Olex Versolex 与 Envirolex 对比:解读澳大利亚隧道工程从 PVC 到 LSZH 电缆的转型

Olex Versolex vs. Envirolex: Understanding the Shift from PVC to LSZH in Australian Tunnels
1. Introduction: Why Australian Tunnels Are Abandoning PVC
引言:为什么澳大利亚隧道正在淘汰 PVC 电缆
Australia’s expanding infrastructure pipeline — including the Sydney Metro, Melbourne Metro Tunnel, WestConnex, and Cross River Rail — has placed fire safety at the centre of cable specification decisions. In enclosed environments such as tunnels, the combustion of conventional PVC-insulated cables releases dense smoke and toxic hydrogen chloride (HCl) gas, severely impeding evacuation and corroding surrounding equipment.[1][2]
This shift is most clearly illustrated by two product lines from Nexans (Olex brand, Australia’s largest cable manufacturer): Versolex® — the long-established PVC-based flexible power cable, and Envirolex® — its Low Smoke Zero Halogen (LSZH) successor specifically designed for fire-sensitive environments. Understanding the technical, regulatory, and performance differences between these two ranges is essential for engineers specifying cables for tunnel and public infrastructure projects, and for international manufacturers seeking to supply LSZH-equivalent products to the Australian market.[3][4]
2. Olex Versolex®: The PVC Benchmark
Olex Versolex®:PVC 基准产品
Versolex® is Nexans’ premium range of flexible power cables with PVC-based insulation (designated X-90 or V-90) and PVC sheathing. It has been the workhorse of Australian commercial and industrial electrical installations for decades, rated to 90 °C continuous conductor temperature at 0.6/1 kV. Versolex® cables are manufactured to AS/NZS 5000.1 and AS/NZS 5000.2, and their PVC components meet the Best Practice Guidelines for PVC in the built environment.[3]
| Parameter 参数 | Versolex® Specification |
|---|---|
| Insulation 绝缘 | X-90 (XLPE), V-90 (PVC), R-EP-90, R-CPE-90, R-HF-90, or R-CSP-90 |
| Sheath 护套 | PVC (V-90) |
| Voltage Rating 额定电压 | 0.6/1 kV |
| Max. Conductor Temperature 最高导体温度 | 90 °C continuous |
| Conductor 导体 | Flexible stranded copper, Class 5 柔性绞合铜,5类 |
| Ambient Reference 参考环境温度 | 40 °C (in air) / 25 °C (in ground) |
| Standards 标准 | AS/NZS 5000.1, AS/NZS 5000.2 |
| Halogen Content 卤素含量 | Contains halogens (Cl in PVC) 含卤素 |
| Available Sizes 可用规格 | 1.5 mm² – 630 mm² (single core); multicore variants |
Nexans 自身也指出 Versolex® 有低烟无卤版本——”参见 ENVIROLEX – 低火灾危害”——并明确推荐 Envirolex® 用于以最高温度连续运行的系统,承认 LSZH 版本是火灾敏感安装的首选方案。
3. Olex Envirolex®: The LSZH Alternative
Olex Envirolex®:LSZH 替代方案
Envirolex® is part of the Nexans Fire Safety Offer, designed as a direct LSZH replacement for Versolex®. It is PVC-free, uses X-HF-110 (cross-linked halogen-free) insulation and HFS-110-TP (halogen-free thermoplastic) sheathing, and is rated to 110 °C continuous — a 20 °C increase over Versolex®. This higher thermal rating delivers a meaningful ampacity advantage in constrained cable routes typical of tunnels.[4][5][6]
| Parameter 参数 | Envirolex® Specification |
|---|---|
| Insulation 绝缘 | X-HF-110, R-HF-110, or R-E-110 (all halogen-free) |
| Sheath 护套 | HFS-110-TP (halogen-free thermoplastic) |
| Voltage Rating 额定电压 | 0.6/1 kV |
| Max. Conductor Temperature 最高导体温度 | 110 °C continuous |
| Conductor 导体 | Flexible stranded copper, Class 5 & 6 |
| Ambient Reference 参考环境温度 | 40 °C (in air) / 25 °C (in ground) |
| Standards 标准 | AS/NZS 5000.1, AS/NZS 4507 |
| Flame Propagation 火焰蔓延 | IEC 60332-3 Category A (bunched cable test) |
| Halogen Content 卤素含量 | Zero halogen — PVC-free 零卤素——无PVC |
| Fire Classification 防火分类 | RHE-3 to AS/NZS 4507 |
| Certifications 认证 | Red List Free, Declare Labelled, Green Star |
| Available Sizes 可用规格 | 1.5 mm² – 630 mm² (single core); 2C+E, 3C+E, 4C+E multicore |
4. Head-to-Head: Versolex® (PVC) vs. Envirolex® (LSZH)
正面对比:Versolex®(PVC)vs. Envirolex®(LSZH)
The following comparison table consolidates every specification point that tunnel engineers and procurement teams need to evaluate when making the PVC-to-LSZH transition decision. The differences go far beyond materials — they encompass thermal performance, fire behaviour, environmental credentials, and long-term total cost of ownership.
| Parameter 参数 | Versolex® (PVC) | Envirolex® (LSZH) |
|---|---|---|
| Insulation Type 绝缘类型 | X-90 / V-90 (contains PVC) | X-HF-110 (halogen-free XLPE) |
| Sheath Material 护套材料 | PVC (V-90) | HFS-110-TP (halogen-free thermoplastic) |
| Max. Conductor Temp 最高导体温度 | 90 °C | 110 °C (+22%) |
| Voltage Rating 额定电压 | 0.6/1 kV | 0.6/1 kV |
| Smoke Emission 烟雾排放 | High — dense black smoke 高——浓密黑烟 | Very low — ≥60% light transmittance (IEC 61034) |
| Halogen Gas Release 卤素气体释放 | HCl released (toxic, corrosive) 释放HCl(有毒腐蚀性) | pH ≥ 4.3, conductivity ≤ 10 µS/mm (IEC 60754) |
| Flame Propagation Test 火焰蔓延测试 | IEC 60332-1 (single cable) | IEC 60332-3 Cat A (bunched — most stringent 最严格) |
| Primary Standard 主要标准 | AS/NZS 5000.1 & 5000.2 | AS/NZS 5000.1, AS/NZS 4507 |
| Tunnel Suitability 隧道适用性 | Not recommended 不推荐 | Specifically designed for tunnels & enclosed spaces |
| Corrosion Risk 腐蚀风险 | High — HCl corrodes switchgear, metal structures | Negligible — non-corrosive combustion gases |
| Environmental Certs 环保认证 | PVC Best Practice compliant | Red List Free, Declare Label, Green Star |
| Relative Material Cost 相对材料成本 | Baseline (1.0×) | ~1.15× – 1.30× (higher upfront 前期较高) |
| Total Cost of Ownership 总拥有成本 | Higher when fire risk factored 考虑火灾风险后更高 | Lower over asset lifecycle 资产全生命周期更低 |
5. Australian Regulatory Framework Driving the LSZH Shift
推动 LSZH 转型的澳大利亚法规框架
The transition from PVC to LSZH in Australian tunnels is not voluntary — it is driven by an increasingly prescriptive regulatory environment. AS/NZS 3013 classifies the fire and mechanical performance of wiring system elements; AS/NZS 3000 (the Wiring Rules) mandates compliance with fire safety requirements; and AS/NZS 1670.3 requires low-smoke halogen-free cables in rail transit and underground facilities.[7][8][9] Infrastructure authorities such as Transport for NSW and the Victorian Department of Transport mandate LSZH cables in all new tunnel projects through their design standards.
| Standard 标准 | Scope 适用范围 | PVC (Versolex) | LSZH (Envirolex) |
|---|---|---|---|
| AS/NZS 5000.1 | LV power cable construction 低压电力电缆构造 | ✓ Compliant | ✓ Compliant |
| AS/NZS 4507 | Fire-performance rated cables 防火性能额定电缆 | ✗ Not rated | ✓ RHE-3 |
| AS/NZS 3013 | Fire & mechanical performance of wiring 布线防火和机械性能 | Limited compliance | ✓ Full compliance |
| AS/NZS 1670.3 | Fire detection & alarm — cabling 火灾探测报警布线 | ✗ Not permitted in tunnels | ✓ Mandatory compliant |
| AS/NZS 3000 | Wiring Rules 布线规则 | ✓ General use | ✓ General + fire-critical |
| IEC 60332-3 | Flame propagation — bunched cables 成束电缆火焰蔓延 | Single cable only | ✓ Cat A (most stringent) |
| IEC 60754-1/-2 | Halogen acid gas emission 卤素酸性气体排放 | Fails — HCl > 5 mg/g | ✓ pH ≥ 4.3 |
| IEC 61034-2 | Smoke density measurement 烟雾密度测量 | Fails — low transmittance | ✓ ≥ 60% light transmittance |
6. The Science: PVC vs. LSZH Combustion Behaviour
科学解析:PVC 与 LSZH 燃烧行为对比
When PVC burns, the chlorine atoms in polyvinyl chloride react with hydrogen to produce hydrogen chloride (HCl) gas. In a tunnel fire scenario, this gas creates a highly corrosive acidic atmosphere that damages electrical switchgear, ventilation systems, structural steel, and signalling equipment — often causing secondary damage exceeding the original fire cost. The dense black smoke produced drops visibility to near zero within minutes, critically impeding evacuation. In contrast, LSZH compounds are formulated from halogen-free polyolefin-based materials that release minimal, non-toxic combustion products and maintain light transmittance above 60% during the IEC 61034 smoke density test.[1][10][11]
| Fire Parameter 火灾参数 | PVC Cable | LSZH Cable | Test Standard |
|---|---|---|---|
| Smoke Density 烟雾密度 | Very high 非常高 | < 20% of PVC levels | IEC 61034-2 |
| Light Transmittance 透光率 | < 30% (rapid obscuration) | ≥ 60–80% | IEC 61034-2 |
| HCl Gas Release 氯化氢释放 | Significant (> 150 mg/g HCl) | ≤ 5 mg/g halogen acid | IEC 60754-1 |
| Gas Acidity (pH) 气体酸度 | pH < 2 (highly acidic) | pH ≥ 4.3 | IEC 60754-2 |
| Gas Conductivity 气体导电性 | > 100 µS/mm | ≤ 10 µS/mm | IEC 60754-2 |
| Flame Propagation 火焰蔓延 | Self-extinguishing (single) 自熄(单根) | Cat A compliant (bunched) 成束合格 | IEC 60332-3-22 |
| Equipment Corrosion 设备腐蚀 | Severe 严重 | Negligible 可忽略 | — |
7. Electrical Performance Data: Envirolex® Single Core
电气性能数据:Envirolex® 单芯
The following table provides representative DC resistance and dimensional data for the Envirolex® flexible single-core range, illustrating that the LSZH construction maintains full electrical performance equivalence to PVC-insulated alternatives while delivering improved thermal capacity.
| Size (mm²) | Max. DC Resistance 20 °C (Ω/km) | Nom. OD (mm) | Approx. Mass (kg/100m) | Product Code |
|---|---|---|---|---|
| 10 | 1.91 | 8.6 | 16 | BZHX01AA001 |
| 16 | 1.21 | 9.8 | 23 | BZHX02AA001 |
| 25 | 0.78 | 11.3 | 31 | BZHX03AA001 |
| 35 | 0.554 | 12.5 | 40 | BZHX04AA001 |
| 50 | 0.386 | 14.3 | 56 | BZHX05AA001 |
| 70 | 0.272 | 16.2 | 75 | BZHX06AA001 |
| 95 | 0.206 | 18.1 | 98 | BZHX07AA001 |
| 120 | 0.161 | 20.4 | 113 | BZHE87AA001 |
| 150 | 0.129 | 22.5 | 151 | BZHE88AA001 |
| 185 | 0.106 | 24.8 | 182 | BZHE89AA001 |
| 240 | 0.0801 | 27.9 | 236 | BZHE90AA001 |
| 300 | 0.0641 | 30.8 | 295 | BZHE91AA001 |
| 400 | 0.0486 | 34.7 | 382 | BZHE92AA001 |
| 500 | 0.0384 | 40.0 | 483 | BZHE93AA001 |
| 630 | 0.0287 | 44.6 | 635 | BZHE94AA001 |
8. Australian Tunnel Projects: Where LSZH Is Now Mandatory
澳大利亚隧道项目:LSZH 已成强制要求的场所
The shift is not theoretical — it is already embedded in the specifications of Australia’s largest active infrastructure programmes. Standards such as AS/NZS 3013 for fire and mechanical performance classification and IEC 60332-3 for flame propagation in bunched cables are now standard requirements in tunnel design documentation.[7][8][2]
| Sector 领域 | Application 应用 | Regulatory Driver 法规驱动 |
|---|---|---|
| Rail Tunnels 铁路隧道 | Traction power, signalling, comms 牵引供电、信号、通信 | AS/NZS 1670.3, AS/NZS 3013 |
| Road Tunnels 公路隧道 | Lighting, ventilation, SCADA 照明、通风、SCADA | AS/NZS 3000, IEC 60332-3 |
| Metro Systems 地铁系统 | Platform power, emergency systems 站台供电、应急系统 | AS/NZS 1670.3, AS/NZS 4507 |
| Hospitals 医院 | Life-safety circuits, operating theatres 生命安全回路、手术室 | AS/NZS 3003, AS/NZS 3013 |
| Data Centres 数据中心 | Rack power, UPS feeds 机架供电、UPS馈线 | IEC 60754, IEC 61034 |
| Public Buildings 公共建筑 | Fire alarm, emergency lighting 火灾报警、应急照明 | AS/NZS 1670, AS/NZS 3013 |
9. Feichun LSZH Cable Solutions: Equivalent Performance for Global Projects
飞纯 LSZH 电缆解决方案:为全球项目提供等效性能
Anhui Feichun Special Cable Co., Ltd. (安徽飞纯特种电缆有限公司) manufactures LSZH power cables engineered to meet the same performance envelope as Olex Envirolex®, including compliance with IEC 60332-3, IEC 60754, and IEC 61034 fire testing requirements. Our cables utilise halogen-free cross-linked polyolefin insulation with 110 °C continuous ratings and are available with third-party test certificates from accredited laboratories, supporting specification approval on Australian tunnel and infrastructure projects.
飞纯的 LSZH 电缆系列涵盖 1.5mm² 至 630mm² 的单芯和多芯结构,额定电压 0.6/1kV,符合 IEC 60332-3 A 类火焰蔓延合规、IEC 60754-1/-2 卤素气体测试和 IEC 61034-2 烟雾密度验证。所有产品外径公差受控,与标准澳大利亚电缆管理系统兼容。请联系我们的工程团队获取项目专属数据表和测试证书。
10. Conclusions
结论
The Australian tunnel infrastructure sector has definitively moved from PVC-based cables like Olex Versolex® to LSZH alternatives like Olex Envirolex®. This transition is driven by a clear technical case — reduced smoke generation, elimination of toxic and corrosive halogen gas emissions, superior flame propagation resistance, and a higher 110 °C continuous thermal rating — reinforced by mandatory regulatory requirements under AS/NZS 3013, AS/NZS 1670.3, and the IEC 60332/60754/61034 test framework. For international cable manufacturers and suppliers, the ability to produce LSZH cables that meet this performance and testing matrix is now a prerequisite for participating in Australian infrastructure projects.
References & Sources
参考文献与来源
- Infrastructure Magazine — “Selecting the right cables for tunnels and overhead transport systems” (2023). infrastructuremagazine.com.au
- TST Cables — “Requirements and standards for LSZH cables in various countries around the world.” tstcables.com
- Nexans Australia — Olex Versolex® Flexible Single Core 90 °C Product Page. nexans.com.au (Versolex)
- Nexans Australia — Olex Envirolex® Flexible Single Core 110 °C Product Page. nexans.com.au (Envirolex Single Core)
- Nexans Australia — Envirolex® Flexible Multicore Low Fire Hazard Cable. nexans.com.au (Envirolex Multicore)
- Nexans Australia — Envirolex® 2C+E 4mm² Specifications and Datasheet. nexans.com.au (Envirolex 2C+E)
- Standards Australia — AS/NZS 3013:2005 Fire and mechanical performance of wiring systems. store.standards.org.au
- NAN Cable — “Electrical Cable Types in Australia: TPS & XLPE (AS/NZS 5000 Guide).” gdnancable.com
- IET — “Cables and fire protection FAQs” — LSF vs. LSZH distinction, BS EN 61034, BS EN 60754 compliance. electrical.theiet.org
- JJ-LAPP — “LSZH Cables Boost Fire Safety in Building Infrastructure.” jj-lapp.com
- Gudacable — “LSZH Cable Defined: Meaning, Safety Standards & PVC Comparison.” gudacable.com
- Blackwoods (Wesfarmers) — Nexans Olex Envirolex® 120mm² Product Listing. blackwoods.com.au
- Greenbuildsupply — “Elevating Safety: Understanding LSZH Conduits” — IEC 60754-1, IEC 61034, NFPA 130. greenbuildsupply.com.au
- Gudacable — “Complete Guide to IEC Standards for Electrical Cables.” gudacable.com (IEC guide)
- Nexans Australia — Olex-Flex Flexible LSZH Earth Cable — RHE-3 to AS/NZS 4507. nexans.com.au (LSZH Earth)