2-NORM TRAY TC-ER MTW: UL-listed tray cable for exposed runs, machine tools and wind turbines

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
2-NORM TRAY TC-ER MTW UL/CSA tray cable | FeiChun Cable
FEICHUN CABLE · UL LISTED TRAY CABLE

2-NORM TRAY TC-ER MTW: UL-listed tray cable for exposed runs, machine tools and wind turbines

An engineering guide to the cable that solves North American field wiring: UL listed to UL 1277 and 1063, TC-ER for exposed runs without conduit, WTTC at 1 000 V for wind turbines, MTW for machine tools per NFPA 79, FT4/IEEE bunched-cable flame rating and UL OIL RES I.

UL listed 1277/1063TC-ER (Exposed Run)MTW · NFPA 79WTTC 1 000 VAWM 1 000 V600 V TC · IEC 0.6/1 kVFT4/IEEEOIL RES IClass 1 Div. 26 kV testRoHS · CE
Document FC-ART-TCER-2026-6290Updated: 20 September 2026FeiChun Cable / 飞纯电缆
Engineer’s summary: this is the cable for NEC field wiring. Unlike AWM types (which may only be used inside equipment), TC-ER is a UL-listed cable type that may be installed in cable trays and run exposed to the machine without conduit, per NEC 336.10(7). It also carries WTTC (1 000 V for wind turbines), MTW (machine tools) and Class 1 Div. 2 listings in one construction.

1. Reading the designation

2-NORM = dual standards (UL/CSA and IEC/VDE). TRAY = tray cable per UL 1277. TC-ER = Tray Cable – Exposed Run. MTW = Machine Tool Wire per UL 1063. ‘G’ = with GNYE; ‘x’ = without.

46

Standard constructions, 2 × 1 to 4 G 120 mm² (AWG 18 to 4/0).

TC-ER

Exposed run without conduit.

1 000 V

WTTC and AWM rating.

FT4

IEEE vertical-tray flame test.

2. Construction

Cross-section 2-NORM TRAY TC-ER MTW 7 G · UL listed, oil-resistant PVC, greyEngineering-drawing style · functional, not to scale · final dimensions per approved order drawingGNYE123456Ø d = 7.9 … 49.3 mm (see tables) (see tables)1Bare Cu strand, IEC 60228 class 52PVC core insulation, black3White numerals (DIN VDE 0293)4GNYE protective conductor (from 3 cores)5Cores stranded in layers6Grey oil-resistant PVC sheath RAL 7001 (EN 50363-4-1)DocumentRevisionProjectionFC-ART-TCER-2026-6290A · 2026-091st angle
Figure 1: Construction of the 7 G version; callouts match the Pos. column of the materials table.
Materials table (Pos. = callout numbers in Figure 1)
Pos.ElementMaterial / formEngineering function
1ConductorBare Cu, fine-wire, IEC 60228 cl. 5 / UL 83Flexibility; AWG equivalents given for each size
2Core insulationPVC90 °C rating
3Core markingBlack cores with white numerals; GNYE from 3 coresDIN VDE 0293
4Protective conductorGNYE core (‘G’)‘x’ versions without
5Core assemblyStranded in layersRound geometry for connectors and glands
6Outer sheathOil-resistant PVC, grey RAL 7001UL OIL RES I; UL wet approval 75 °C; FT4/IEEE

3. Technical data

Technical data (complete)
ParameterValueEngineering note
ConductorBare copper strand, IEC 60228 class 5 / UL 83
Core insulationPVC
Core identificationAcc. to DIN VDE 0293: black cores with white numerals; G = with GNYE from 3 cores
StrandingCores stranded in layers
Outer sheathPVC (oil-resistant)
Sheath colourGrey, RAL 7001
Rated voltage600 V (TC and MTW); 1 000 V (WTTC and AWM); IEC: 0.6/1 kVMultiple voltage classes in one cable
Test voltage6 kV
Conductor resistanceAcc. to IEC 60228 cl. 5
Min. bending radius fixed4 × d
Min. bending radius moved13 × d
Operating temp. fixed−40 °C / +90 °C
Operating temp. moved−5 °C / +90 °C
Burning behaviourFlame-retardant acc. to IEC 60332-1, IEC 60332-3A and UL category FT4/IEEEBunched-cable rating: IEC 60332-3A and FT4/IEEE
Oil resistanceUL OIL RES I; acc. to UL 1277 and UL 1063Oil-resistant sheath
Water resistanceUL wet approval 75 °C
Chemical resistanceLargely resistant to acids and bases
StandardsUL 1277, UL 1063 (MTW), NEC 336.10(7) Class 1 Div. 2 per NEC Art. 336, 392, 501
ApprovalsUL listed acc. to UL 1277 and 1063; UL/CSA recognised acc. to UL 10012 and 2587
TC-ERTray Cable – Exposed Run: open wiring between cable tray and industrial machine per NEC 336.10(7)No conduit required for the exposed section
WTTCWind Turbine Tray Cable1 000 V rating for nacelle and tower wiring
MTWMachine Tool Wire, acc. to UL 1063NFPA 79 compliant for machine wiring
ComplianceRoHS; 2014/35/EU Low Voltage Directive (CE); NFPA 79 2007

4. What each listing means

Listings and their NEC / application scope
ListingStandardVoltageScopeWhy it matters
TC (Tray Cable)UL 1277600 VCable trays per NEC Art. 392Basic tray listing
TC-ER (Exposed Run)NEC 336.10(7)600 VExposed run from tray to machineNo conduit needed for the last section
MTW (Machine Tool Wire)UL 1063600 VInside machine toolsNFPA 79 compliance
WTTC (Wind Turbine Tray Cable)UL 12771 000 VWind-turbine tower and nacelleHigher voltage for turbine applications
AWM (Appliance Wiring Material)UL 10012/25871 000 VInside equipmentUL/CSA recognised
Class 1 Div. 2NEC Art. 501600 VHazardous locations (abnormal gas/vapour)No separate hazloc cable needed
IEC 0.6/1 kV—0.6/1 kVEuropean installationsDual-standard coverage

5. Full dimension and weight tables

All 46 constructions are listed, grouped by cross-section with AWG equivalents. Bending radii are calculated from the nominal outer diameter (4 × d fixed, 13 × d moved).

Cross-section 1 mm² / AWG 18 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 10 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
2 x 1 (AWG 18)TC-ER / MTW / WTTC / AWM10034027.919.287.032103
3 G 1 (AWG 18)TC-ER / MTW / WTTC / AWM10035688.328.8102.033108
3 x 1 (AWG 18)TC-ER / MTW / WTTC / AWM10054258.328.8101.333108
4 G 1 (AWG 18)TC-ER / MTW / WTTC / AWM10040699.138.4125.036118
5 G 1 (AWG 18)TC-ER / MTW / WTTC / AWM10041709.948.0150.040129
7 G 1 (AWG 18)TC-ER / MTW / WTTC / AWM100413510.867.2218.043140
12 G 1 (AWG 18)TC-ER / MTW / WTTC / AWM100413614.7115.2335.059191
18 G 1 (AWG 18)TC-ER / MTW / WTTC / AWM100413717.1172.8466.068222
25 G 1 (AWG 18)TC-ER / MTW / WTTC / AWM100413819.5240.0617.078254
34 G 1 (AWG 18)TC-ER / MTW / WTTC / AWM100485823.8326.0897.095309
Cross-section 1.5 mm² / AWG 16 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 9 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
2 x 1.5 (AWG 16)TC-ER / MTW / WTTC / AWM10041398.628.8106.034112
3 G 1.5 (AWG 16)TC-ER / MTW / WTTC / AWM10041409.143.2127.036118
4 G 1.5 (AWG 16)TC-ER / MTW / WTTC / AWM10041419.957.6155.040129
5 G 1.5 (AWG 16)TC-ER / MTW / WTTC / AWM100414210.872.0187.043140
7 G 1.5 (AWG 16)TC-ER / MTW / WTTC / AWM100414311.8100.8272.047153
8 G 1.5 (AWG 16)TC-ER / MTW / WTTC / AWM100437414.6115.2357.058190
12 G 1.5 (AWG 16)TC-ER / MTW / WTTC / AWM100414416.1172.8421.064209
18 G 1.5 (AWG 16)TC-ER / MTW / WTTC / AWM100414518.8259.2594.075244
25 G 1.5 (AWG 16)TC-ER / MTW / WTTC / AWM100414622.6360.0847.090294
Cross-section 2.5 mm² / AWG 14 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 8 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
2 x 2.5 (AWG 14)TC-ER / MTW / WTTC / AWM10041479.448.0137.038122
3 G 2.5 (AWG 14)TC-ER / MTW / WTTC / AWM10041489.972.0166.040129
4 G 2.5 (AWG 14)TC-ER / MTW / WTTC / AWM100414910.896.0205.043140
5 G 2.5 (AWG 14)TC-ER / MTW / WTTC / AWM100415011.9120.0251.048155
7 G 2.5 (AWG 14)TC-ER / MTW / WTTC / AWM100415113.0168.0393.052169
8 G 2.5 (AWG 14)TC-ER / MTW / WTTC / AWM100437516.0192.0489.064208
12 G 2.5 (AWG 14)TC-ER / MTW / WTTC / AWM100415217.7288.0568.071230
18 G 2.5 (AWG 14)TC-ER / MTW / WTTC / AWM100415320.8432.0807.083270
Cross-section 4 mm² / AWG 12 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 4 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
3 G 4 (AWG 12)TC-ER / MTW / WTTC / AWM100415411.3115.2231.045147
4 G 4 (AWG 12)TC-ER / MTW / WTTC / AWM100415512.4153.6290.050161
5 G 4 (AWG 12)TC-ER / MTW / WTTC / AWM100415614.4192.0379.058187
7 G 4 (AWG 12)TC-ER / MTW / WTTC / AWM100415715.7268.8550.063204
Cross-section 6 mm² / AWG 10 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 3 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
3 G 6 (AWG 10)TC-ER / MTW / WTTC / AWM100416712.5172.8307.050162
4 G 6 (AWG 10)TC-ER / MTW / WTTC / AWM100415814.5230.4410.058188
5 G 6 (AWG 10)TC-ER / MTW / WTTC / AWM100415915.9288.0501.064207
Cross-section 10 mm² / AWG 8 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 3 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
3 G 10 (AWG 8)TC-ER / MTW / WTTC / AWM100416817.0288.0543.068221
4 G 10 (AWG 8)TC-ER / MTW / WTTC / AWM100416018.6384.0679.074242
5 G 10 (AWG 8)TC-ER / MTW / WTTC / AWM100416120.6480.0840.082268
Cross-section 16 mm² / AWG 6 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 3 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
3 G 16 (AWG 6)TC-ER / MTW / WTTC / AWM100416920.7460.8833.083269
4 G 16 (AWG 6)TC-ER / MTW / WTTC / AWM100416223.8614.41,109.095309
5 G 16 (AWG 6)TC-ER / MTW / WTTC / AWM100416326.3768.01,362.0105342
Cross-section 25 mm² / AWG 4 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
4 G 25 (AWG 4)TC-ER / MTW / WTTC / AWM100416427.3960.01,569.0109355
Cross-section 35 mm² / AWG 2 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
4 G 35 (AWG 2)TC-ER / MTW / WTTC / AWM100416530.21,344.02,041.0121393
Cross-section 50 mm² / AWG 1 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
4 G 50 (AWG 1)TC-ER / MTW / WTTC / AWM100416636.71,920.02,967.0147477
Cross-section 70 mm² / AWG 2/0 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
4 G 70 (AWG 2/0)TC-ER / MTW / WTTC / AWM100516641.72,688.03,971.0167542
Cross-section 95 mm² / AWG 3/0 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
4 G 95 (AWG 3/0)TC-ER / MTW / WTTC / AWM100542746.73,648.05,198.0187607
Cross-section 120 mm² / AWG 4/0 · TC-ER 600 V · MTW 600 V · WTTC 1 000 V · AWM 1 000 V · 1 constructions
Dimension n × mm²VersionReference item no.Outer Ø mmCu index kg/kmWeight kg/kmMin. bend fixed 4 × d mmMin. bend moved 13 × d mm
4 G 120 (AWG 4/0)TC-ER / MTW / WTTC / AWM100585849.34,608.06,169.0197641

6. Application envelope

Oil-resistant power and control cable for cable trays and cable channels, for machines and equipment destined for the North American market. For medium mechanical stress, for fixed and flexible applications with free movement without tensile stress and without forced guidance. Suitable for dry, damp and wet interiors including water-oil mixtures. TC-ER approval for open wiring between cable tray and industrial machine per NEC 336.10(7).

Application envelope of 2-NORM TRAY TC-ER MTW ✔ Machine tools (MTW), NFPA 79 Wind turbines (WTTC), machine tools (MTW) ✔ Cable trays, exposed runs (TC-ER) Free movement ≥ 12.5 × d, above −5 °C ✘ Not designed for • Drag chains / forced guidance• Tensile load, reels, festoons• Direct burial• Outdoors without UV protection• Flexing below −5 °C / EMC circuits For EMC choose a screened type;for chains a PUR/TPE chain cable. Suitable for dry, humid and wet rooms. TC-ER allows exposed runs between tray and machine per NEC 336.10(7); Class 1 Div. 2.
Figure 2: Permitted duties and exclusions.

7. Comparison

2-NORM TRAY TC-ER MTW compared with other cable types
TypeApprovalsVoltageFireNEC field-wiring scope
MULTINORM H05VV5-FHAR + UL + CSA (AWM)300/500 V · 600 VIEC 60332-1, VW-1, FT1AWM only (equipment internal)
2-NORM 1 000 V UL/CSAcURus + VDE-Reg.300/500 V · 1 000 VIEC 60332-3-24 Cat. C, VW-1, FT1AWM / equipment wiring
2-NORM TRAY TC-ER MTWUL listed (1277/1063) + UL/CSA recognised600 V · 1 000 V · IEC 0.6/1 kVIEC 60332-3A, FT4/IEEEField wiring: trays, exposed runs, Class 1 Div. 2
UL TC-ER (generic)UL listed600 VFT4NEC field wiring

8. Design calculations

Ampacity: NEC Table 310.15(B)(16) for 90 °C column, derated for conduit fill and ambient For TC in tray: NEC 392.80 or UL 1277 tables Machine tools: NFPA 79 ampacity basis Short-circuit (PVC, Cu): I_k ≈ 115 × S / √t e.g. 4 G 120, t = 0.5 s → ≈ 19.5 kA Voltage drop: ΔU = √3 × I × L × (R cosφ + X sinφ) Bending: fixed R ≥ 4 × d · moved R ≥ 13 × d e.g. 25 G 1.5 (d = 22.6 mm): 90 mm / 294 mm Exposed run (TC-ER): max. 15 m from tray to machine per typical AHJ practice; confirm with local inspector

9. Certification and traceability

This cable is UL listed to UL 1277 and UL 1063, UL/CSA recognised to UL 10012 and 2587, and listed for NEC 336.10(7) Class 1 Div. 2 per NEC Articles 336, 392 and 501. It is RoHS-conform, CE-conform to the 2014/35/EU Low Voltage Directive and conforms to NFPA 79 2007 wiring norms. FeiChun Cable holds a complete export certification portfolio — including CE, UKCA, VDE, EAC, ATEX and IECEx — and every certificate supplied is checked against the exact type, voltage, factory and standard of the order.

Routine tests

Conductor resistance, 6 kV voltage test, dimensions, UL surface marking.

Type tests

FT4/IEEE vertical-tray flame, IEC 60332-3A bunched, UL OIL RES I oil immersion, UL wet 75 °C.

Delivery documents

Approved datasheet, test report per drum, UL listing marks (TC-ER, MTW, WTTC), batch number and length marking.

10. FAQ

What does TC-ER mean?

Tray Cable – Exposed Run. Under NEC 336.10(7) it may be run exposed (without conduit) between the cable tray and the industrial machine or equipment it serves. This eliminates the conduit or armour otherwise required for the exposed section.

TC-ER versus AWM — what is the difference?

AWM (Appliance Wiring Material) is for wiring inside equipment only. TC-ER is a listed cable type for field wiring in cable trays and the exposed run to the machine. If the NEC or the local authority requires a listed tray cable, AWM is not sufficient.

What is WTTC?

Wind Turbine Tray Cable — a 1 000 V tray-cable rating for wiring inside wind-turbine towers and nacelles. The cable also carries the standard 600 V TC rating.

What is MTW?

Machine Tool Wire, listed to UL 1063. It confirms the cable is suitable for wiring inside machine tools per NFPA 79 (Electrical Standard for Industrial Machinery).

Can it be used in Class 1 Division 2?

Yes. It is listed for NEC 336.10(7) Class 1 Div. 2 per NEC Articles 336, 392 and 501 — hazardous locations where ignitable concentrations of flammable gases or vapours exist only under abnormal conditions.

Is it oil-resistant?

Yes: UL OIL RES I per UL 1277 and UL 1063, and water-resistant with UL wet approval at 75 °C. The sheath is also largely resistant to acids and bases.

Does it need a screen?

This cable is unscreened. For EMC-critical circuits, combine with a screened type or add external screening at the installation.

FeiChun Cable / 飞纯电缆
Technical and project enquiries: [email protected]
Manufacturing in China, export support
+86 13855123218
FEICHUN CABLE

UL-listed tray cable: TC-ER, MTW, WTTC and Class 1 Div. 2 in one construction

For machines, wind turbines, trays and exposed runs on the North American market.

[email protected]

+86 13855123218

Document FC-ART-TCER-2026-6290. Final values are governed by the approved datasheet, order drawing, batch test reports and certificate scope.