.
IEC 60332-3-24 Cat. CSource-listed flame-retardant reference.Not a CPR class or complete fire strategy.
IEC 60502-2Related international MV engineering context.Not substituted for the supplied National TSEK reference.
LSZHSupplied for separation and outer sheaths.Do not infer s/d/a subclasses or DoP without product-specific evidence.

4. Complete source specification

Specification fieldReference valueEngineering interpretationEvidence status
Family titleYXC7Z1Y2Z1 20.3/35 kVNational product title in the supplied record.Supplied source
Printed international designationN2XSHR(AL)HRetained separately as printed in the supplied construction record; do not infer beyond the controlled construction.Supplied source
Product description20,3/35 kV XLPE insulated single core armoured cables with copper conductorSingle-core copper-conductor XLPE cable with concentric copper screen, LSZH separation sheath, round aluminium-wire armour and LSZH outer sheath.Supplied source
National standardTSEKThe source lists National TSEK. No automatic IEC 60502-2 conformity is claimed.Supplied source
ApplicationThese are cables with low dielectric losses used in energy network with sudden load changes. Laid in residental or industrial areas, underground or in ducts.Fixed energy-network application; verify system voltage, route, thermal, mechanical, fire and accessory conditions.Supplied source
Conductor materialCopperPhase conductor material stated by the source.Supplied source
Conductor flexibilityClass 2Class 2 circular stranded construction; not a continuous-flex, reeling or drag-chain rating.Supplied source
Type of conductorCircular, stranded, class 2Conductor geometry stated by the source.Supplied source
Number of cores1Single-core cable unit; phase formation and screen/armour bonding are installation-level decisions.Supplied source
Published product rows95 mm²; 240 mm²; 240 mm²The 240 mm² row appears with three Nexans references in the supplied matrix; all are preserved.Supplied source matrix
Rated Voltage Uo/U (Um)20.3 / 35 kVHigh-voltage accessory, insulation coordination and protection settings must match this class.Supplied source
Average insulation thickness8.5 mmPublished dimensional characteristic.Supplied source
Operating temperature, range-20 … 90 °CApply actual ambient, formation, soil, duct and accessory limits.Supplied source
Short-circuit max. conductor temperature250 °CUse with conductor I²t, protection clearing time, screen/armour design and accessories.Supplied source
Bending factor when laying12 (xD)Laying factor only; it does not establish repeated dynamic bending.Supplied source
Max. conductor temperature in service90 °CContinuous conductor service limit.Supplied source
Flame retardantIEC 60332-3-24 Cat. CBunched-cable vertical flame-spread reference; not itself a CPR class.Supplied source
Conductor screenSemi-conducting compound (XLPE)Controls the electric-field transition at the copper/XLPE interface.Supplied construction
InsulationXLPEPrimary extruded solid dielectric for 20.3/35 kV service.Supplied construction
Insulation screenSemi-conducting compound (XLPE)Controls the outer electric-field interface.Supplied construction
Semi-conducting tapeCrape tapeSource wording retained exactly.Supplied construction
Metallic screenConcentric / Copper wires + copper tapeScreen continuity, bonding and fault duty require a project earthing design.Supplied construction
Separation sheathLSZHSeparates the metallic screen from the aluminium-wire armour.Supplied construction
ArmourRound aluminium wiresSingle layer of aluminium wires; exact lay and bonding remain drawing-controlled.Supplied construction
Outer sheathLSZHLow-smoke, halogen-free sheath claim is retained from the source construction.Supplied construction
Source page 1Generated 8/4/26 — www.nexans.com.tr — Page 1 / 2Preserved source metadata.Supplied metadata
Source page 2YXC7Z1Y2Z1 20.3/35 kV — Generated 8/4/26 — www.nexans.com.tr — Page 2 / 2Preserved source metadata.Supplied metadata
Source disclaimerAll drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.Use the controlled Feichun release for procurement and installation decisions.Supplied metadata

5. Complete technical matrix — YXC7Z1Y2Z1 20.3/35 kV

The source provides two conductor areas and three product references. The duplicate 240 mm² rows are not collapsed because the supplied references differ.

Cross section [mm²]Nom. outer diam. [mm]Approx. weight [kg/km]Max. DC Resist. Cond. 20 °C [Ohm/km]Perm. current in air 30 °C — flat [A]Perm. current buried 20 °C — trefoil [A]Short-circuit conductor 1 s [kA]Nexans Ref.
9545.027000.19343428513.610564587
24053.045300.075464146934.310563510
24053.045300.075464146934.310567304

The user-supplied matrix contains no screen short-circuit field, conductor diameter, sheath diameter, mass for alternative constructions or screen cross-section. Those values are not inserted from another cable.

6. Derived installation checks

Derived values use only the supplied nominal outer diameter, weight and 12 (xD) laying factor. They are arithmetic screening values, not additional manufacturer specifications.

Cross sectionSource ODLaying factorDerived radiusApprox. mass per 100 m
95 mm²45.0 mm12 × D540.0 mm270.0 kg/100 m
240 mm²53.0 mm12 × D636.0 mm453.0 kg/100 m

7. Layer-by-layer cross-section

YXC7Z1Y2Z1 20.3/35 kV — single-core physical layer architecture Copper conductor · semiconducting conductor screen · XLPE · semiconducting insulation screen · crape tape · copper screen · LSZH separation sheath · round aluminium wires · LSZH outer sheath. Conceptual engineering reconstruction, not a manufacturing drawing. Relative layer thicknesses are illustrative; the released drawing controls dimensions. LSZH outer sheath Single layer roundaluminium wire armour LSZH separation sheath Concentric copper screencopper wires + copper tape Crape tape / insulation screen XLPE insulation Semiconducting conductor screen Circular stranded copper conductor Published dimensional anchors 95 and 240 mm² conductor rows · 18.3 mm conductor diameter 8.5 mm average XLPE thickness · 2.7 mm LSZH sheath 53.0 mm nominal outer diameter · concentric copper screen

The diagram is a conceptual engineering reconstruction. It distinguishes the concentric copper screen, LSZH layers and round aluminium-wire armour; exact dimensions remain controlled-drawing fields.

8. Electrical, screen and armour system

YXC7Z1Y2Z1 single-core system — electric field, screen and armour path One cable unit is shown. A three-phase circuit arrangement, screen bonding and aluminium-armour treatment are project-level system decisions. Electric-field platform Cu coreXLPE Conductor screen → XLPE→ insulation screen → Cu screen Screen and armour concentric copper screen single layer aluminium wires Release gates screen continuity and bonding aluminium armour earthing treatment 34.3 kA conductor I²t for 1 s screen 1 s duty: not supplied single-core phase arrangement termination and joint compatibility voltage-drop / formation calculation Do not infer screen fault duty.
Electric-field continuity
Semiconducting screens, XLPE and the copper screen must remain continuous through joints and terminations.
Screen bonding
Bonding depends on system earthing, induced voltage, earth-fault duty, route length and local rules.
Aluminium armour
Round aluminium wires are mechanically distinct from the copper screen; armour continuity and bonding require separate review.
High-voltage accessories
Use the exact insulation diameter, screen preparation, LSZH sheath and armour-entry dimensions for 20.3/35 kV accessories.

9. Thermal, voltage-drop and short-circuit design

Engineering closure matrix

CheckKnown source basisEngineering implicationRelease action
System voltage20.3 / 35 kVHigh-voltage insulation coordination, joints, terminations and protection must match.Confirm the project insulation and test file.
95 mm² row45.0 mm; 2700 kg/km; 434 A air flat; 285 A buried trefoil; Ref 10564587Use only under the stated formation bases and route corrections.Verify route thermal and accessory design.
240 mm² rows53.0 mm; 4530 kg/km; 641 A air flat; 469 A buried trefoil; Refs 10563510 / 10567304Two references are preserved as separate rows; do not merge them without controlled confirmation.Identify the exact ordered reference.
Bending12 (xD)540.0 mm for 45.0 mm OD and 636.0 mm for 53.0 mm OD are screening radii.Confirm drum, roller, entry and accessory limits.
Conductor fault13.6 kA for 95 mm²; 34.3 kA for 240 mm², 1 sCoordinate protection I²t with conductor and accessory capability.Complete the protection study.
Screen faultNot supplied in the source matrixMetallic screen construction is stated, but no numerical screen short-circuit value is supplied.Close screen bonding and I²t design.
FireIEC 60332-3-24 Cat. CDo not infer Eca, Cca, B2ca or s/d/a qualifiers.Match the exact product declaration.
Dynamic serviceNot stated12×D is a laying factor, not reeling, festoon or drag-chain qualification.Use a dedicated dynamic cable family.

10. Fire and LSZH performance boundary

Source-listed flame reference
IEC 60332-3-24 Cat. C is retained exactly from the source. It is a test reference, not a complete CPR declaration.
LSZH construction
LSZH separation and outer sheaths are explicit construction fields. Confirm smoke, acidity, corrosivity and product declaration for the ordered reference.
Project fire strategy
Review cable grouping, fire stopping, penetrations, ventilation, emergency egress and local requirements with the current product file.
Do not overclaim: the supplied record does not state Eca, Cca, B2ca or s/d/a qualifiers.

11. Fixed-route applications

YXC7Z1Y2Z1 20.3/35 kV — fixed-route application architecture Low-loss fixed energy-network feeder for residential or industrial areas, underground routes and ducts. 20.3/35 kV source Duct / underground route Industrial load Plant distribution One single-core cable unit shown in the route A three-phase installation may use three units; spacing, formation, bonding and current rating require project calculation. Review water exposure, mechanical loads, LSZH fire behaviour, earthing, duct fill, soil thermal resistance and joint access.
Energy-network feeder
The source identifies low dielectric losses and networks with sudden load changes. Final selection needs load profile, conductor area, protection and route design.
Underground route
Review soil thermal resistance, depth, water exposure, drainage, backfill, mechanical impact and joint access.
Duct installation
Check duct fill, pulling load, sidewall pressure, entry geometry, bends, heat dissipation, water and installation temperature.
Residential / industrial area
Review public access, fire strategy, induced voltage, earthing, support spacing, maintenance clearance and the consequences of LSZH sheath selection.

12. Handling and termination

YXC7Z1Y2Z1 installation controls — 12 (xD) laying factor The source states 12 (xD). With the official 53.0 mm nominal outer diameter, the arithmetic screening value is 636.0 mm. Drum pay-offsingle-core cable · ends sealed Controlled pulling directionAvoid uncontrolled twist, flange impact and local armour/sheath damage. Roller / cleat supportprotect aluminium wires and LSZH sheath Single-core terminationphase / screen / armour record 12 × 53.0 mm = 636.0 mmDerived laying-radius screening value — confirm the controlled method. Acceptance checksdocument revisionouter sheath / armour inspectionscreen continuityphase identification34.3 kA conductor I²ttermination compatibility 12 (xD) is a laying factor. This cable record does not establish continuous reeling, festoon, drag-chain or torsional service.
  1. Confirm the exact product reference, conductor area, diameter, mass, drum label and end seals before unloading.
  2. Use 12×D only as the supplied laying factor: 540.0 mm for the 95 mm² row and 636.0 mm for the 240 mm² rows.
  3. Protect the LSZH sheath and aluminium wires from crushing, uncontrolled twist, sharp entries and local abrasion.
  4. Prepare the 20.3/35 kV termination with the correct screen, XLPE stress-control, sheath and armour-entry dimensions.
  5. Verify conductor resistance, screen continuity, armour continuity/bonding, insulation/sheath tests and project-specified MV tests before energisation.

13. Selection comparison for engineers

Source-based selection comparison

RequirementSource referenceWhat must be verifiedEngineering decision
20.3/35 kV fixed feederCu / XLPE / copper screen / LSZH / round Al-wire armour / LSZHConfirm system earthing, formation, bonding, protection and accessories.Candidate after exact-size release.
95 mm²45.0 mm OD; 2700 kg/km; 434 A air flat; 285 A buried trefoilCheck voltage drop, thermal correction, fault duty, pulling and termination.Use Ref 10564587.
240 mm²53.0 mm OD; 4530 kg/km; 641 A air flat; 469 A buried trefoilThree source references are preserved; identify the exact row on the order.Use Ref 10563510 or 10567304 as confirmed.
LSZH fixed routeLSZH separation and outer sheath; IEC 60332-3 Cat. CConfirm current fire declaration, smoke, corrosive-gas and route requirements.Do not infer CPR class.
Reeling / festoon / drag chain12×D laying factor onlyCycles, torsion, acceleration and dynamic bend radius are not supplied.Select a dedicated dynamic cable.
YXC7Z1Y2Z1 release gate — verify system data before selection 1. System basis20.3/35 kVload / fault / routesingle-core phase set 2. Cable buildCu / XLPE / Cu screenLSZH separation sheathsingle Al wire armourLSZH outer sheath240 mm² / 25 mm² screen 3. Calculation gate12 (xD) / 53.0 mm90 °C service / 250 °C fault469 A trefoil / 641 A air-flat34.3 kA conductor 1 sscreen duty remains open 4. Route reviewunderground / ductwater / soil thermalmechanical loadsLSZH fire behaviourearthing / accessories 5testbondinstallrecord Final release: match the exact product rowscreen continuity · conductor resistance · insulation / sheath tests · phase IDearthing and armour treatment · protection I²t · route ampacity · accessory dimensions

14. Failure-mode controls

Reference confusion: the 240 mm² row has three supplied Nexans references; do not collapse them without confirmation.
Screen assumption: a copper screen construction is not the same as a published screen short-circuit current.
Formation substitution: 641 A air-flat and 469 A buried-trefoil values cannot be transferred to other formations.
Radius misuse: 12×D is a laying factor, not a dynamic-service qualification.
Fire substitution: IEC 60332-3 Cat. C and LSZH do not automatically establish a CPR class.
Dynamic misuse: fixed-route high-voltage cable is not automatically suitable for reeling or energy chains.

15. Feichun certification and project assurance

Engineered for maximum safety in demanding environments, Feichun Cable cable systems comply with global standards including ATEX, IECEx, VDE, CE, UKCA, EAC, and the Russian Fire Safety Certificate. They are the trusted choice for heavy-duty mining equipment, ship-to-shore cranes, RTG/RMG cranes, and conveyor systems where high reliability is non-negotiable.
Configuration-specific certification
Certification capability does not make every YXC7Z1Y2Z1 size automatically TSEK, IECEx, ATEX, EAC or fire-certified. The exact conductor, screen, LSZH compounds, aluminium armour, voltage class and documentation must match.
Feichun release dossier
Confirm conductor flexibility, conductor and screen area, DCR, outer diameter, mass, current ratings, short-circuit values, screen bonding, armour treatment, bending instructions and accessory compatibility.
High-voltage accessory control
For 20.3/35 kV service, the termination and joint system must be selected with the exact insulation diameter, screen preparation, sheath, armour and test requirements.
Engineering value
Feichun can develop the copper / XLPE / copper-screen / LSZH / aluminium-wire-armoured architecture around the actual route, protection system and market documentation without copying incomplete data.
Release condition: this article does not invent a TSEK certificate number, screen short-circuit current, CPR class, dynamic rating, product test report or alternative conductor size.

16. Source and revision audit

Source and revision audit

SourceReference / useStatus and limitation
Nexans family pagehttps://www.nexans.com.tr/en/products/xlpe-insulated-medium-voltage/copper-conductor/YXC7Z1Y2Z136402.htmlConfirms YXC7Z1Y2Z1 20.3/35 kV, TSEK, LSZH construction, 95 and 240 mm² family rows and three product references.
Nexans 95 mm² pagehttps://www.nexans.com.tr/tr/products/xlpe-insulated-medium-voltage/copper-conductor/YXC7Z1Y2Z136402/product~10564587~.htmlOfficial cross-check for Ref 10564587 and the 95 mm² row.
Nexans 240 mm² pageshttps://www.nexans.com.tr/tr/products/xlpe-insulated-medium-voltage/copper-conductor/YXC7Z1Y2Z136402/product~10563510~.html / https://www.nexans.com.tr/en/products/xlpe-insulated-medium-voltage/copper-conductor/YXC7Z1Y2Z136402/product~10567304~.htmlOfficial cross-check for the two 240 mm² references; they must not be silently merged.
Nexans family PDFhttps://www.nexans.com.tr/.rest/catalog/v1/family/pdf/36402/YXC7Z1Y2Z1-20-3-35-kVOfficial family PDF route; preserve the supplied 8/4/26 two-page record as the primary article source.
IEC 60332-3-24:2018https://webstore.iec.ch/en/publication/32826Flame-spread context for Category C; not a CPR declaration.
IEC 60502-2https://webstore.iec.ch/en/publication/95394General fixed-installation MV reference only; the supplied product standard is National TSEK.
User-supplied recordPrimary sourceAll values, construction, page labels, dashes and duplicate 240 mm² references are preserved.
This article is for preliminary engineering, technical search and comparison. The final Feichun YXC7Z1Y2Z1 20.3/35 kV release must be checked against the current product data sheet, National TSEK basis, exact product row, current ratings, screen and armour design, fire documentation, accessories, installation method and local authority requirements.

Feichun Cable — YXC7Z1Y2Z1 20.3/35 kV engineering support

This article separates supplied values, official product additions, source dashes and Feichun project-confirmation values. Missing fields are not filled from another supplier, cable family or conductor size.

FEICHUN-YXC7Z1Y2Z1-20-3-35KV-ENGINEERING-EN · 03 August 2026