(N)TSCGH3S-LED 6/10 kV 

FeiChun® High-Voltage Luminescent MV Trailing Cable with No External Inverter: The Complete VDE 0250-813 Guide for 10 kV Shovels & Draglines

Reeling & Trailing Cables for Cranes & Mining — Feichun Special Cable Blogs
(N)TSCGH3S-LED 6/10 kV FeiChun Luminescent MV Trailing Cable — VDE 0250-813 | 6/10 kV 17 kV Test | No External Inverter | FC-EMH™ Self-Powered LED | Halogen Free | −50 °C | High-Voltage Shovels & Draglines | TENAX-LUMEN Alternative — FeiChun Cable
FeiChun® | VDE 0250-813 | 6/10 kV Luminescent Trailing Cable | No Inverter | Halogen Free | TENAX-LUMEN 10 kV Alternative

(N)TSCGH3S-LED 6/10 kV — FeiChun® High-Voltage Luminescent MV Trailing Cable with No External Inverter: The Complete VDE 0250-813 Guide for 10 kV Shovels & Draglines

10 Part Numbers · 3×35 mm² to 3×240 mm² · Rated 6/10 (12) kV · Test Voltage 17 kV · FC-EMH™ Self-Powered · No AC/AC Inverter · Halogen Free IEC 60754-2 · Cold Flexible −50 °C · 360° Illumination · Live/Dead Indication · GOST-R Certified · TENAX-LUMEN 10 kV Alternative
Manufacturer’s technical guide: (N)TSCGH3S-LED 6/10 kV — the VDE 0250-813 luminescent trailing cable for high-voltage electric rope shovels and draglines. Rated 6/10 kV, tested at 17 kV. FC-EMH™ harvests energy from the 10 kV field — no inverter, no external wiring. FC-LED™ strips in outer interstices replace EL phosphor wire. Glows red when energised. Dark when isolated. Zero maintenance. Direct factory manufacturer.
Anhui Feichun Special Cable Co., Ltd. | Published: March 2026 | Read time: ~20 min | Doc. Ref: FC-TDS-TSCGH3S-10KV-LED-2026-F28A6DBB

⚡ Why 6/10 kV? The High-Voltage Case for Larger Shovels & Draglines

Not every electric rope shovel or walking dragline runs on 3.6/6 kV. The world’s largest open-cut mining machines — shovels with dipper capacities above 40 cubic metres, draglines with boom lengths exceeding 90 metres, and high-capacity bucket wheel excavators — frequently operate on 6/10 kV supply systems. The reason is straightforward electrical engineering: for equivalent mechanical power output, a 10 kV supply draws approximately 60% of the current that a 6 kV supply requires. Lower current means smaller conductor cross-sections for the same power delivery, reduced resistive losses over long trailing cable runs, and the ability to extend the reach of mobile equipment further from the mine’s fixed switchgear without unacceptable voltage drop.

In the mining regions where the largest shovels and draglines operate — the open lignite pits of Germany and Eastern Europe, the brown coal basins of Kazakhstan, the iron ore and coal operations of Russia’s eastern fields, and the hard rock mines of Central Asia — the mine distribution voltage is frequently 6/10 kV as a system standard, not as a single-machine exception. For these operations, 3.6/6 kV trailing cables are simply not the right specification: the cable’s insulation system must be rated for the higher voltage class, and the cable’s performance parameters — test voltage, capacitance, inductance — must reflect the thicker insulation wall required at 6/10 kV.

FeiChun’s (N)TSCGH3S-LED 6/10 kV is the purpose-built answer for these applications. It delivers the same FC-EMH™ self-powered LED technology, the same FC-TPU™ X-Series transparent sheath, the same halogen-free IEC 60754-2 compliance, and the same inverter-free plug-and-play installation — in a cable designed and certified to DIN VDE 0250-813 at 6/10 (12) kV rated voltage with 17 kV test voltage.

⭐ The 10 kV Advantage in the FC-EMH™ Context

One technical consequence of the higher operating voltage is directly beneficial to the FC-EMH™ induction harvesting system. At 6/10 kV, the phase conductors generate a stronger electromagnetic field per unit current than at 3.6/6 kV — because the higher voltage means the same mechanical load is driven with lower current, and the FC-EMH™ coil’s coupling with the field is enhanced at the higher voltage-to-current ratio. In practice, the FC-EMH™ system in the 6/10 kV cable variant operates with a larger harvesting margin than the 3.6/6 kV version at equivalent mechanical load — providing even more reliable LED activation at partial-load and standby conditions typical of large shovels during non-cutting cycles.

🔍 6/10 kV vs 3.6/6 kV: Key Differences in the LED Trailing Cable Family

FeiChun’s (N)TSCGH3S-LED is available in two voltage classes: 3.6/6 kV (document FC-TDS-TSCGH3S-LED-2026-68645ACD) and 6/10 kV (this document, FC-TDS-TSCGH3S-10KV-LED-2026-F28A6DBB). Both variants share the same FC-EMH™ module, FC-LED™ strip architecture, FC-ASB™ aramid stress-relief braid, FC-SPM™ surge protection, and FC-TPU™ X-Series sheath. The differences arise entirely from the insulation system requirements of the higher voltage class.

(N)TSCGH3S-LED — 6/10 kV vs 3.6/6 kV: Key Parameter Differences
Parameter(N)TSCGH3S-LED 6/10 kV (This Document)(N)TSCGH3S-LED 3.6/6 kV
Rated Voltage U₀/U6/10 (12) kV3,6/6 (7,2) kV
Test Voltage17 kV11 kV
Maximum System Voltage Um12 kV7.2 kV
EPR Insulation WallThicker — per VDE 0250-813 at 6/10 kVStandard — per VDE 0250-813 at 3.6/6 kV
CapacitanceLower nF/km (larger insulation radius)Higher nF/km (smaller insulation radius)
Overall Cable DiameterSlightly larger for same conductor cross-sectionSlightly smaller for same conductor cross-section
Part Number FormatFC-TSCGH10-LED###FC-TSCGH-LED-###
LED TechnologyFC-EMH™ — identicalFC-EMH™ — identical
SheathFC-TPU™ X-Series — identicalFC-TPU™ X-Series — identical
Cold-Start Temperature−50 °C — identical−50 °C — identical
Halogen FreeYes, IEC 60754-2 — identicalYes, IEC 60754-2 — identical
GOST-R CertificationYes — identicalYes — identical
Primary MarketsGermany, Eastern Europe, Russia, Kazakhstan, CIS 10 kV mine systems; large-class shovels and draglinesGeneral VDE/GOST-R markets; 6 kV mine systems; standard-class shovels and draglines
🔵 Specifying the Right Voltage Class: 6/10 kV or 3.6/6 kV?

The selection is straightforward: match the cable’s rated voltage class to your mine’s nominal supply voltage. If your shovel or dragline is supplied from a 6 kV system (line-to-line voltage 6 kV, line-to-earth voltage approximately 3.5 kV), specify the 3.6/6 kV variant. If your machine is supplied from a 10 kV system (line-to-line voltage 10 kV, line-to-earth voltage approximately 5.8 kV), specify the 6/10 kV variant. Using a 3.6/6 kV cable on a 10 kV system is a serious insulation over-stress condition — the cable’s insulation is rated for a maximum system voltage (Um) of 7.2 kV, which is exceeded on a 10 kV system. If in doubt, contact [email protected] with your system voltage and equipment details for a confirmed specification.

🔬 FC-EMH™ vs EL-String vs TENAX-LUMEN 10 kV: Full Technology Comparison

EL-string luminescent cables — including TENAX-LUMEN — are available in the 6/10 kV voltage class, carrying the same external inverter dependency that characterises all EL-string technology regardless of voltage rating. The inverter requirement is not a function of the cable’s voltage class: it is a fundamental characteristic of EL phosphor wire technology. A TENAX-LUMEN 10 kV cable requires the same 130 V AC, 800–1300 Hz external inverter as a TENAX-LUMEN 6 kV cable — nothing about the higher voltage class eliminates or reduces the inverter burden.

Equally, the critical live/dead indication failure of EL-string technology applies at 10 kV just as it does at 6 kV — and the safety consequences are more severe. A 10 kV cable carries approximately 67% higher phase-to-earth voltage than a 6 kV cable. Contact with an energised 10 kV trailing cable is immediately and certainly fatal. The inability of an EL-string cable to distinguish between an energised 10 kV cable and an isolated one is not a technical footnote at this voltage — it is a life-safety failure mode.

(N)TSCGH3S-LED 6/10 kV — FC-EMH™ vs EL-String (TENAX-LUMEN 10 kV & Equivalents)
ParameterFeiChun® FC-EMH™ LED — (N)TSCGH3S-LED 6/10 kVEL-String 10 kV — TENAX-LUMEN & Equivalents
External Power SupplyNONE — Self-powered. FC-EMH™ harvests from 6/10 kV field.Required: AC/AC inverter, 130 V AC, 800–1300 Hz. Mandatory at each termination.
Inverter RequiredNo inverter. At any voltage class.Yes — mandatory at 6 kV and 10 kV alike.
Live / Dead Indication at 10 kV✅ YES — LED on = cable live at 10 kV. LED off = de-energised. Critical at 10 kV where contact is immediately fatal.❌ NO — EL wire glows from inverter regardless of whether 10 kV conductors are energised or isolated.
InstallationPlug-and-play. Disconnect, connect, energise, glow. Zero wiring changes.Inverter installation, dedicated HV-rated wiring, electrical commissioning. Same burden at 10 kV as at 6 kV.
External Current DrawZero.~15 A/km from external supply.
LED Service Life50,000+ hours. No brightness degradation.10,000–15,000 hours. Significant phosphor fading. Progressive dimming.
MaintenanceZero — FC-SPM™ PTC auto-reset.Inverter periodic maintenance, component replacement, end-of-life inverter replacement.
Cold Operation−50 °C cold-start. FC-EMH™ X-variant and FC-SPM™ fully cold-rated.Inverter-dependent — most commercial inverters not specified below −20 to −30 °C.
Halogen FreeYes — IEC 60754-2. FC-TPU™ X-Series PUR sheath.Varies by manufacturer and sheath specification.
Points of FailureOne: the cable.Two: the cable + the inverter.
⚠️ Live/Dead Indication Is More Critical at 10 kV — Not Less

At 6/10 kV, the phase-to-earth voltage on a fully energised conductor is approximately 5.8 kV. Inadvertent contact with an energised 10 kV conductor — whether by a ground worker, haul truck tyre, or dozer blade — results in immediately fatal electrical arc flash. A cable that glows regardless of its energisation status (any EL-string product including TENAX-LUMEN) provides no warning to a person approaching what appears to be an active cable during an isolation window. The (N)TSCGH3S-LED goes dark when isolated — providing the correct visual indication that the cable is safe to approach. At 10 kV, this live/dead distinction is not a feature. It is a fatality-prevention mechanism.

🔧 Cable Construction: Layer-by-Layer Breakdown at 6/10 kV

The (N)TSCGH3S-LED 6/10 kV is built on the established (N)TSCGH3S platform at the higher voltage class — identical core construction to the 3.6/6 kV variant, with the insulation system specified for the 6/10 kV service requirement per DIN VDE 0250-813.

✅ (N)TSCGH3S-LED 6/10 kV Construction — Inside → Out

1. Conductors: Finely stranded tinned copper, Class 5, per DIN EN 60228 / IEC 60228 / VDE 0295. Phase conductors from 35 mm² to 240 mm². PE conductors Class 5 with semi-conductive special rubber. Tinned conductors provide corrosion resistance in the open-pit environment.

2. Inner SC Layer: Semi-conductive EPR over each phase conductor. At 6/10 kV, uniform electric field distribution and partial discharge suppression at the conductor surface are critical — any field concentration at the conductor can initiate insulation degradation over time. The inner SC layer provides the smooth equipotential surface required for reliable long-service EPR insulation performance.

3. Insulation: EPR rubber, compound 3GI3 — specified to the 6/10 kV wall thickness per DIN VDE 0250-813. The thicker insulation wall compared to the 3.6/6 kV version is the primary structural difference between the two voltage classes. EPR at 6/10 kV must withstand the 17 kV factory test without breakdown and the 10 kV maximum system voltage continuously throughout the cable’s service life in trailing and reeling duty. Compound 3GI3 EPR’s superior moisture-treeing resistance is particularly significant at 6/10 kV: water treeing in wet mine environments is a primary degradation mechanism for MV cable insulation, and EPR’s resistance to this failure mode is a key reason VDE 0250-813 specifies EPR for trailing cable applications.

4. Outer SC Layer: Semi-conductive NBR, easy-strip. Enables consistent site termination and jointing at 10 kV without requiring specialised tooling — important for mine maintenance crews working in the field without workshop facilities.

5. Pilot Conductor: Tinned copper Class 5, EPR insulated. Pilot continuity monitoring provides an additional safety channel for earth-leakage protection relay operation on the machine or the switchgear.

6. Core Arrangement & Central Filler: Cores laid around a semi-conductive central filler with aramid yarns. The aramid yarn tensile reinforcement is sized for the maximum tensile load of the heaviest construction (3×240 mm² — 18,000 N). The FC-EMH™ module is integrated in the central filler zone.

7. FC-EMH™ Module: FeiChun® proprietary electromagnetic induction pickup, integrated in the central filler zone. At 6/10 kV, the phase conductors generate a proportionally stronger electromagnetic field contribution, providing the FC-EMH™ coil with a robust harvesting environment across the full load range from standby to full rated current. Galvanically isolated from all 10 kV conductors. Cold-start to −50 °C.

8. FC-LED™ Strips in Outer Interstices: High-intensity LED strips, warning red (620–630 nm), in the outer interstices. FC-ASB™ aramid stress-relief braid protects the LED FPC circuits. 360° radial illumination with light homogeneity >95%.

9. Outer Sheath: Transparent FR-PUR — FC-TPU™ X-Series (Formula FC-2026-TPU-X5). Cold-flexible to −50 °C. Halogen free IEC 60754-2. LED-transmissive at 620–630 nm. 3–5× abrasion resistance versus conventional mining elastomers.

💡 FC-LED™ in Outer Interstices: 360° Illumination at 10 kV — Why Live/Dead Indication Matters More at Higher Voltage

The FC-LED™ strip placement in the outer interstices of the cable cross-section — and the resulting 360° illumination with >95% light homogeneity — is the same architecture as the 3.6/6 kV version. What changes at 6/10 kV is the operational significance of the live/dead indication that the FC-EMH™ system provides.

At 3.6/6 kV, contact with an energised conductor is extremely dangerous. At 6/10 kV, it is immediately and certainly fatal — the arc flash energy at 10 kV is approximately three times higher than at 6 kV for equivalent fault impedance. The required approach distance for electrical safety increases significantly. And the consequence of a worker misjudging whether a cable is isolated — because it appears to glow from an EL-string inverter whether energised or not — becomes more severe at 10 kV than at 6 kV.

The FC-EMH™ system’s live/dead indication — cable glowing = energised at 10 kV, cable dark = isolated — provides exactly the correct visual cue for isolation safety at the voltage class where that cue matters most. No EL-string product, including TENAX-LUMEN 10 kV, can provide this indication. They glow at 10 kV and they glow at zero volts, identically, because the inverter doesn’t know or care about the MV conductor status.

🛡️ FC-SPM™ Four-Layer Surge Protection: Cold-Rated to −50 °C at 10 kV

The electromagnetic transient environment of a large 10 kV electric rope shovel or dragline is more severe than that of a 6 kV machine — not because the machine is necessarily larger, but because 10 kV motor starts and 10 kV drive switching events generate proportionally higher voltage transients that can couple into the cable’s electromagnetic field and reach the FC-EMH™ module. The FC-SPM™ four-layer protection chain in the 6/10 kV variant is rated to handle this environment, with all components cold-rated to −50 °C.

(N)TSCGH3S-LED 6/10 kV — FC-SPM™ Protection Architecture (Cold-Rated −50 °C)
LayerComponentFunction10 kV Application Context
1Magnetic Saturation CapsCaps harvestable energy at source — prevents destructive energy levels reaching downstream electronics regardless of load current or transient magnitudeLarge 10 kV motor starts on high-capacity shovels/draglines generate high-energy transients. Layer 1 is the first barrier at source.
2TVS Diodes (Cold-rated −50 °C)Picosecond-response voltage spike clamping. Absorbs transient energy before it reaches regulation stages.10 kV drive rectifier switching and motor inrush transients produce higher voltage spike amplitudes than 6 kV systems. TVS clamping threshold is sized accordingly.
3Zener / LDO (Cold-rated −50 °C)Stable 12/24 V DC to LED circuit across full load range — shovel standby to full 10 kV rated cutting load.At 10 kV, the harvested voltage varies across a wider range with load — the LDO provides tight regulation throughout the duty cycle.
4PTC Resettable FuseAuto-reset overcurrent protection. No fuse replacement. No manual reset. Self-recovery after fault clearance.Essential for 10 kV cables where cable interior access along the run is impractical. Auto-reset maintains LED illumination after transient events without maintenance intervention.

🧊 FC-TPU™ X-Series Transparent PUR Sheath: Halogen Free & Cold Flexible

The FC-TPU™ X-Series outer sheath is identical between the 3.6/6 kV and 6/10 kV variants — its performance properties are independent of the cable’s voltage class, as the sheath does not participate in the cable’s insulation system. All properties described apply equally to the 6/10 kV cable.

FC-TPU™ X-Series — Key Properties for 6/10 kV Trailing Cable Service
PropertyFC-TPU™ X-SeriesStandard Black TPUPCP / CSP Mining Grade
Optical TransparencyLED-transmissive — warning red 620–630 nmOpaque blackOpaque black
Cold Flexibility−50 °C−30 to −40 °C−25 to −35 °C
Halogen FreeYes — IEC 60754-2VariesNo — HCl on combustion
Flame RetardancyDIN EN 60332-1-2 / IEC 60332-1-2FRFR
Abrasion Resistance3–5× standard mining elastomer2–3×1× baseline
Oil / Ozone / UVResistant / Resistant / ResistantResistant / Resistant / ResistantResistant / Resistant / Moderate
Fire Gas ToxicityLow — halogen freeVariesHigh — HCl and dioxins

📐 Dimensional & Physical Data: All 10 Part Numbers

The (N)TSCGH3S-LED 6/10 kV is available in 10 standard constructions. The part number format for this voltage class is FC-TSCGH10-LED### — note the “10” designation distinguishing this series from the 3.6/6 kV FC-TSCGH-LED-### series. Two constructions feature the T-suffix (3×50+3×25/3 and 3×70+3×35/3), indicating a three-core protective earth arrangement rather than the standard two-PE-plus-pilot configuration.

(N)TSCGH3S-LED 6/10 kV — Dimensional & Physical Data (All 10 Part Numbers, FC-TSCGH10 Series)
ConstructionPart NumberCond. Dia. mmCable Dia. Min mmCable Dia. Max mmWeight kg/kmLED Power
3×35+2×16+1×16FC-TSCGH10-LED0357.550.555.03 786FC-EMH™
3×50+2×16+1×16FC-TSCGH10-LED050954.058.54 424FC-EMH™
3×70+2×25+1×16FC-TSCGH10-LED07010.658.563.05 432FC-EMH™
3×95+2×25+1×16FC-TSCGH10-LED09512.662.567.06 384FC-EMH™
3×120+2×35+1×16FC-TSCGH10-LED12014.867.572.07 830FC-EMH™
3×150+2×35+1×16FC-TSCGH10-LED1501672.076.58 736FC-EMH™
3×185+2×50+1×16FC-TSCGH10-LED18517.779.584.011 200FC-EMH™
3×240+2×70+1×16FC-TSCGH10-LED24020.384.589.014 000FC-EMH™
3×50+3×25/3FC-TSCGH10-LED050T954.058.54 368FC-EMH™
3×70+3×35/3FC-TSCGH10-LED070T10.658.563.05 376FC-EMH™
📌 T-Suffix Constructions: Three-Core PE Arrangement

The FC-TSCGH10-LED050T and FC-TSCGH10-LED070T constructions (designated with the T-suffix) feature a three-core symmetrical PE arrangement (3×25/3 and 3×35/3 respectively) rather than the standard two-PE-plus-pilot layout. This construction type is specified for machines where the earth circuit design requires three symmetrical earth conductors — common in certain European and CIS switchgear configurations. Confirm your machine’s earth circuit requirement before selecting between the standard and T-suffix variants. Contact [email protected] for selection guidance.

⚙️ Electrical & Mechanical Data: 6/10 kV Values

The thicker EPR insulation required at 6/10 kV compared to 3.6/6 kV results in measurably lower capacitance per km for equivalent conductor cross-sections — a consequence of the increased radial separation between the conductor and the outer SC layer. Inductance and conductor resistance values are essentially unchanged.

(N)TSCGH3S-LED 6/10 kV — Electrical & Mechanical Data (VDE 0298-4 Current Capacity at Surface, 30 °C)
ConstructionMax. Tensile NCapacitance nF/kmInductance mH/kmResistance 20°C Ω/kmCurrent Cap. A
3×35+2×16+1×162 6252400.350.565162
3×50+2×16+1×163 7502700.330.393202
3×70+2×25+1×165 2503100.310.277250
3×95+2×25+1×167 1253400.300.210301
3×120+2×35+1×169 0003800.290.164352
3×150+2×35+1×1611 2504100.280.132404
3×185+2×50+1×1613 8754400.270.108461
3×240+2×70+1×1618 0004900.260.0817540
3×50+3×25/33 7502700.330.393202
3×70+3×35/35 2503100.310.277250

Current capacity per VDE 0298-4, Table 15, surface installation at 30 °C ambient. The LED system does not affect any electrical parameter — capacitance, inductance, resistance, and current capacity values are identical to the equivalent standard (N)TSCGH3S 6/10 kV construction.

📋 Standards, Certifications & Operating Parameters

(N)TSCGH3S-LED 6/10 kV — Complete Standards, Certifications & Operating Parameters
ParameterSpecification
Cable StandardBased on DIN VDE 0250-813
ConductorsDIN EN 60228 / IEC 60228 / VDE 0295
Flame RetardancyDIN EN 60332-1-2 / IEC 60332-1-2
Halogen FreeYes — IEC 60754-2 compliant
CertificationsGOST-R / GOST-K / GOST-B + Fire Certificate
Rated Voltage U₀/U6/10 (12) kV
Maximum System Voltage Um12 kV
Test Voltage17 kV
Conductor Temperature90 °C continuous; 250 °C short-circuit (5 sec)
Ambient — Fixed−50 °C to +80 °C
Ambient — Flexible−50 °C to +60 °C
Bending Radius — Fixed6×D
Bending Radius — Flexible10×D
Bending Radius — S-type Reeling20×D
Oil / Ozone / UVResistant / Resistant / Resistant
LED WavelengthWarning Red 620–630 nm
LED Strip PositionOuter interstices — 360° radial. Homogeneity >95%.
LED Power SourceFC-EMH™ EM induction — No external inverter. No external DC.
External Current DrawZero — entirely self-powered
LED Cold-Start Temperature−50 °C (FC-EMH™ X-variant cold-rated)
LED Service Life50,000+ hours. No progressive dimming.
Live/Dead Indication✅ YES — LED on = 10 kV energised; LED off = de-energised
Surge ProtectionFC-SPM™ 4-layer (Mag. Sat. Caps → TVS −50°C → Zener/LDO −50°C → PTC auto-reset)
Outer SheathFC-TPU™ X-Series Transparent PUR — halogen free IEC 60754-2, cold flex −50 °C
Part Number FormatFC-TSCGH10-LED### (note “10” voltage class designator)

🏆 Eight Key Operational Advantages vs EL-String & TENAX-LUMEN 10 kV

1. No External Inverter — At 10 kV as at 6 kV

The inverter burden of EL-string technology does not diminish at 10 kV — it is present at every voltage class, on every installation, for the life of every EL-string luminescent cable. The (N)TSCGH3S-LED 6/10 kV eliminates the inverter permanently, as completely as the 3.6/6 kV variant does. For 10 kV mine operations running large fleets of shovels and draglines, the aggregate inverter cost across the fleet and across the mine’s life is substantial. The (N)TSCGH3S-LED replaces it with zero ongoing cost beyond the cable itself.

2. Live/Dead Indication at 10 kV — The Safety Case Is Stronger, Not Weaker

At 10 kV, the consequence of approaching a live cable under the false impression it is isolated — a misimpression that any EL-string cable actively creates — is more severe than at 6 kV. The (N)TSCGH3S-LED’s FC-EMH™ live/dead indication is not just a safety feature at 10 kV. It is the single most important safety differentiation between a cable that can prevent a fatality and one that cannot.

3. Correct Specification for 10 kV Mine Systems

Specifying a 3.6/6 kV cable on a 10 kV system is a regulatory and safety violation — the cable’s insulation is inadequate for the operating voltage. The (N)TSCGH3S-LED 6/10 kV is the correct specification for 10 kV systems, carrying the correct insulation wall, the correct test voltage (17 kV), and the correct VDE 0250-813 certification for the 6/10 kV voltage class. There is no guesswork and no concession on the electrical rating.

4. GOST-R Certification for 10 kV Russian and Kazakh Markets

The (N)TSCGH3S-LED 6/10 kV holds GOST-R/-K/-B certification alongside its VDE 0250-813 certification. Russia and Kazakhstan operate large open-cut mining operations — Kuzbass coal, Ekibastuz coal, Sokolovsko-Sarbaiskoe iron ore, and others — predominantly on 6/10 kV mine distribution systems. A cable with dual VDE and GOST-R certification at 6/10 kV is directly applicable to these major markets in a single product.

5. Cold-Start LED Activation at −50 °C — Critical for Siberian and Kazakh Operations

The open-cut mines of Russia’s Kemerovo Oblast, Krasnoyarsk Krai, and northern Kazakhstan regularly experience winter ambient temperatures below −40 °C. Standard commercial inverters for EL-string cables are not rated for this. The FC-EMH™ X-variant’s cold-rated capacitors and LDO regulators activate the LED system reliably from −50 °C — including cold-start on first energisation of the winter season.

6. Superior LED Brightness and 50,000+ Hour Service Life

FC-LED™ strips deliver higher luminous intensity than EL phosphor wire and maintain consistent brightness throughout their 50,000+ hour service life. A TENAX-LUMEN 10 kV cable progressively dims over its first 10,000–15,000 hours — the same performance limitation applies at 10 kV as at any other voltage class. The (N)TSCGH3S-LED’s day-one brightness is its lifetime brightness.

7. Halogen Free — Ahead of European and CIS Regulatory Trends

IEC 60754-2 halogen-free compliance is increasingly a specification requirement in European mining markets and in progressive CIS regulatory frameworks. The FC-TPU™ X-Series sheath ensures the (N)TSCGH3S-LED 6/10 kV meets this requirement today, without requiring a future upgrade or a product change when local regulations catch up with the halogen-free direction of travel.

8. FC-TSCGH10 Part Numbers — Direct Ordering Reference for 10 kV Procurement

The FC-TSCGH10-LED part number series provides a clear, unambiguous ordering reference for 10 kV procurement. The “10” voltage class designator in the part number eliminates specification ambiguity between the 3.6/6 kV and 6/10 kV variants during procurement and when maintaining cable inventory records across a mixed-voltage mining operation.

🏗️ Application Scenarios: High-Voltage ERS, Large Draglines & 10 kV Mine Systems

Large-Class Electric Rope Shovels at 10 kV

The world’s largest electric rope shovels — Komatsu P&H 4800, Bucyrus 495HF, Marion 351-M, and equivalent machines in European, Russian, and Kazakh operations — are frequently supplied at 10 kV for the power efficiency reasons described in Section 1. The (N)TSCGH3S-LED 6/10 kV replaces the standard 10 kV trailing cable on these machines with no modifications to the machine, reel, or switchgear, providing continuous red LED illumination of the full cable route from shovel to switchgear.

Walking Draglines — Large German Lignite Operations & CIS Coal Mines

The large walking draglines operating in German open lignite mines (Hambach, Garzweiler, Nochten) and in Russian and Kazakh coal mines operate on 6/10 kV or higher voltage supply systems. The (N)TSCGH3S-LED 6/10 kV provides luminescent tail rope identification for these machines — visible to operators of the massive earthmoving fleet that shares pit space with the dragline, in dusty summer conditions and in winter darkness at operating temperatures that routinely reach −35 °C or below.

Bucket Wheel Excavators & Large Spreaders at 10 kV

The large bucket wheel excavators operating in German lignite — Thyssenkrupp TAKRAF machines with theoretical capacities exceeding 200,000 m³/day — operate on high-voltage supply systems where the cable reel cable voltage class is 6/10 kV. The (N)TSCGH3S-LED 6/10 kV, rated for 20×D S-type reeling, is directly applicable to these large-scale reeling cable applications.

TENAX-LUMEN 10 kV Retrofit — Remove the Inverters Across Your 10 kV Fleet

For operations currently running TENAX-LUMEN 10 kV or equivalent EL-string 10 kV cables with external inverters, the (N)TSCGH3S-LED 6/10 kV provides a direct retrofit path. Match your existing cable’s conductor cross-section to the appropriate FC-TSCGH10-LED part number. Replace the cable. Decommission and remove the inverter. The retrofitted system provides live/dead indication that TENAX-LUMEN cannot, superior brightness, 50,000+ hour service life, and zero inverter maintenance — across every machine in the 10 kV fleet.

❓ Frequently Asked Questions

Can the (N)TSCGH3S-LED 6/10 kV be used on a machine that was previously using TENAX-LUMEN 10 kV?

Yes. The (N)TSCGH3S-LED 6/10 kV is a direct drop-in replacement for any TENAX-LUMEN 10 kV cable of the same conductor construction. The cable terminates identically to a standard (N)TSCGH3S 6/10 kV cable. The existing inverter can be decommissioned and removed permanently. For cross-reference between TENAX-LUMEN part numbers and FeiChun FC-TSCGH10-LED part numbers, contact [email protected].

What is the difference in cable weight between the 6/10 kV and 3.6/6 kV versions?

For the same conductor cross-section, the 6/10 kV version is slightly heavier due to the thicker EPR insulation wall required at the higher voltage class. For example, the 3×95+2×25+1×16 construction weighs 6,440 kg/km in the 3.6/6 kV version (FC-TSCGH-LED-095) and 6,384 kg/km in the 6/10 kV version (FC-TSCGH10-LED095) — the difference arises from differences in overall cable geometry rather than a simple insulation wall weight addition. Full data is in Section 8 above.

Does the 17 kV test voltage affect installation or jointing requirements?

The 17 kV factory test voltage is a manufacturing and QA requirement — it does not change site installation or jointing procedures beyond what is already required for 10 kV cable work. Site terminations and joints must be made using materials and techniques rated for the 6/10 kV class. Contact [email protected] for guidance on compatible termination and jointing systems for the (N)TSCGH3S-LED 6/10 kV.

What is the LED activation behaviour at partial load — shovel at standby on 10 kV?

At 10 kV, the FC-EMH™ module operates in a more favourable electromagnetic environment than at 6 kV — the higher voltage-to-current ratio at equivalent mechanical load provides a stronger coupling between the phase conductor field and the pickup coil at standby current levels. LED activation at low load is reliable in the 6/10 kV variant. For application-specific minimum activation current data, contact [email protected].

Is the (N)TSCGH3S-LED 6/10 kV available in longer drum lengths for large dragline tail rope applications?

FeiChun manufactures the (N)TSCGH3S-LED 6/10 kV to customer-specified drum lengths. Contact [email protected] with your required length, construction, and delivery schedule for a production and lead time quotation.

🏷️ 80 High-Traffic SEO Tags — 10 kV Mine Electrical Engineers & Procurement

The following keyword groups represent the primary search terms used by mine managers, electrical engineers, procurement managers, and OEM specifiers when sourcing 10 kV luminescent trailing cables, 10 kV EL-string replacements, and inverter-free 10 kV LED mining cable solutions.

🔵 Primary Product, 10 kV & Competitive Displacement Terms

NTSCGH3S-LED 10kV · TSCGH3S-LED 10kV · N TSCGH3S LED 10kV · 10kV luminescent trailing cable · 6 10kV luminescent trailing cable VDE · 10kV LED trailing cable mine · 6 10 kV MV trailing cable LED · VDE 0250-813 10kV LED cable · DIN VDE 0250-813 10kV luminescent · no inverter 10kV LED mining cable · no external inverter 10kV trailing cable · TENAX-LUMEN 10kV · TENAX LUMEN 10kV alternative · TENAX LUMEN 10kV replacement · TENAX LUMEN 10kV equivalent · replace TENAX LUMEN 10kV · LED vs TENAX-LUMEN 10kV · EL string replacement 10kV LED cable · electroluminescent string 10kV alternative · no inverter 10kV luminescent cable · inverter-free 10kV LED mining cable · replace EL string 10kV shovel dragline · 10kV self-powered luminescent cable · FC-EMH 10kV LED trailing cable · shovel cable 10kV no inverter · dragline cable 10kV no inverter · high voltage shovel cable LED · high voltage dragline cable LED · luminescent shovel cable 10kV VDE · luminescent dragline cable 10kV VDE

✅ Technical, Engineering & Voltage-Specific Terms

6 10kV trailing cable LED · 6/10kV luminescent cable VDE 0250-813 · 17kV test voltage trailing cable · 17kV test luminescent cable mine · FC-TSCGH10-LED part number · FC-TSCGH10 cable series · FC-EMH electromagnetic harvesting 10kV · FC-LED strips 10kV outer interstices · FC-TPU X-Series 10kV transparent sheath · FC-SPM surge protection 10kV cable · FC-ASB aramid braid 10kV LED · 360 degree illumination 10kV cable · LED homogeneity 10kV trailing cable · halogen free 10kV trailing cable IEC 60754-2 · IEC 60754-2 10kV LED cable · 10kV cold flexible LED cable minus 50 · minus 50 10kV luminescent cable · cold start 10kV LED cable Arctic · 10kV transparent PUR mining cable sheath · GOST-R 10kV luminescent trailing cable · GOST-R VDE dual certified 10kV cable · 50000 hour LED 10kV mining cable · no phosphor fade 10kV mining cable · EPR insulation 10kV trailing cable · Class 5 conductor 10kV LED cable · T-suffix construction 3PE 10kV cable · 3×50 3×25 10kV LED trailing cable · 3×70 3×35 10kV LED trailing cable

⭐ Safety, Regional, Operational & Procurement Terms

live dead 10kV cable indicator mine · LOTO 10kV LED cable indicator · energised cable indicator 10kV mine · 10kV cable visibility mining LED · warning red LED 10kV cable mine · plug and play 10kV LED cable mine · zero maintenance 10kV luminescent cable · PTC auto reset 10kV LED cable mine · Russia 10kV mining cable LED luminescent · Siberia 10kV mining cable LED · Kuzbass 10kV shovel cable LED · Kazakhstan 10kV mining cable LED · Ekibastuz 10kV dragline cable · Germany lignite 10kV LED cable · German open pit 10kV luminescent cable · Eastern Europe 10kV LED trailing cable · CIS 10kV luminescent cable VDE · GOST-R 10kV LED cable Russia Kazakhstan · Nordic 10kV mining cable LED · Canada 10kV mining LED cable cold · large electric rope shovel 10kV LED · P H 4800 shovel 10kV cable LED · walking dragline 10kV cable LED · bucket wheel excavator 10kV LED cable · spreader 10kV LED cable mine · 10kV cable reel LED luminescent · 20xD S-type reeling 10kV LED cable · FeiChun 10kV luminescent cable · FeiChun NTSCGH3S 10kV · FeiChun no inverter 10kV cable · FeiChun GOST-R 10kV mining cable · direct factory 10kV luminescent cable China · LED cable 3×35 10kV shovel · LED cable 3×95 10kV dragline · LED cable 3×185 10kV trailing · LED cable 3×240 10kV mining · TENAX-LUMEN 10kV retrofit LED · eliminate inverter 10kV shovel fleet

Standards & References

  1. DIN VDE 0250-813, “Cables for power installations — Part 813: Trailing cables for rated voltages from 3.6/6 kV (Um = 7.2 kV) up to and including 18/30 kV (Um = 36 kV),” VDE Verlag, Berlin.
  2. DIN EN 60228 / IEC 60228 / VDE 0295, “Conductors of insulated cables,” IEC, Geneva; DIN Deutsches Institut für Normung, Berlin.
  3. DIN EN 60332-1-2 / IEC 60332-1-2, “Tests on electric and optical fibre cables under fire conditions — Part 1-2: Test for vertical flame propagation for a single insulated wire or cable,” IEC, Geneva.
  4. IEC 60754-2, “Test on gases evolved during combustion of materials from cables — Part 2: Determination of acidity (by pH measurement) and conductivity,” IEC, Geneva. (Halogen-free compliance standard.)
  5. VDE 0298-4, “Use of electric cables and insulated conductors for power installations — Part 4: Recommended values for the current-carrying capacity of cables and flexible cords,” VDE Verlag, Berlin.
  6. GOST R 55025, “Electric cables and wires for open-cast mines and quarries,” Federal Agency on Technical Regulating and Metrology (Rosstandart), Moscow.
  7. IEC 60502-2, “Power cables with extruded insulation and their accessories for rated voltages from 6 kV (Um = 7.2 kV) up to and including 30 kV (Um = 36 kV),” IEC, Geneva.
  8. Anhui Feichun Special Cable Co., Ltd., “(N)TSCGH3S-LED 6/10 kV Luminescent Trailing Cable — Technical Data Sheet FC-TDS-TSCGH3S-10KV-LED-2026-F28A6DBB, Rev. A1,” Hefei, March 2026.

Contact Anhui Feichun Special Cable Co., Ltd. — Mining Division

Technical Enquiries [email protected]
Mining Division [email protected]
WhatsApp +86 138 5608 5607 & +86 138 5512 3218
Document Reference FC-TDS-TSCGH3S-10KV-LED-2026-F28A6DBB | Rev. A1 | March 2026
© 2026 Anhui Feichun Special Cable Co., Ltd. All rights reserved. FC-TPU™, FC-EMH™, FC-LED™, FC-SPM™, FC-ASB™, and FeiChun® are trademarks of Anhui Feichun Special Cable Co., Ltd. Technical data subject to change without notice. Verify specifications with FeiChun Technical at [email protected] before specification or procurement. Document: FC-TDS-TSCGH3S-10KV-LED-2026-F28A6DBB | Rev. A1 | March 2026.
Previous Article

(N)TSCGH3S-LED 3,6/6 kV

Next Article

PROTOLON (FL) NTSFLCGEWOEU-LED — FeiChun® Self-Powered LED Medium Voltage Flat Reeling Cable: The Complete VDE 0250-813 Guide for Container Cranes & Mining

Write a Comment

Leave a Comment

您的邮箱地址不会被公开。 必填项已用 * 标注