ALSECURE® PLUS MICA TAPE SINGLE CORE🔥 FIRE RATED
Single Core Flexible Copper Conductor | Mica Taped | 0.6/1kV | AS/NZS 3013 WS52W Circuit Integrity | 110°C
The ALSECURE® PLUS MICA TAPE SINGLE CORE represents the highest standard in fire-resistant cable technology, utilizing proven glass mica tape barrier technology to maintain circuit integrity during fire conditions. This cable is specifically engineered for critical life-safety applications where continued electrical operation during fire events is essential for emergency evacuation systems, fire suppression equipment, and essential services.[1]
The mica tape layer provides a ceramic-like barrier that maintains dielectric properties at temperatures exceeding 800°C, ensuring the cable can continue to supply power to critical circuits for a minimum of 120 minutes (2 hours) during fire conditions as verified by AS/NZS 3013 WS52W testing protocols.[2]
The WS52W classification per AS/NZS 3013 defines the fire and mechanical performance characteristics of wiring system elements. Understanding this rating is essential for specifying cables in life-safety applications.[3]
• Circuit integrity maintained for 120 minutes
• Tested at 830°C flame temperature
• Exceeds IEC 60331 requirements
• Suitable for 2-hour fire-rated systems
• Level 2: Moderate impact resistance
• W suffix: Maintains function under water spray
• Compliant with BS 6387 Category C,W,Z
• Suitable for sprinkler-protected areas
Conductor: Flexible stranded plain annealed copper, Class 5 per AS/NZS 1125. Multi-strand construction ensures optimal flexibility for installation in conduit and trunking systems.
Fire Barrier: Glass mica tape wrapped around conductor with minimum 40% overlap. Mica maintains insulating properties at temperatures exceeding 1000°C.[4]
Insulation: X-HF-110 cross-linked halogen-free polyolefin compound. Maintains dielectric stability at 110°C continuous operation with excellent thermal aging properties.
Sheath: HFS-110-TP halogen-free thermoplastic sheath providing UV resistance, oil resistance, and mechanical protection. Low smoke emission per AS/NZS 4507 RHE.
• AS/NZS 5000.1 – Electric cables
• AS/NZS 4507 – Reduced Halogen Emission (RHE)
• AS/NZS 3013 – Fire & Mechanical Performance (WS52W)
• AS/NZS 1125 – Conductor specifications
• AS/NZS 3000 – Wiring Rules compliance
• IEC 60331-21 – Fire resistance test (0.6/1kV)
• IEC 60332-1 – Single cable flame test
• IEC 61034-2 – Smoke density test
• IEC 60754-1/2 – Halogen content test
• BS 6387 – Category C, W, Z compliance
| Parameter | ALSECURE® PLUS Mica | Standard LSZH | PVC Cable |
|---|---|---|---|
| Circuit Integrity (Fire) | 120 minutes | 0 min (fails) | 0 min (fails) |
| Fire Test Temperature | 830-950°C | N/A | N/A |
| Mica Tape Barrier | Yes (glass mica) | No | No |
| Smoke Density (IEC 61034) | ≥60% transmittance | ≥60% | <20% |
| HCl Emission | <0.5% | <0.5% | up to 30% |
| Water Spray Resistance | Yes (W rated) | No | No |
| Green Star Compatible | Yes (PVC-free) | Yes | No |
Data referenced from AS/NZS 3013 and IEC 60331 testing standards.[5]
| Conductor (mm²) | Insul. (mm) | Sheath (mm) | OD (mm) | Mass (kg/100m) | Min. Bend (mm) | Max. Pull (kN) | Product Code | Status |
|---|---|---|---|---|---|---|---|---|
| 10 | 0.7 | 1.4 | 8.9 | 18 | 40 | 0.22 | PFLX01AA001 | Stock |
| 16 | 0.8 | 1.4 | 10.1 | 24 | 61 | 0.34 | PFLX02AA001 | Stock |
| 25 | 0.9 | 1.4 | 11.6 | 34 | 70 | 0.53 | PFLX03AA001 | Stock |
| 35 | 0.9 | 1.4 | 13.5 | 44 | 81 | 0.72 | PFLX04AA001 | Stock |
| 50 | 1.0 | 1.4 | 15.3 | 63 | 92 | 1.08 | PFLX05AA001 | Stock |
| 70 | 1.1 | 1.4 | 17.2 | 82 | 103 | 1.50 | PFLX06AA001 | Stock |
| 95 | 1.1 | 1.6 | 19.3 | 110 | 116 | 2.00 | PFLX07AA001 | Stock |
| 120 | 1.2 | 1.6 | 21.6 | 134 | 130 | 2.50 | PFLE87AA001 | Order |
| 150 | 1.4 | 1.6 | 23.5 | 162 | 141 | 3.10 | PFLE88AA001 | Order |
| 185 | 1.6 | 1.8 | 26.2 | 196 | 236 | 3.80 | PFLE89AA001 | Order |
| 240 | 1.7 | 1.8 | 29.1 | 254 | 262 | 5.10 | PFLE90AA001 | Order |
| 300 | 1.8 | 1.8 | 31.8 | 309 | 286 | 6.20 | PFLE91AA001 | Order |
| 400 | 2.0 | 2.0 | 35.9 | 396 | 323 | 8.10 | PFLE92AA001 | Order |
| 500 | 2.2 | 2.2 | 40.8 | 510 | 367 | 10.60 | PFLE93AA001 | Order |
| 630 | 2.4 | 2.2 | 45.0 | 646 | 405 | 13.70 | PFLE94AA001 | Order |
Made to Stock Made to Order
| Conductor (mm²) | DC Resistance @ 20°C (Ω/km) | Current Rating Free Air (A) | Voltage Drop (mV/A/m) |
|---|---|---|---|
| 10 | 1.91 | 73 | 4.7 |
| 16 | 1.21 | 98 | 2.9 |
| 25 | 0.780 | 129 | 1.9 |
| 35 | 0.554 | 158 | 1.35 |
| 50 | 0.386 | 192 | 0.93 |
| 70 | 0.272 | 245 | 0.66 |
| 95 | 0.206 | 298 | 0.49 |
| 120 | 0.161 | 346 | 0.39 |
| 150 | 0.129 | 395 | 0.31 |
| 185 | 0.106 | 450 | 0.26 |
| 240 | 0.0801 | 538 | 0.20 |
| 300 | 0.0641 | 621 | 0.16 |
| 400 | 0.0486 | 745 | 0.12 |
| 500 | 0.0384 | 868 | 0.10 |
| 630 | 0.0287 | 1005 | 0.08 |
Current ratings based on single cable in free air at 30°C ambient. Installation method corrections per AS/NZS 3008.1.1 required.
Sheath Colors (4-character codes):
Example: PFLX01AA001JBNA = 10mm² Red sheath
Installation Requirements:
• Maximum pulling tension: As per table
• Install in metal conduit or trunking for max fire rating
• Ambient temp during installation: >0°C