Medium-Voltage Submersible Pump Motor Cable FC-FLX™ SUB-MV (N)TSCGEWÖU 6/10 kV 3×50 + 2×25/2 + S(4×0.5) mm²

Continuous-length replacement cable for Xylem Flygt pump 3400/883 with motor M54-60-6MDY/04 (250 kW, 6000 V, 50 Hz) — replaces original Xylem part no. 950023.

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
FC-TDS-SUB-2026-969E · FC-FLX™ SUB-MV (N)TSCGEWÖU 6/10 kV 3×50+2×25/2+S(4×0.5) — Technical Datasheet
Technical Datasheet · FC-TDS-SUB-2026-969E · Rev A
TYPE: SUB-MV U0/U (Um) 6/10 (12) kV EPR insulation CPE rubber outer sheath Permanent immersion Screened pairs S(4×0.5)

Medium-Voltage Submersible Pump Motor CableFC-FLX™ SUB-MV (N)TSCGEWÖU 6/10 kV 3×50 + 2×25/2 + S(4×0.5) mm²

Continuous-length replacement cable for Xylem Flygt pump 3400/883 with motor M54-60-6MDY/04 (250 kW, 6000 V, 50 Hz) — replaces original Xylem part no. 950023.

Doc no. FC-TDS-SUB-2026-969E Issue date 18 September 2026 Project JSC Pavlodar River Port, Kazakhstan Supply 1 × 180 m or 1 × 200 m, no joints
52.0 ± 1.5 mm
Overall diameter (50.5 – 53.5 mm)
≈ 4.25 kg/m
Nominal cable weight (4,250 kg/km)
315 / 520 mm
Min. bending radius, fixed / during handling
100 m
Max. permanent immersion depth (1.0 MPa)

1Application and scope

This datasheet defines a flexible medium-voltage power cable with integrated screened control pairs, built to the (N)TSCGEWÖU design principle of DIN VDE 0250-813 for heavy-duty rubber-insulated flexible cables. It is engineered as a direct replacement for the original supply cable of a Flygt 3400/883 submersible pump, for continuous operation with a 6000 V three-phase motor while permanently immersed in water.

The construction matches the requirement exactly: three 50 mm² phase conductors, two split earth conductors totalling 25 mm², and one S(4×0.5) control element made of four copper conductors arranged as two twisted pairs under a common screen. No optical fibres, no external control cable and no 3×50+3×25/3 substitution are used.

Design basis: DIN VDE 0250-813 construction principle · IEC 60228 class 5 conductors · DIN VDE 0207-20 (EPR 3GI3) insulation · DIN VDE 0207-21 (5GM5 / CPE) outer sheath · test methods of IEC 60502-2, IEC 60885-3 and IEC 60811 · flame propagation to IEC 60332-1-2.

2Motor and duty data used for the design check

ParameterValue (as confirmed by buyer)ParameterValue
Pump modelFlygt 3400/883Rated current≈ 30 A
Motor modelM54-60-6MDY/04Speed995 rpm
Rated power250 kWPower factorcos φ 0.83
Rated voltage6000 V, 3~, 50 HzMax. liquid temperature40 °C
ConnectionStar (Y)Reference / serial no.2431110
Original cableNTSCGEWÖU / NTSCGEWCOEUSOriginal Xylem P/N950023

3Cable cross-section

L1L2L3 PEPE 1234 Ø 52.0 ± 1.5 mm 1234567 891011121314 FC-FLX™ SUB-MV 6/10 kV 3×50+2×25/2+S(4×0.5) mm² FeiChun Special Cables · Hefei Doc no. FC-TDS-SUB-2026-969E Drawing FC-DWG-SUB-969E-01 Drawn ZY · Checked QA Rev A Scale ≈ 7 : 1 18.09.2026 Projection Units: mm
Fig. 1 — Section A–A, drawn to scale at nominal dimensions (first-angle projection).
Pos.ElementMaterial / design
1Phase conductor 3 × 50 mm²Tinned annealed copper, class 5 (IEC 60228)
2Conductor screenExtruded semi-conductive EPR
3InsulationEPR type 3GI3, 3.4 mm nominal
4Insulation screenExtruded semi-conductive EPR, triple extruded with 2 and 3
5Earth conductor 2 × 25/2 mm²Tinned copper class 5, 2 × 12.5 mm² split in interstices
6Earth coveringSemi-conductive rubber
7Control conductors S(4×0.5)Tinned Cu class 5, EPR insulated, 2 twisted pairs
8Common screenTinned copper braid, ≥ 85 % coverage + drain contact
9Control element sheathSemi-conductive / rubber sheath
10Filler and centreRubber filling compound, water-blocking
11Inner sheathRubber compound, extruded into interstices
12Anti-torsion reinforcementHigh-tenacity polyester braid
13Outer sheathCPE heavy-duty rubber, 5GM5 grade, black
14Outer surface / markingEmbossed legend and metre marks

4Construction details

ElementSpecificationNominal value
Phase conductorsTinned annealed copper, flexible class 5, IEC 602283 × 50 mm², Ø ≈ 9.2 mm
Conductor screenSemi-conductive EPR, extruded≈ 0.6 mm
InsulationEPR 3GI3, DIN VDE 0207-20; 90 °C rated3.4 mm nominal
Insulation screenSemi-conductive EPR, extruded, strippable≈ 0.6 mm
Diameter over coreTriple-extruded, dry-cured (CCV)≈ 18.6 mm
Phase core identificationPrinted numbers on semi-conductive screen1 · 2 · 3 (L1 · L2 · L3)
Earth conductorsTwo tinned copper class 5 conductors in outer interstices, each with semi-conductive rubber covering2 × 12.5 mm² (Σ 25 mm²)
Control element S(4×0.5)4 × 0.5 mm² tinned copper class 5, EPR insulated; two twisted pairs; common tinned-copper braid screen; semi-conductive/rubber sheath; placed in third intersticeØ ≈ 8.4 mm
Control core coloursPair A: white / brown · Pair B: green / yellow (DIN 47100)+ printed 1–4
Lay-upThree phase cores, earths and control element stranded with short lay length; water-blocking rubber fillerØ ≈ 40.1 mm
Inner sheathRubber compound, extruded to fill interstices≈ 2.0 mm
ReinforcementPolyester anti-torsion braid between sheaths≈ 0.5 mm
Outer sheathCPE-based heavy-duty rubber, 5GM5 grade (DIN VDE 0207-21); water, oil, ozone and UV resistant; flame retardant≈ 3.5 mm, black

5Dimensions and weights

CharacteristicValueRemark
Overall diameter, nominal52.0 mmMeasured to IEC 60811-201/-203
Overall diameter, tolerance± 1.5 mm (50.5 – 53.5 mm)Guaranteed range on the supplied drum
Cable weight, nominal≈ 4.25 kg/m (4,250 kg/km)Tolerance ± 5 %
Copper content≈ 1.62 kg/mPhase + earth + control
Net weight, 180 m≈ 765 kgCable only
Net weight, 200 m≈ 850 kgCable only

6Electrical characteristics

CharacteristicValue
Rated voltage U0/U (Um)6/10 (12) kV, AC
Routine AC test voltage, core to core and to earth21 kV (3.5 U0), 5 min
Partial discharge at 1.73 U0 (10.4 kV)≤ 10 pC
Max. DC resistance, phase conductor at 20 °C0.393 Ω/km
Max. DC resistance, earth (2 × 12.5 mm² in parallel) at 20 °C0.795 Ω/km
Max. DC resistance, control conductor 0.5 mm² at 20 °C40.1 Ω/km
Insulation resistance at 20 °C (power cores)≥ 2,000 MΩ·km
Capacitance per core, approx.0.33 µF/km
Inductance per phase, approx.0.34 mH/km
Current rating, in air 30 °C / immersed in water ≤ 40 °C180 A / 180 A
Short-circuit current, phase conductor (1 s, 90 → 250 °C)7.15 kA
Control element rating / test voltage300/500 V · 2 kV AC, 5 min

7Mechanical, thermal and immersion characteristics

CharacteristicValue
Min. bending radius, fixed installation (6 × D)315 mm
Min. bending radius, during handling / pump lifting (10 × D)520 mm
Max. conductor temperature, continuous / short circuit+90 °C / +250 °C
Ambient temperature, flexing / fixed−25 … +60 °C / −40 … +60 °C
Water temperature, permanent immersionup to +40 °C (motor limit)
Max. permanent immersion depth100 m water column (1.0 MPa)
Max. static tensile load on phase conductors (15 N/mm²)2,250 N
Flame propagationIEC 60332-1-2
Oil, ozone and UV resistanceYes (5GM5 / CPE)
Handling note: the pump must be lifted by its lifting chain or wire — never by the cable. Keep at least 520 mm bending radius at the cable entry and cable holder, and use a support grip every 3–5 m on vertical runs.

8Application engineering check for the Flygt 6000 V motor

8.1 Voltage class selection

The motor’s rated voltage of 6000 V is the phase-to-phase voltage U. A 3.6/6 kV cable (Um 7.2 kV) is rated exactly at the motor voltage and leaves only the IEC voltage-tolerance margin. A 6/10 kV cable (Um 12 kV) gives a thicker EPR wall, a lower electrical stress in permanent immersion and a large reserve against supply over-voltage, switching transients and long-term water ageing. FeiChun recommends 6/10 kV for this duty, and this datasheet is based on it.

8.2 Current-carrying capacity

Motor current ≈ 30 A versus 180 A rating of 3 × 50 mm² — a utilisation of about 17 %. Conductor operating temperature will stay close to the water temperature.

8.3 Voltage drop over 180 m / 200 m

ΔU = √3 · I · L · (R90 cos φ + X sin φ), with I = 30 A, R90 ≈ 0.50 Ω/km, X ≈ 0.10 Ω/km, cos φ = 0.83:

LengthΔUΔU as % of 6000 VResult
180 m≈ 4.4 V≈ 0.07 %Negligible
200 m≈ 4.9 V≈ 0.08 %Negligible

8.4 Earth and control functions

The two split earth conductors (Σ 25 mm²) are embedded in semi-conductive rubber in contact with the core screens, forming the protective-earth and screen-return path required for 6 kV operation. The S(4×0.5) screened pairs carry the motor’s monitoring circuits (thermal and leakage sensors) with their common screen protecting them from the adjacent 6 kV field.

8.5 Cable entry

The overall diameter of 52.0 ± 1.5 mm is designed to suit the original Flygt MV cable entry. The cable is terminated in the entry with a Flygt grommet/seal sleeve matched to the measured OD; FeiChun will confirm the final OD against the original cable marking and entry photographs before production starts.

9Factory tests and test reports supplied

TestMethod / criterionReport
High-voltage AC withstand21 kV, 5 min, each core to all others and earth — no breakdownSupplied
Partial dischargeIEC 60885-3; ≤ 10 pC at 1.73 U0Supplied
Insulation resistance500/2500 V DC, corrected to 20 °C; ≥ 2,000 MΩ·kmSupplied
Water immersion testFull drum length immersed in water, then HV and insulation resistance repeated — no breakdown, no IR drop beyond limitSupplied
Conductor resistanceIEC 60228 limits, all phase, earth and control conductorsSupplied
Control elementContinuity, pair identity, screen continuity, 2 kV AC testSupplied
Dimensional checkOD, insulation and sheath thickness, length and joint-free confirmationSupplied

A complete factory test report and inspection certificate is issued for the actual drum and sent with the shipping documents. Sample reports from previous production of the same design can be provided before the order is placed.

10Supply, marking and packing

ItemDetail
Delivery lengthOne continuous length of 180 m or 200 m on one drum, without joints or repairs (no minimum order quantity applies)
Sheath markingFEICHUN FC-FLX™ SUB-MV (N)TSCGEWÖU 6/10 kV 3×50+2×25/2+S(4×0.5) 2026 + metre marks
DrumSteel-reinforced wooden drum, barrel Ø ≥ 1,100 mm; cable ends sealed with heat-shrink caps; drum lagged
Drum size / gross weight (est.)Flange ≈ Ø 1,800 × W 1,100 mm · ≈ 1,150 kg (180 m) / ≈ 1,250 kg (200 m)
HS code8544.60

11Written confirmation of suitability

FEICHUN
SPECIAL
CABLES
QA

Declaration of suitability — FC-TDS-SUB-2026-969E

Anhui FeiChun Special Cable Co., Ltd. hereby confirms that the cable FC-FLX™ SUB-MV (N)TSCGEWÖU 6/10 kV 3×50+2×25/2+S(4×0.5) mm², manufactured to this datasheet:

  1. is suitable for continuous operation with the Flygt 3400/883 pump and motor M54-60-6MDY/04, 250 kW, 6000 V, 3~, 50 Hz, star connection, rated current ≈ 30 A;
  2. is suitable for permanent immersion in water at up to 40 °C and up to 100 m depth;
  3. has EPR insulation and a waterproof CPE rubber outer sheath, and contains the S(4×0.5) control element as two copper twisted pairs with a common screen, with no optical fibres;
  4. is designed to fit the original Flygt cable entry, and will be supplied as one continuous 180 m or 200 m length without joints.
Zihao YangTechnical Sales Manager, International Business Department
Quality Assurance DepartmentAnhui FeiChun Special Cable Co., Ltd. · Date: 18.09.2026
Trademark and intellectual property notice. Xylem, Flygt and part number 950023 are trademarks or identifiers of their respective owners and are cited only to identify the equipment for which this cable is intended; FeiChun has no affiliation with those owners. FC-FLX™ and FeiChun® are trademarks of Anhui FeiChun Special Cable Co., Ltd. This datasheet, including the cross-section drawing, is protected under the Copyright Law and Anti-Unfair Competition Law of the People’s Republic of China and the Copyright Act 1968 (Cth) of Australia; it may not be copied or passed to third parties for manufacturing purposes without written consent. Values marked “≈” are nominal design values; binding values are those in the factory test report of the supplied drum.

Anhui FeiChun Special Cable Co., Ltd.
International Business Department · Hefei, Anhui Province, China
www.feichuncables.com

Technical: [email protected]
Mining & pump cables: [email protected]
Sales: [email protected]
WhatsApp: +86 138 5512 3218

FC-TDS-SUB-2026-969E · Rev A · 18.09.2026FC-FLX™ SUB-MV 6/10 kV 3×50+2×25/2+S(4×0.5)
FC-TDS-SUB-2026-969E · FC-FLX™ SUB-MV 6/10 kV 3×50+2×25/2+S(4×0.5) · Pavlodar River Port