ÖPVC-JZ/OZ-CY: compact screened control cable with numbered cores

An engineering guide to a multicore control cable built for EMC: black PVC cores with white numerals, a tinned copper braid of approx. 85 % coverage applied directly over the core assembly and a grey RAL 7001 PVC sheath — the space-saving alternative to ÖPVC-JZ/OZ-YCY.

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
ÖPVC-JZ/OZ-CY compact screened control cable | FeiChun Cable
FEICHUN CABLE · SCREENED NUMBERED-CORE CONTROL CABLE

ÖPVC-JZ/OZ-CY: compact screened control cable with numbered cores

An engineering guide to a multicore control cable built for EMC: black PVC cores with white numerals, a tinned copper braid of approx. 85 % coverage applied directly over the core assembly and a grey RAL 7001 PVC sheath — the space-saving alternative to ÖPVC-JZ/OZ-YCY.

Similar to EN 50525-2-51IEC 60228 class 5IEC 60332-1300/500 VTest voltage 4 kVCu braid ≈85 %2–50 coresC ≈120 / 155 nF/kmRoHS · CE
Document FC-ART-JZCY-2026-033CUpdated: 20 September 2026FeiChun Cable / 飞纯电缆
Engineer’s summary: JZ/OZ-CY is the space-saving screened option: no inner sheath, so outer diameters are clearly smaller than YCY, at the cost of less mechanical protection and a 2 kV core/screen test. It is rated for fixed laying and free movement only — not drag chains, not burial.

1. Reading the designation

JZ = with GNYE and numbered cores (‘G’); OZ = without GNYE (‘x’). C-Y = copper braid under a PVC outer sheath, with no inner sheath. The whole range is rated 300/500 V; test voltage is 4 kV core/core and 2 kV core/screen.

53

Standard constructions, 2 × 0.5 to 4 G 35 mm².

50

Maximum core count (0.75 mm²).

≈85 %

Braid optical coverage.

120 nF/km

Core/core capacitance.

2. Construction

Omitting the inner sheath is what makes CY compact and lighter. The trade-off: the braid bears directly on the core assembly, so impacts and tight bends reach the cores more directly. Where the route carries mechanical risk, use YCY or protect the cable in conduit or ducting.

Cross-section ÖPVC-JZ-CY 7 G · numbered cores, Cu braid, grey sheathEngineering-drawing style · functional, not to scale · final dimensions per approved order drawingGNYE123456Ø d = 5.4 … 30.4 mm (see tables)1Bare Cu strand, IEC 60228 class 52PVC core insulation, black3White numerals (DIN VDE 0293)4GNYE protective conductor (JZ)5Tinned Cu braid, approx. 85 %, over cores/tape6Grey PVC outer sheath, RAL 7001DocumentRevisionProjectionFC-ART-JZCY-2026-033CA · 2026-091st angle
Figure 1: Construction of the 7 G version; callouts match the Pos. column of the materials table.
Outer diameter: JZ/OZ-CY versus JZ/OZ-YCY (same construction)
ConstructionCY Ø mmYCY Ø mmDifference
2 × 0.55.47.0−23 %
5 G 17.99.6−18 %
12 G 1.512.915.2−15 %
25 G 1.517.920.5−13 %
4 G 1017.219.4−11 %
4 G 2525.128.9−13 %
Materials table (Pos. = callout numbers in Figure 1)
Pos.ElementMaterial / formEngineering function
1ConductorBare Cu, fine-wire, IEC 60228 cl. 5Flexibility for installation and free movement
2Core insulationPVC, black+70 °C continuous, +150 °C short-circuit
3Core markingWhite numerals per DIN VDE 0293Clear identification of many control circuits
4Protective conductorGNYE core in JZ (‘G’) versionsOZ (‘x’) versions have none
5Overall screenTinned Cu braid, approx. 85 % optical coverageEMC screening directly over the core assembly — no inner sheath
6Outer sheathPVC, grey RAL 7001IEC 60332-1; acids, bases and specified oils largely resisted

3. Technical data

Technical data (complete)
ParameterValueEngineering note
Conductor materialBare copper strand
Conductor classIEC 60228 class 5
Core insulationPVC
Core identificationAcc. to DIN VDE 0293: black cores with white numerals; G: with GNYE
StrandingCores stranded in layers
Overall screenTinned copper braid, optical coverage approx. 85 %EMC-compliant; space-saving alternative to JZ/OZ-YCY
Outer sheathPVC
Sheath colourGrey, RAL 7001
Rated voltage U0/U300/500 VWhole range, 0.5–35 mm²
Test voltageCore/core: 4 kV; core/screen: 2 kVCore/screen lower because there is no inner sheath between cores and braid
CapacitanceCore/core approx. 120 nF/km; core/screen approx. 155 nF/kmRelevant for long signal runs and drive-cable charging currents
Conductor resistanceAcc. to IEC 60228 cl. 5
Insulation resistanceMin. 20 MΩ × km
Current carrying capacityAcc. to DIN VDE (technical guideline)
Min. bending radius fixed6 × dLarger than unscreened JZ/OZ (4 × d) because of the braid
Min. bending radius moved15 × d
Operating temp. fixed−40 °C / +80 °C
Operating temp. moved−15 °C / +70 °C
Conductor temperature+70 °C operation; +150 °C short-circuit
Burning behaviourSelf-extinguishing and flame-retardant acc. to IEC 60332-1Single-cable test
Chemical resistanceLargely resistant to acids, bases and specified oils
StandardSimilar to EN 50525-2-51
ComplianceRoHS; 2014/35/EU Low Voltage Directive (CE); LABS-/silicone-free during production

4. EMC: the braid only works if it is terminated

Recommended practice 1. Bond the braid 360° with EMC cable glands; avoid pigtails — a few centimetres of pigtail lose most of the high-frequency screening. 2. Keep the braid continuous up to the gland; do not open it further than necessary. 3. Segregate screened control cables from unscreened power cables on trays, or use a metal divider. 4. Bond both ends for drive and switching noise; for ground-loop-sensitive analogue signals, follow the equipment manufacturer.

5. Full dimension and weight tables

All 53 constructions are listed, grouped by cross-section. Bending radii are calculated from the nominal outer diameter (6 × d fixed, 15 × d moved).

Cross-section 0.5 mm² · 300/500 V · screened · 8 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 0.5OZ (without GNYE)05007865.436.040.03281
3 G 0.5JZ (with GNYE)05007195.743.056.03486
4 G 0.5JZ (with GNYE)05007256.349.077.03894
5 G 0.5JZ (with GNYE)05007326.757.090.040100
7 G 0.5JZ (with GNYE)05007467.569.0112.045112
12 G 0.5JZ (with GNYE)05006939.6104.0177.058144
18 G 0.5JZ (with GNYE)050069711.4141.0237.068171
25 G 0.5JZ (with GNYE)050071013.6211.0350.082204
Cross-section 0.75 mm² · 300/500 V · screened · 14 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 0.75OZ (without GNYE)05007825.943.056.03588
3 G 0.75JZ (with GNYE)05007216.252.071.03793
3 x 0.75OZ (without GNYE)50006976.252.071.03793
4 G 0.75JZ (with GNYE)05007266.861.092.041102
4 x 0.75OZ (without GNYE)05014886.861.092.041102
5 G 0.75JZ (with GNYE)05007337.572.0109.045112
7 G 0.75JZ (with GNYE)05007408.189.0156.049122
8 G 0.75JZ (with GNYE)05007528.693.0160.052129
10 G 0.75JZ (with GNYE)050068410.3107.0164.062154
12 G 0.75JZ (with GNYE)050069510.8138.0210.065162
18 G 0.75JZ (with GNYE)050070412.5211.0287.075188
25 G 0.75JZ (with GNYE)050071215.1280.0416.091226
34 G 0.75JZ (with GNYE)050071816.8307.0471.0101252
50 G 0.75JZ (with GNYE)050366820.0480.0732.0120300
Cross-section 1 mm² · 300/500 V · screened · 10 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 1OZ (without GNYE)05007896.351.072.03894
3 G 1JZ (with GNYE)05007226.562.090.03998
3 x 1OZ (without GNYE)05008006.562.090.03998
4 G 1JZ (with GNYE)05007277.274.0109.043108
4 x 1OZ (without GNYE)05008147.274.0109.043108
5 G 1JZ (with GNYE)05007347.988.0126.047118
7 G 1JZ (with GNYE)05007498.5112.0171.051128
12 G 1JZ (with GNYE)050069611.4185.0262.068171
18 G 1JZ (with GNYE)050070513.4268.0378.080201
25 G 1JZ (with GNYE)050071316.2354.0541.097243
Cross-section 1.5 mm² · 300/500 V · screened · 9 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 1.5OZ (without GNYE)05007907.065.090.042105
3 G 1.5JZ (with GNYE)05007157.582.0115.045112
3 x 1.5OZ (without GNYE)05008037.582.0115.045112
4 G 1.5JZ (with GNYE)05007208.2100.0153.049123
5 G 1.5JZ (with GNYE)05007358.9119.0176.053134
7 G 1.5JZ (with GNYE)05007439.6154.0220.058144
12 G 1.5JZ (with GNYE)050069812.9268.0340.077194
18 G 1.5JZ (with GNYE)050070615.3373.0499.092230
25 G 1.5JZ (with GNYE)050071417.9530.0688.0107268
Cross-section 2.5 mm² · 300/500 V · screened · 6 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
2 x 2.5OZ (without GNYE)05007938.192.0140.049122
3 G 2.5JZ (with GNYE)05007238.9118.0167.053134
4 G 2.5JZ (with GNYE)05007309.7147.0216.058146
5 G 2.5JZ (with GNYE)050073710.7176.0253.064160
7 G 2.5JZ (with GNYE)050075011.9253.0326.071178
12 G 2.5JZ (with GNYE)050069915.8345.0545.095237
Cross-section 4 mm² · 300/500 V · screened · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 4JZ (with GNYE)050072412.0248.0284.072180
Cross-section 6 mm² · 300/500 V · screened · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 6JZ (with GNYE)050073114.2343.0385.085213
Cross-section 10 mm² · 300/500 V · screened · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 10JZ (with GNYE)050072817.2535.0663.0103258
Cross-section 16 mm² · 300/500 V · screened · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 16JZ (with GNYE)050672220.2800.0984.0121303
Cross-section 25 mm² · 300/500 V · screened · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 25JZ (with GNYE)050686925.11,075.01,481.0151376
Cross-section 35 mm² · 300/500 V · screened · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend radius fixed (6 × d) mmMin. bend radius moved (15 × d) mm
4 G 35JZ (with GNYE)050687030.41,576.01,961.0182456

6. Application envelope

Power, control and connecting cable in electrical facilities, for interference-free data and signal transmission, in fixed laying and flexible applications with free movement, without tensile stress and without forced guidance. Suitable for dry, humid and wet rooms. Outdoor use only with UV protection; not for burial.

Application envelope of ÖPVC-JZ/OZ ✔ Drive to motor (VSD) 360° braid bonding at both ends ✔ Signals near power circuits Free movement ≥ 15 × d, no tension ✘ Not designed for • Drag chains / forced guidance• Tensile load, reels, festoons• Direct burial• Outdoors without UV protection• Pigtail braid terminations Use a PUR/TPE screened chain cablefor drag chains. Suitable for dry, humid and wet rooms. Suitable for dry, humid and wet rooms; the braid works only if terminated 360°.
Figure 2: Permitted duties and exclusions.

7. Comparison

JZ/OZ-CY compared with related cables
TypeScreenSheathDiameterTest voltageTypical use
ÖPVC-JZ/OZNoneSingle PVC, grey—4 kVGeneral control wiring
ÖPVC-JZ/OZ-CYTinned Cu braid ≈85 %Single PVC, greySmallest screened Ø4 kV core/core · 2 kV core/screenScreened control where space is tight
ÖPVC-JZ/OZ-YCYTinned Cu braid ≈85 %PVC inner + transparent outerLarger Ø4 kVScreened control with extra mechanical protection
PUR chain cable, screenedHigh-coverage braidPUR/TPE——Drag chains, robots

8. Design calculations

Current rating: DIN VDE base value × f(ambient) × f(grouping) × f(loaded cores) Short-circuit (PVC 70 → 150 °C, Cu): I_k ≈ 115 × S / √t e.g. 4 G 35, t = 0.5 s → ≈ 5.7 kA Voltage drop: ΔU = √3 × I × L × (R cosφ + X sinφ) Bending: fixed R ≥ 6 × d · moved R ≥ 15 × d e.g. 25 G 1.5 (d = 17.9 mm): 107 mm / 269 mm Capacitive charging current (per phase, rough): I_c ≈ 2π·f·C·U₀·L Gland sizing: select EMC gland clamping range around the nominal outer Ø in the tables

9. Certification and traceability

This cable is RoHS-conform, CE-conform to the 2014/35/EU Low Voltage Directive and LABS-/silicone-free during production, with flame behaviour to IEC 60332-1. FeiChun Cable holds a complete export certification portfolio — including CE, UKCA, VDE, EAC, ATEX and IECEx — and every certificate supplied is checked against the exact type, voltage, factory and standard of the order.

Routine tests

Conductor resistance, 4 kV core/core and 2 kV core/screen voltage tests, insulation resistance, braid continuity, core numbering, dimensions and marking.

Type tests

IEC 60332-1 flame, sheath ageing, cold behaviour, oil resistance on request.

Delivery documents

Approved datasheet, test report per drum, batch number and length marking.

10. FAQ

CY or YCY?

CY is the compact version: the braid is applied directly over the cores, so the outer Ø is typically 11–23 % smaller. YCY adds a PVC inner sheath for mechanical protection and a higher core/screen margin.

Why is core/screen tested at only 2 kV?

Without an inner sheath, only the core insulation separates conductor and braid. Core/core is still tested at 4 kV.

What do the capacitance values mean?

About 120 nF/km core/core and 155 nF/km core/screen. For long analogue or drive circuits, capacitance affects signal rise time and drive charging current.

Is 85 % coverage enough?

For typical industrial EMC, yes, provided the braid is bonded 360° at both ends with EMC glands.

Can it go in a drag chain?

No: free movement only, without tensile stress or forced guidance.

Outdoor use?

Only with UV protection; never buried.

FeiChun Cable / 飞纯电缆
Technical and project enquiries: [email protected]
Manufacturing in China, export support
+86 13855123218
FEICHUN CABLE

Screened numbered-core control cable in the smallest diameter

For control panels, drives, machinery and industrial installations.

[email protected]

+86 13855123218

Document FC-ART-JZCY-2026-033C. Final values are governed by the approved datasheet, order drawing, batch test reports and certificate scope.