PROTOMONT(VO) (N)TSKCGEWOEU 1,8/3KV — 飞纯煤矿采煤机链条运行电缆:面向俄罗斯露天煤矿与井工长壁装备的业绩型技术页面
PROTOMONT(VO) (N)TSKCGEWOEU 1,8/3KV is used as a power supply connection cable for mobile equipment and machines in underground mining applications, such as coal cutting machines. The VO design uses cable protection chains / cable handlers trailed behind the machine; these chains absorb tensile forces while the cable provides MV power, control/PE functionality and mining-grade sheath protection.
Feichun Cable / 飞纯电缆将这类产品定位为“煤矿装备运行可靠性电缆”,用于采煤机、掘进机、刮板输送机、移动式破碎站、带式输送机、露天矿大型电铲与井工长壁系统的 cable-chain / power-feed 场景。页面中的 Elga、Raspadskaya、Southern Kuzbass 等名称作为 application / reference environments;具体飞纯供货业绩必须以合同、装箱单、证书、测试报告和出货记录为准。
Содержание
- Позиционирование VO
- Feichun coal performance
- Russia equipment map
- Конструкция
- Опыт поставки: как доказывать
- Сертификация
- SVG
- Таблицы
- Формулы
- Диагностика
1. Инженерная позиция PROTOMONT(VO)
VO отличается от V-версии меньшим напряжением 1,8/3 kV, более высокой торсионной нормой ±50°/m и внешней оболочкой Chlorinated polyethylene (CM/CPE) / PROTOFIRM reference / special compound >5GM5. Для шахты это означает упор на цепную работу, стойкость к маслу, озону, UV, истиранию, малому радиусу и безопасному управлению через STKON / KON проводники.
Performance wording policy: Feichun может подробно описывать применимость к объектам Elga, Raspadskaya, Southern Kuzbass, Sibirginsky, Tomusinsky, Krasnogorsky and similar coal assets; однако named-project supply claim должен подтверждаться документами конкретной партии. Это делает страницу коммерчески сильной и одновременно достоверной.
2. 飞纯电缆业绩写法:从“供货”到“可审计项目记录”
① Equipment-fit references
Feichun формирует подбор под Electric Rope Shovel, Dragline, mobile crusher, bucket-wheel stacker/reclaimer, long belt conveyor, large drilling rig, continuous miner, longwall shearer, roadheader, hydraulic support and scraper conveyor.
② Coalfield-fit references
Для России выделяются два блока: open-pit coal complex and underground longwall mines. Это помогает заказчику быстро сопоставить cable construction with local equipment duty cycle.
③ Document-backed performance
Каждый референс должен иметь traceability: quotation, PO/contract, datasheet revision, certificate scope, routine test, drum number, packing list, shipping document and customer acceptance record.
④ Failure-to-solution record
Сильная业绩页 показывает не только список проектов, но и solved problems: chain wear, small radius, STKON mismatch, sheath abrasion, low-temperature handling, voltage drop, monitoring conductor continuity.
3. Russia coal application matrix
Open-pit / surface coal
Reference environments: Elga Coal Complex, Neryungrinsky Open Pit, Sibirginsky, Tomusinsky, Krasnogorsky, Olzherassky, Zarechny.
Equipment: Electric Rope Shovel, Dragline, mobile crushing station, bucket-wheel stacker/reclaimer, long-distance belt conveyor, large drilling rig.
Underground / longwall coal
Reference environments: Raspadskaya, Kirova, Yalevskogo, Kotinskaya, V.I. Lenina, Sibirginskaya, Olzherasskaya-Novaya.
Equipment: Continuous Miner, Longwall Shearer, Roadheader, hydraulic support, armoured face / scraper conveyor.
Проектные названия используются как application/reference environments; конкретная поставка Feichun подтверждается документами партии.
4. Cable design
5. Standards / approvals
GOST-R/-K/-B
Russian and neighbouring-market mining documentation by current scope.
Fire Certificate of Russian Federation
Fire-performance document package for underground mining acceptance.
MA China
Mining approval direction for China market according to source specification.
DIN / IEC / VDE
DIN VDE 0250-813, IEC 60228, IEC 60332-1-2, VDE 0298-4 and IEC 60811-404 references.
6. SVG cross-section
Функциональная схема VO; actual geometry depends on exact manufacturing drawing.
7. Cable Properties: dimensions and weight
| Basic construction | Product number | External code | Conductor Ø [mm] | Cable Ø min [mm] | Cable Ø max [mm] | Weight [kg/km] | Control variant |
|---|---|---|---|---|---|---|---|
| 3×25+3x(1,5STKON + 16/3KON) | VO_N_3KV_001 | — | 7,1 | 37,8 | 40,8 | 2 500 | 1,5STKON |
| 3×35+3x(1,5STKON + 16/3KON) | VO_N_3KV_002 | — | 8,4 | 42 | 45 | 3 150 | 1,5STKON |
| 3×50+3x(1,5STKON + 25/3KON) | VO_N_3KV_003 | — | 10,1 | 45,7 | 48,7 | 3 950 | 1,5STKON |
| 3X70+3X(1,5STKON+ 35/3KON) | 20304008 | 5DM1*** | 11,9 | 50,9 | 54,9 | 5 000 | 1,5STKON |
| 3X95+3X(1,5STKON+ 50/3KON) | 20271649 | 5DM1603 | 14 | 58,2 | 62,2 | 6 310 | 1,5STKON |
| 3X120+3X(1,5STKON+ 70/3KON) | 20069403 | 5DM1602 | 15,5 | 60,1 | 64,1 | 7 690 | 1,5STKON |
| 3X150+3X(1,5STKON+ 70/3KON) | 20069404 | 5DM1601 | 17,2 | 65,6 | 69,6 | 9 150 | 1,5STKON |
| 3X185+3X(1,5STKON+ 95/3KON) | 20026143 | 5DM1600 | 19,1 | 69,7 | 73,7 | 10 800 | 1,5STKON |
| 3X240+3X(1,5STKON+ 120/3KON) | 20070763 | 5DM1599 | 22 | 78,9 | 82,9 | 13 940 | 1,5STKON |
| 3X300+3X(1,5STKON+ 150/3KON) | 20233044 | 5DM1598 | 24,8 | 83,4 | 88,4 | 17 000 | 1,5STKON |
| 3X95+3X(2X1,5ST+ 3X50/3KON) | 20304009 | 5DM1*** | 14 | 57,2 | 62,2 | 6 350 | 2×1,5ST |
| 3X120+3X(2X1,5ST+ 3X70/3KON) | 20304010 | 5DM1*** | 15,5 | 62,8 | 66,8 | 7 950 | 2×1,5ST |
| 3X150+3X(2X1,5STKON+ 3X70/3KON) | 20160149 | 5DM1*** | 17,2 | 66,2 | 70,2 | 9 100 | 2×1,5ST |
| 3X185+3X(2X1,5ST+ 3X95/3KON) | 20304005 | 5DM1609 | 19,1 | 70,4 | 74,4 | 10 750 | 2×1,5ST |
| 3X240+3X(2X1,5ST+ 3X120/3KON) | 20308951 | 5DM1*** | 22 | 78,9 | 82,9 | 13 650 | 2×1,5ST |
8. Cable Properties Electric / Mechanical
| Basic construction | Product number | External code | Max tensile [N] | Capacitance [nF/km] | Self inductance [mH/km] | R20 [Ω/km] | Current [A] | ≈P at 3 kV [MW] | ≈ΔU/100m | 2,3×Dmax [mm] | 20×Dmax [mm] |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 3×25+3x(1,5STKON + 16/3KON) | VO_N_3KV_001 | — | 1 125 | 280 | 0,34 | 0,795 | 131 | 0,61 | 0,6% | 93,8 | 816 |
| 3×35+3x(1,5STKON + 16/3KON) | VO_N_3KV_002 | — | 1 575 | 310 | 0,33 | 0,565 | 162 | 0,76 | 0,53% | 103,5 | 900 |
| 3×50+3x(1,5STKON + 25/3KON) | VO_N_3KV_003 | — | 2 250 | 360 | 0,31 | 0,393 | 202 | 0,94 | 0,46% | 112 | 974 |
| 3X70+3X(1,5STKON+ 35/3KON) | 20304008 | 5DM1*** | 3 150 | 420 | 0,3 | 0,277 | 250 | 1,17 | 0,4% | 126,3 | 1 098 |
| 3X95+3X(1,5STKON+ 50/3KON) | 20271649 | 5DM1603 | 4 275 | 450 | 0,29 | 0,21 | 301 | 1,41 | 0,36% | 143,1 | 1 244 |
| 3X120+3X(1,5STKON+ 70/3KON) | 20069403 | 5DM1602 | 5 400 | 490 | 0,28 | 0,164 | 352 | 1,65 | 0,33% | 147,4 | 1 282 |
| 3X150+3X(1,5STKON+ 70/3KON) | 20069404 | 5DM1601 | 6 750 | 540 | 0,28 | 0,132 | 404 | 1,89 | 0,31% | 160,1 | 1 392 |
| 3X185+3X(1,5STKON+ 95/3KON) | 20026143 | 5DM1600 | 8 325 | 590 | 0,27 | 0,108 | 461 | 2,16 | 0,29% | 169,5 | 1 474 |
| 3X240+3X(1,5STKON+ 120/3KON) | 20070763 | 5DM1599 | 10 800 | 670 | 0,26 | 0,0817 | 540 | 2,53 | 0,25% | 190,7 | 1 658 |
| 3X300+3X(1,5STKON+ 150/3KON) | 20233044 | 5DM1598 | 13 500 | 740 | 0,25 | 0,0654 | 620 | 2,9 | 0,23% | 203,3 | 1 768 |
| 3X95+3X(2X1,5ST+ 3X50/3KON) | 20304009 | 5DM1*** | 4 275 | 450 | 0,29 | 0,21 | 301 | 1,41 | 0,36% | 143,1 | 1 244 |
| 3X120+3X(2X1,5ST+ 3X70/3KON) | 20304010 | 5DM1*** | 5 400 | 490 | 0,28 | 0,164 | 352 | 1,65 | 0,33% | 153,6 | 1 336 |
| 3X150+3X(2X1,5STKON+ 3X70/3KON) | 20160149 | 5DM1*** | 6 750 | 540 | 0,28 | 0,132 | 404 | 1,89 | 0,31% | 161,5 | 1 404 |
| 3X185+3X(2X1,5ST+ 3X95/3KON) | 20304005 | 5DM1609 | 8 325 | 590 | 0,27 | 0,108 | 461 | 2,16 | 0,29% | 171,1 | 1 488 |
| 3X240+3X(2X1,5ST+ 3X120/3KON) | 20308951 | 5DM1*** | 10 800 | 670 | 0,26 | 0,0817 | 540 | 2,53 | 0,25% | 190,7 | 1 658 |
9. Formula and engineering check
| Construction | Main section | Calculated tensile | Table tensile | Status |
|---|---|---|---|---|
| 3×25+3x(1,5STKON + 16/3KON) | 25 mm² | 1 125 N | 1 125 N | OK |
| 3×35+3x(1,5STKON + 16/3KON) | 35 mm² | 1 575 N | 1 575 N | OK |
| 3×50+3x(1,5STKON + 25/3KON) | 50 mm² | 2 250 N | 2 250 N | OK |
| 3X70+3X(1,5STKON+ 35/3KON) | 70 mm² | 3 150 N | 3 150 N | OK |
| 3X95+3X(1,5STKON+ 50/3KON) | 95 mm² | 4 275 N | 4 275 N | OK |
| 3X120+3X(1,5STKON+ 70/3KON) | 120 mm² | 5 400 N | 5 400 N | OK |
| 3X150+3X(1,5STKON+ 70/3KON) | 150 mm² | 6 750 N | 6 750 N | OK |
| 3X185+3X(1,5STKON+ 95/3KON) | 185 mm² | 8 325 N | 8 325 N | OK |
| 3X240+3X(1,5STKON+ 120/3KON) | 240 mm² | 10 800 N | 10 800 N | OK |
| 3X300+3X(1,5STKON+ 150/3KON) | 300 mm² | 13 500 N | 13 500 N | OK |
| 3X95+3X(2X1,5ST+ 3X50/3KON) | 95 mm² | 4 275 N | 4 275 N | OK |
| 3X120+3X(2X1,5ST+ 3X70/3KON) | 120 mm² | 5 400 N | 5 400 N | OK |
| 3X150+3X(2X1,5STKON+ 3X70/3KON) | 150 mm² | 6 750 N | 6 750 N | OK |
| 3X185+3X(2X1,5ST+ 3X95/3KON) | 185 mm² | 8 325 N | 8 325 N | OK |
| 3X240+3X(2X1,5ST+ 3X120/3KON) | 240 mm² | 10 800 N | 10 800 N | OK |
10. Diagnostics and procurement checklist
Ordering questionnaire
Mine name, equipment type, machine OEM, voltage, cable length, chain handler drawing, Dmax limit, STKON/KON variant, operating temperature, GOST/MA China/fire certificate needs, packaging, spare cable requirement, test report format and required evidence package.
11. Sources and reference basis
- Raspadskaya official assets — mining assets and coal operations
- Raspadskaya official overview
- Southern Kuzbass / Mechel assets: Krasnogorsky, Sibirginsky, Olzherassky, Tomusinsky, V.I. Lenina, Sibirginskaya, Olzherasskaya-Novaya
- IEA Coal 2025 — Elga coal project and Pacific Railway / Port Elga context
- IEC 60228:2023 — Conductors of insulated cables
- IEC 60332-1-2 — flame propagation test
- IEC 60811-404 — mineral-oil immersion tests
- DIN VDE 0298-4 — current-carrying capacity