TXP / TXP-D: PUR Round Cable for Heavy-Duty Festoon and Energy-Guiding Applications

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
TXP / TXP-D | PUR Round Cable for Heavy-Duty Festoon | Feichun Cable
Feichun Cable · Industrial handling, crane and mobile machinery engineering

TXP / TXP-D: PUR Round Cable for Heavy-Duty Festoon and Energy-Guiding Applications

A practical engineering guide to a halogen-free polyurethane round cable family for continuous heavy-duty conveying machinery, container-crane trolleys, process cranes, conveyors and moveable stage equipment. The design target is not merely flexibility; it is stable performance while speed, acceleration, guide forces, abrasion, temperature and atmospheric exposure act at the same time.

PUR round cable0.6/1 kV TXP300 V TXP-D data branchTravel up to 210 m/minHalogen freeEnergy guiding chains
English engineering articleIssued 05 August 2026Complete supplied matricesFive inline SVG drawings

What is TXP / TXP-D?

TXP is a halogen-free PUR round cable for continuous heavy-duty festoon and energy-guiding duties. TXP-D is the data branch of the same design philosophy, covering paired copper data and fibre-optic constructions. The round cable architecture is chosen when the machine imposes repeated bending, acceleration and guide interaction rather than a static installation.

The supplied type designation is D12Y11Y. The family is aimed at horizontal or vertical machinery with energy guiding chains, including container-crane trolley power supply; process cranes and conveyor equipment indoors or outdoors; and theatres or scenic machinery where halogen-free and flame-retardant compounds are required. The stated electrical rating is U₀/U = 0.6/1 kV for TXP, while the detailed data-cable table identifies the supplied TXP-D data branch as 300 V.

The design combines highly flexible class-5 copper conductors, a polyester-based halogen-free insulation system, a twisted core arrangement around a central element, and a PUR outer sheath described as abrasion- and cut-resistant. This is a sensible architecture for a cable that must survive frequent continuous bending, but the machine guide and end restraint still determine the actual service life.

210 m/min
Maximum travel speed stated in the supplied TXP / TXP-D product record. Validate it with trolley spacing, acceleration and guide friction.
6 × Ø / 10 × Ø
Front mechanical statement: TXP 6ר dynamic; TXP-D 10ר dynamic. The additional table also lists 6ר festoon and 7.5ר energy-chain values.
−40…+80°C
TXP flexing ambient range; TXP-D has a separate −30…+70°C flexing range and −40…+80°C fixed range.
≈80%
Approximate tinned-copper braid coverage specified for screened constructions.

Public engineering context. Conductix-Wampfler describes festoon cables as products engineered for heavy-duty operation, high dynamics and harsh environments, with finely stranded conductors and robust sheath compounds. That context supports the engineering logic of this family; the exact TXP / TXP-D values and order rows below are transcribed from the supplied record.

Electrical, mechanical, thermal and chemical envelope

Electrical

TXP rated voltage: U₀/U = 0.6/1 kV.

TXP-D data row: U₀/U = 300 V.

AC test voltage: 2.5 kV.

Ampacity: according to DIN VDE 0298-4.

Mechanical

Travel speed: up to 210 m/min.

Front dynamic radius statement: TXP 6ר; TXP-D 10ר.

Additional table: 6ר fixed, 6ר festoon, 7.5ר energy guiding chains.

These values are preserved as separate source statements.

Thermal

TXP flexing: −40°C…+80°C.

TXP fixed: −50°C…+80°C.

TXP-D flexing: −30°C…+70°C.

TXP-D fixed: −40°C…+80°C.

Maximum conductor service temperature is 90°C; short circuit is 250°C.

Chemical and environmental

Halogen free · ozone resistant · oil resistant according to DIN EN 60811-2-1 · UV resistant · free of lacquer-damaging substances and silicone during production.

TXP flame retardant according to IEC 60332-1; TXP-D flame retardant according to IEC 60332-2-1. General colour: black.

Product envelope — supplied values are kept separate from engineering interpretation
ParameterSupplied valueEngineering interpretation
FamilyTXP / TXP-DPUR round cable for heavy-duty festoon and conveying machinery
TypeD12Y11YType designation in the supplied record; final print marking must be confirmed
TXP rated voltageU₀/U = 0.6/1 kVPower and control branch
TXP-D data voltageU₀/U = 300 VData branch; do not quote it as the 0.6/1 kV power rating
Travel speedup to 210 m/minApplication limit supplied for dynamic travel
TXP front dynamic radius6 × ØUse with TXP construction and released duty
TXP-D front dynamic radius10 × ØUse with TXP-D construction unless the final release states otherwise
Additional radius table6 × Ø fixed; 6 × Ø festoon; 7.5 × Ø energy guiding chainsSeparate source statement; resolve against the selected duty
Ambient TXPflexing −40…+80°C; fixed −50…+80°CTXP ambient range
Ambient TXP-Dflexing −30…+70°C; fixed −40…+80°CTXP-D ambient range
Conductor / short circuit90°C / 250°CConductor limits, not ambient limits
AC test voltage2.5 kVRelease test report must identify the applicable circuit and standard
ColourblackTXP-D copper pair row separately states green PVC outer sheath
Temperature and radius are not one generic “flexibility” number. A TXP cable may have a different ambient flexing range from TXP-D, and the radius depends on construction and installation category. The final drawing must identify the exact branch.
TXP / TXP-D — PUR round festoon cable architecture Fine-stranded class-5 copper · halogen-free polyester insulation · twisted cores around a central element · PUR sheath. Schematic only — not to scale and not a released manufacturing drawing. Exact diameter and layer geometry follow the selected order number. centralelement 1234 1. Halogen-free PUR outer sheathAbrasion- and cut-resistant polyurethane for continuous heavy duty. 2. Screen optionShielded variants add PETP protection and an approximately 80% tinned-copper braid. 3. Twisted core arrangementCores are twisted around a central element; this is a round-cable load path. 4. Class-5 copper + halogen-free insulationFinely stranded bare copper according to VDE 0295 and polyester-based insulation. Round-cable boundary:the catalogue uses Ø min/max;do not quote a flat-cable d × B assumption.
Figure 1 — schematic TXP round cross-section. The drawing explains the architecture and is not a dimensional manufacturing drawing.

Construction: why the round PUR architecture is used

The conductor is finely stranded bare copper, class 5 according to VDE 0295. The cores are twisted around a central element, which gives the cable a controlled round load path as it passes through an energy chain or festoon guide. The insulation compound is polyester-based and free of halogen; the outer sheath is polyurethane and free of halogen.

For heavy moving machinery, the outer sheath is not a cosmetic layer. The supplied design calls for an abrasion- and cutproof PUR material and also specifies resistance to ozone, oil and UV. These properties are valuable when the cable sees guide friction, steel dust, outdoor radiation, oil mist, humidity or repeated contact with trolley hardware. They do not remove the need to finish guides, control clamp pressure and eliminate sharp edges.

TXP / TXP-D construction features from the supplied record
Construction itemSupplied design detailService significance
ConductorFinely stranded bare copperSupports repeated bending and carries the electrical load
Conductor classClass 5 acc. to VDE 0295Use the specified flexibility class for termination and bending review
Core arrangementCores twisted around central elementCreates a controlled round cable geometry for dynamic movement
InsulationCompound based on polyester; free of halogenSupports the stated halogen-free and dynamic-duty design
Conductor codingUp to 5 cores: coloured acc. VDE 0293-308; from 6 cores: light insulation with black numerals, with/without GN/YEControls wiring and replacement accuracy
Outer sheathPolyurethane, free of halogenAbrasion- and cut-resistant PUR protection for heavy-duty service
General chemical propertiesOzone resistant; oil resistant acc. DIN EN 60811-2-1; UV resistantUseful for severe atmospheric conditions, subject to actual media and concentration
Production cleanlinessFree from lacquer-damaging substances and silicone during productionImportant in theatres, scenic machinery, painted steel plants and clean assembly zones
ColourBlackTXP-D copper pair exception: supplied row states PVC outer sheath, green

Round-cable discipline. A round cable is not automatically torsion-proof. The selected TXP duty should control the bending plane, guide clearance, end grip and return path. Where the machine creates multi-axis torsion or uncontrolled helical movement, the application should be reviewed as a different cable duty.

TXP / TXP-D — duty environments A round PUR cable for continuous heavy-duty movement where speed, acceleration, abrasion and climate act together. A. Container-crane trolley / energy chain travel up to 210 m/mincontainer-crane trolley · conveyor transfer equipment B. Theatres, conveyors and process plants stage machineryprocess crane / conveyorHalogen-free and flame-retardant materials matter when people, equipment and atmosphere share the space. Engineering reading:TXP and TXP-D belong in a complete guide system. Cable speed is not independent from energy-chain radius, loop control, acceleration and cable mass.Use the exact order row and the actual machine cycle when validating the service life.
Figure 2 — heavy-duty applications: container-crane trolley, energy guiding chain, theatre machinery, process crane and conveyor equipment.

Complete TXP / TXP-D order matrices

The following tables preserve all supplied conductor schedules, part numbers, outer-diameter ranges, copper indices, approximate weights, permitted tensile loads and minimum-order fields. A dash is retained exactly as a supplied field. Thousands separators such as 1.050, 1.152 and 1.200 are also retained as written.

Control cable TXP — 0.6/1 kV; complete source matrix supplied for this article
Cable familyConductors / constructionPart No.Outer Ø min/max [mm]Cu approx. [kg/km]Weight approx. [kg/km]Permitted tensile load [N]U₀/UMinimum order quantity
Control cable TXP12 G 1.5131240-R12G1,5#14.3 – 15.51733202700.6/1 kV–
Control cable TXP18 G 1.5131240-R18G1,5#14.5 – 15.72593804000.6/1 kV–
Control cable TXP24 G 1.5131240-R24G1,5#16.5 – 17.83465005400.6/1 kV–
Control cable TXP4 G 2.5131240-R4G2,5#9.2 – 10.2961601500.6/1 kV–
Control cable TXP5 G 2.5131240-R5G2,5#9.8 – 11.01201801800.6/1 kV–
Control cable TXP7 G 2.5131240-R7G2,5#11.5 – 12.71682502600.6/1 kV–
Control cable TXP12 G 2.5131240-R12G2,5#16.5 – 17.72884604500.6/1 kV–
Control cable TXP18 G 2.5131240-R18G2,5#16.7 – 17.94325806700.6/1 kV–
Control cable TXP24 G 2.5131240-R24G2,5#19.2 – 20.45767609000.6/1 kV–
Screened control cable TXP — 0.6/1 kV; complete source matrix supplied for this article
Cable familyConductors / constructionPart No.Outer Ø min/max [mm]Cu approx. [kg/km]Weight approx. [kg/km]Permitted tensile load [N]U₀/UMinimum order quantity
Screened control cable TXP7 G 1.5C131249-R7G1,5C#10.9 – 12.11922201500.6/1 kV–
Screened control cable TXP12 G 1.5C131249-R12G1,5C#15.0 – 16.22503602700.6/1 kV–
Screened control cable TXP18 G 1.5C131249-R18G1,5C#15.0 – 16.23414204000.6/1 kV–
Screened control cable TXP4 G 2.5C131249-R4G2,5C#12.1 – 13.21572501500.6/1 kV–
Screened control cable TXP5 G 2.5C131249-R5G2,5C#12.8 – 14.01902801800.6/1 kV–
Screened control cable TXP12 G 2.5C131249-R12G2,5C#17.4 – 18.62505304500.6/1 kV–
Screened control cable TXP18 G 2.5C131249-R18G2,5C#17.5 – 18.83416506700.6/1 kV–
Power cable TXP — 0.6/1 kV; complete source matrix supplied for this article
Cable familyConductors / constructionPart No.Outer Ø min/max [mm]Cu approx. [kg/km]Weight approx. [kg/km]Permitted tensile load [N]U₀/UMinimum order quantity
Power cable TXP1 × 25131140-R1X25#9.9 – 11.12402703700.6/1 kV–
Power cable TXP1 × 35131140-R1X35#11.7 – 12.93363805200.6/1 kV–
Power cable TXP1 × 50131140-R1X50#13.9 – 15.14805307500.6/1 kV–
Power cable TXP1 × 70131140-R1X70#16.2 – 17.46727401.0500.6/1 kV–
Power cable TXP1 × 95131140-R1X95#17.9 – 19.19129401.4200.6/1 kV–
Power cable TXP1 × 120131140-R1X120#20.2 – 21.51.1521.2001.8000.6/1 kV–
Power cable TXP1 × 150131140-R1X150#21.8 – 23.21.4401.4902.2500.6/1 kV–
Power cable TXP4 G 4131140-R4G4#10.3 – 11.51542302400.6/1 kV–
Power cable TXP4 G 6131140-R4G6#12.1 – 13.22303203600.6/1 kV–
Power cable TXP4 G 10131140-R4G10#15.0 – 16.23845206000.6/1 kV–
Power cable TXP4 G 16131140-R4G16#17.7 – 18.96147509600.6/1 kV–
Power cable TXP4 G 25131140-R4G25#21.1 – 22.59601.1601.5000.6/1 kV–
Power cable TXP4 G 35131140-R4G35#25.8 – 27.41.3441.6502.1000.6/1 kV–
Power cable TXP4 G 50131140-R4G50#31.0 – 33.01.9202.4103.0000.6/1 kV–
Power cable TXP5 G 4131140-R5G4#11.6 – 12.71922903000.6/1 kV–
Power cable TXP5 G 6131140-R5G6#14.0 – 15.22884204500.6/1 kV–
Power cable TXP5 G 16131140-R5G16#19.4 – 20.67689201.2000.6/1 kV–
Screened power cable TXP — 0.6/1 kV; complete source matrix supplied for this article
Cable familyConductors / constructionPart No.Outer Ø min/max [mm]Cu approx. [kg/km]Weight approx. [kg/km]Permitted tensile load [N]U₀/UMinimum order quantity
Screened power cable TXP1 × 25C131141-R1X25C#10.3 – 11.53103303700.6/1 kV–
Screened power cable TXP1 × 35C131141-R1X35C#12.3 – 13.54064305200.6/1 kV–
Screened power cable TXP1 × 50C131141-R1X50C#15.4 – 16.65506107500.6/1 kV–
Screened power cable TXP1 × 70C131141-R1X70C#17.0 – 18.37478101.0500.6/1 kV–
Screened power cable TXP1 × 95C131141-R1X95C#18.9 – 20.11.0661.0301.4200.6/1 kV–
Screened power cable TXP4 G 4C131149-R4G4C#13.6 – 14.72213302400.6/1 kV–
Screened power cable TXP4 G 6C131149-R4G6C#15.1 – 16.33004203600.6/1 kV–
Screened power cable TXP4 G 10C131149-R4G10C#18.4 – 19.64546406000.6/1 kV–
Screened power cable TXP4 G 16C131149-R4G16C#21.2 – 22.56949409600.6/1 kV–
Screened power cable TXP4 G 25C131149-R4G25C#24.5 – 26.21.0501.3601.5000.6/1 kV–
Screened power cable TXP4 G 35C131249-R4G35C#29.6 – 31.61.4441.8702.1000.6/1 kV–
Screened power cable TXP4 G 50C131149-R4G50C#35.1 – 37.62.0302.5603.0000.6/1 kV–
Data cable TXP-D — 300 V; complete source matrix supplied for this article
Cable familyConductors / constructionPart No.Outer Ø min/max [mm]Cu approx. [kg/km]Weight approx. [kg/km]Permitted tensile load [N]U₀/UMinimum order quantity
Data cable TXP-D* 2X2X0,75C PN IE TP131349-R2X2X0,75C-TP#6.3 – 6.72968150300 V–
Data cable TXP-D12 G 62,5/125131340-R12G62,5/125#13.0 – 15.0–170300300 V–
Data cable TXP-D12 G 50/125131340-R12G50/125#13.0 – 15.0–170300300 V–
Source-format note. A separator line shown between screened control rows is treated as a page-layout artefact, not as a cable record. The supplied screened-power table contains the part number 131249-R4G35C# for the 4 G 35C row; it is preserved exactly and not corrected by assumption.

How to read the order table

Outer Ø min/max = supplied round-cable diameter range Cu approx. = copper index in kg/km Weight approx. = cable mass in kg/km Permitted tensile load = catalogue value in N; not a universal working load U₀/U = branch-specific voltage field Minimum order quantity = supplied dash unless a concrete quantity is stated
Bending radius — preserve the TXP / TXP-D source boundary The supplied record contains a front summary and an additional mechanical table. Both are shown; the final project release must identify the applicable duty table. Front product statement TXP dynamic minimum6 × ØØ = selected outer diameter Additional mechanical table Fixed installation6 × ØFestoon6 × ØEnergy guiding chains7.5 × ØTXP-D front statement10 × Ø The TXP-D 10 × Ø statement and the7.5 × Ø energy-chain line are not silently merged. Release rule:confirm TXP or TXP-D, fixed / festoon / energy-chain duty, outer diameter basis and the applicable technical edition before manufacture.A generic radius copied from another cable family is not an engineering approval.
Figure 3 — both radius statements from the supplied record are shown. The final project release must resolve which construction and duty table applies.

The bending-radius issue that must not be hidden

The supplied record contains two mechanical descriptions. The opening product summary says TXP 6ר and TXP-D 10ר for the dynamic minimum bending radius. The additional technical data later lists minimum radii for free movement as 6ר for fixed installation, 6ר for festoon and 7.5ר for energy guiding chains.

These statements may reflect different construction categories, application tables or document versions. It would be poor engineering practice to silently choose the smaller number or to claim that the conflict does not exist. The correct action is to identify the exact product branch, installation mode, guide system and applicable technical edition in the release drawing. Until that is done, both source statements remain visible.

TXP

Front statement: dynamic minimum 6ר. Additional table: fixed 6ר, festoon 6ר, energy guiding chain 7.5ר.

TXP-D

Front statement: dynamic minimum 10ר. Additional table: fixed 6ר, festoon 6ר, energy guiding chain 7.5ר.

What to confirm

TXP or TXP-D; copper or fibre; energy chain or festoon; fixed / moving category; outer diameter basis; manufacturer release and installation instructions.

What not to do

Do not copy a radius from another PUR cable, a round reeling cable or a flat festoon cable and present it as TXP approval.

TXP / TXP-D — screening, data pairs and optical fibres The data branch is electrically different from the power/control branch and includes paired copper and fibre-optic constructions. Screened TXP construction PETP protection foiltinned copper braid ≈80%inner sheath PUR where specifiedFinal screen termination and bonding are part of the EMC design. TXP-D data elements paired copper data: 2X2X0,75C PN IE TPsupplied row: 300 V · PVC outer sheath · green fibre rows: 12G 62.5/125 or 50/125optical attenuation and bandwidth remain fibre-type specific. Do not use “TXP-D” as a generic data label:the copper pair, 62.5/125 multimode and 50/125 multimode rows have different optical / electrical functions and must be selected separately.Screen coverage, fibre type, bend radius, connector plan and test wavelength belong in the release documentation.
Figure 4 — schematic screened construction and TXP-D paired / fibre-optic data elements. Optical values remain type-specific.

Screening, paired data and fibre-optic options

Screened TXP constructions add an inner PUR sheath where specified, PETP foil for contact protection, a tinned copper braid with approximately 80% coverage and polyester fleece protection. The screen is not an isolated accessory: the cable gland, cabinet entry, trolley bonding and shield continuity test must be designed with it.

TXP-D contains three different supplied data concepts: a paired copper cable marked 2X2X0,75C PN IE TP, a 12-core 62.5/125 fibre construction and a 12-core 50/125 fibre construction. The copper data row has a stated 300 V rating; the fibre rows show a dash in the copper-index field because the optical construction is not represented by a copper conductor index in the supplied matrix.

TXP-D fibre-optic technical data — values transcribed from supplied record
Fibre propertySinglemode E9/125Multimode 50/125Multimode 62.5/125
Maximum attenuation at 850 nm—3.0 dB/km3.5 dB/km
Maximum attenuation at 1300 nm0.5 dB/km1.0 dB/km1.5 dB/km
Maximum attenuation at 1550 nm0.3 dB/km——
Numerical aperture ±0.02—0.20.27
Bandwidth at 850 nm—400 MHz200 MHz
Bandwidth at 1300 nm—1500 MHz600 MHz
Optical RFQ point. Specify fibre type, core/cladding notation, required wavelengths, attenuation test method, bandwidth requirement, connector or splice plan, and whether the fibre shares the same dynamic radius as the copper cable construction. Do not replace 62.5/125 with 50/125 merely because the outer cable dimensions are the same.

Installation, inspection and failure prevention

In a fast energy-guiding system, the cable is a moving structural member as well as an electrical component. A damaged PUR sheath is often the first visible sign of a guide problem, not the original cause. A trolley that runs unevenly, a chain that twists or a clamp that carries dynamic shock can shorten the life of even a correctly specified cable.

Installation

  • Verify the exact outer-Ø range against the energy-chain cavity, guide rollers and clamp.
  • Use the applicable radius statement from the final release, not a generic value.
  • Keep the cable free of compression, sharp edges and uncontrolled twist.
  • Use end grips and strain reliefs that transfer load through the designated cable path.
  • Separate power, control, screened and fibre functions according to the system EMC and communication design.

Commissioning

  • Run the first cycles at reduced speed and observe the complete guide path.
  • Check chain fill, cable position, loop stability and return movement.
  • Verify conductor continuity, insulation resistance and screen continuity where applicable.
  • For fibre, test attenuation and continuity at the specified wavelengths.
  • Record actual speed, acceleration, ambient temperature and guide condition.

Maintenance

  • Inspect PUR for notching, cuts, flattening, glazing and local hardening.
  • Check guide rollers, chain links, separators and end clamps for damage.
  • Inspect screen braid and foil termination on screened variants.
  • Look for abnormal electrical heating or intermittent control signals.
  • Replace the cable when the sheath, insulation, screen or fibre protection has been compromised.
TXP / TXP-D field troubleshooting guide — engineering interpretation
Observed symptomLikely mechanismEngineering response
Longitudinal cut or notch in PURGuide edge, foreign body, excessive chain pressure or cable rubbingRemove the damage source; verify guide finish, fill and outer-Ø clearance
Cable twists or migrates in chainIncorrect separator, poor chain alignment or multi-axis forceRe-align the guide system and confirm the cable’s intended movement
Repeated end-grip pullAcceleration shock or underspecified strain reliefRecalculate the load path; do not transfer machine shock to the copper
Screen intermittently openBraid break, foil damage or poor terminationRepair the complete screen path and test continuity through travel
Fibre attenuation increasesMicrobending, crushing, tight bend or damaged protectionInspect radius, chain pressure, splice and optical test results
Conductor temperature highOvercurrent, grouping, poor heat dissipation or damaged conductorRecheck DIN VDE 0298-4 basis and installation derating
TXP / TXP-D RFQ logic — electrical function and mechanical life are inseparable A correct replacement is defined by the machine duty, cable family, order row, radius, environment and termination path. 1 · Machinespeed / accelerationguide or energy chaintemperature / atmosphere 2 · FamilyTXP power / controlTXP screenedTXP-D copper / fibre0.6/1 kV vs 300 V branch 3 · Order rowouter Ø min/maxCu index / weightpermitted tensile loadscreen / fibre optionconfirm radius statement 4 · Releasedrawingtestscertificatestermination plan weight / grip loadloop flexingacceleration shock Permitted tensile load is catalogue evidence, not a universal working load:design the complete cable path, end restraint, clamp, safety factor and machine acceleration.
Figure 5 — RFQ and load-path logic: the correct cable is selected only after machine duty, family, order row, radius, environment and release documents agree.

Standards, documentation and Feichun certification capability

The supplied TXP / TXP-D record references VDE 0295 for conductor class, VDE 0293-308 for conductor coding and DIN VDE 0298-4 for ampacity. It also identifies DIN EN 60811-2-1 for oil resistance, IEC 60332-1 for TXP flame retardance and IEC 60332-2-1 for TXP-D flame retardance. The final test report must identify the released compound, construction, applicable edition and test configuration.

For export projects, Feichun Cable can prepare a project-specific technical file and support the applicable certification / approval route, including ATEX, IECEx, VDE, CE, UKCA, EAC and the Russian Fire Safety Certificate. The certification scope must match the exact TXP / TXP-D construction, market, voltage branch, screen, fibre option and installation duty; a generic certificate from another product family is not a valid substitute.

Standards and certification map — documentation must follow the exact release
Reference / documentRelevanceRelease control
User-supplied TXP / TXP-D recordAll product values, construction features, order matrices, fibre properties and radius statementsPrimary source for this article; final Feichun drawing controls production
DIN VDE 0295 / IEC 60228 contextClass-5 finely stranded bare copperConfirm conductor class in the released construction
VDE 0293-308Core identification and GN/YE optionConfirm marking and protective-conductor arrangement
DIN VDE 0298-4Ampacity calculation basisCurrent rating depends on installation, grouping, ambient and duty
DIN EN 60811-2-1Oil-resistance reference supplied for TXP / TXP-DUse the applicable compound and test report
IEC 60332-1TXP flame-retardant referenceConfirm the applicable test edition
IEC 60332-2-1TXP-D flame-retardant referenceConfirm the exact data-cable construction and test
Halogen-free / RoHS statementsMaterial and environmental requirementsProvide the declaration for the released product and destination
ATEX / IECEx / VDE / CE / UKCA / EAC / Russian Fire SafetyPotential project approval routesScope depends on the final product and destination requirements

Public references used for engineering context: Conductix-Wampfler official festoon cable overview; Conductix-Wampfler cable catalogue PDF; IEC 60811-404 publication context; IEC 60332-1-2 publication context.

RFQ checklist: information that prevents the wrong TXP cable

For a reliable replacement or new-build quotation, send machine information together with the exact electrical schedule. A part number without the movement duty is not enough for a heavy-duty festoon cable.

Machine duty

  • Festoon or energy-guiding-chain arrangement
  • Horizontal or vertical travel
  • Travel speed, acceleration and braking
  • Travel length, guide length and duty cycle
  • Minimum available bend radius and cavity dimensions

Electrical function

  • TXP control, screened control, power or screened power
  • TXP-D copper pair, 62.5/125 or 50/125 fibre
  • Core count and cross-section
  • U₀/U = 0.6/1 kV or 300 V data branch
  • Screen, PE / GN/YE and termination requirements

Environment

  • Flexing and fixed ambient temperatures
  • Oil, ozone, UV, water, humidity and atmospheric corrosion
  • Steel dust, foundry heat, theatre scenery or conveyor contamination
  • Lacquer-sensitive production environment
  • Colour, print marking and traceability

Documentation

  • Exact outer Ø range, weight and copper index
  • Permitted tensile-load data and system safety factor
  • Applicable radius statement and installation category
  • 2.5 kV test report and ampacity basis
  • Screen / fibre test data and approval package

RFQ line example TXP screened power · 4 G 35C · U₀/U 0.6/1 kV · 131249-R4G35C# reference heavy-duty energy-guiding chain · travel up to 210 m/min outer Ø 29.6–31.6 mm · Cu 1.444 kg/km · weight 1.870 kg/km permitted tensile load 2.100 N · screen braid ≈80% · required length: [project value] radius basis: [TXP / TXP-D + final duty table] · termination drawing: [attach]

The example preserves the supplied 4 G 35C screened-power row, including its unusual part-number prefix. Feichun should confirm the final marking, dimensions, screen details, test evidence, certificates and accessories before production.

Feichun manufacturing position. Feichun Cable can manufacture a functionally equivalent TXP / TXP-D solution around the required 0.6/1 kV power/control schedule, 300 V data branch, PUR compound, screen architecture, paired copper or fibre-optic option and heavy-duty movement. The finished product should be released through an independent Feichun construction drawing with its own dimensional data, dynamic limits, tests, traceability and certification scope.