Comprehensive technical guide to flame-retardant, halogen-free medium voltage cables with dual waterblocking technology. Manufactured in accordance with IEC 60502-2 and VDE 0276-620 standards for power distribution networks.

N2XS(FL)H cable, medium voltage cable, XLPE insulated cable, IEC 60502-2, LSZH cable, waterblocking cable, 12/20kV power cable, Feichun Cable, CPR compliant cable
What is N2XS(FL)H Cable? | Complete Technical Guide | Anhui Feichun Special Cable Co., Ltd.

What is N2XS(FL)H Medium Voltage Power Cable?

Comprehensive technical guide to flame-retardant, halogen-free medium voltage cables with dual waterblocking technology. Manufactured in accordance with IEC 60502-2 and VDE 0276-620 standards for power distribution networks.

IEC 60502-2 Compliant 6/10kV – 18/30kV XLPE Insulation LSZH Sheath CPR Compliant

1. Overview: Purpose and Applications

The N2XS(FL)H cable designation represents a sophisticated medium voltage power distribution cable engineered for demanding industrial and infrastructure applications. This cable type combines cross-linked polyethylene (XLPE) insulation with a Low Smoke Zero Halogen (LSZH) outer sheath and incorporates dual-layer waterblocking technology, making it suitable for both internal and external installations where fire safety and environmental protection are paramount.

According to industry specifications referenced by reelingcable.com, medium voltage cables in this category are particularly valuable for power distribution in utility networks, energy generation facilities, and industrial infrastructure requiring continuous, reliable power transmission under challenging environmental conditions.

Designation Breakdown: N2XS(FL)H

Code ElementDesignationTechnical Meaning
NStandard DesignGerman (DIN/VDE) standard construction
2XXLPE InsulationCross-linked polyethylene, 90°C rated
SCopper ScreenCopper wire and tape metallic screening
(F)Longitudinal WaterblockingSwellable tape/powder barrier
(L)Radial WaterblockingLaminated Al/PET tape barrier
HLSZH SheathLow Smoke Zero Halogen outer sheath

Primary Application Scenarios

The N2XS(FL)H cable finds extensive application across diverse sectors where medium voltage power distribution is critical. As documented by amplexmining.com.au, specialized cables in industrial environments must withstand severe physical punishment including constant abrasion, crushing forces, and exposure to environmental extremes while maintaining electrical integrity.

Power Stations
Primary

Substations and generation facilities requiring fire-safe cabling

Underground Networks
Essential

Cable ducts, direct burial, and tunnel installations

Industrial Facilities
Critical

Manufacturing plants, data centers, life sciences

Buildings/Infrastructure
CPR Required

Internal installations with fire regulation compliance

2. Technical Characteristics and Performance Parameters

The N2XS(FL)H cable is engineered to deliver exceptional electrical performance while maintaining mechanical durability under demanding operational conditions. The following specifications represent standard manufacturing parameters in accordance with international standards.

Voltage Ratings and Electrical Parameters

Parameter6/10 (12) kV8.7/15 (17.5) kV12/20 (24) kV18/30 (36) kV
Rated Voltage U₀/U (Um)6/10 (12)kV8.7/15 (17.5)kV12/20 (24)kV18/30 (36)kV
AC Test Voltage (5 min)21kV30.45kV42kV63kV
Lightning Impulse Test75kV95kV125kV170kV
Insulation Thickness (Nominal)3.4mm4.5mm5.5mm8.0mm

Thermal Performance Thresholds

Max Operating Temperature
+90°C
Emergency Overload (8h)
+130°C
Short Circuit (5s max)
+250°C
Min Installation Temp
-20°C

Current Carrying Capacity Reference

The following ampacity values are calculated for cables installed in air at an ambient temperature of 30°C with conductor operating temperature of 90°C. Actual current ratings should be verified against specific installation conditions.

Conductor Size (mm²)In Air (A)Direct Buried (A)In Duct (A)Short Circuit 1s (kA)
351701551405.0
502001801657.2
7024522020010.0
9529526524013.6
12034030027517.2
15038534031021.5
18544038535026.5
24051544540534.4
30058550546043.0
40068057552557.3
50077564559071.6
63088572566590.2

📊 Derating Factors

Apply correction factors for ambient temperatures above 30°C: at 40°C use 0.91, at 50°C use 0.82, at 60°C use 0.71. For grouped cables, apply additional derating based on spacing and configuration per IEC 60287.

3. Material Structure and Construction

The N2XS(FL)H cable employs a layered construction approach with each component specifically engineered to address particular electrical, mechanical, or environmental requirements. As detailed by cranecable.com, port and industrial cables must endure continuous mechanical stress while maintaining electrical integrity, making proper material selection essential for operational longevity.

1

Conductor — Class 2 Stranded Copper

Compacted stranded copper conductor per EN 60228 Class 2, providing optimal conductivity-to-size ratio. Stranded construction enhances flexibility while maintaining current-carrying capacity for medium voltage applications.

2

Conductor Screen — Semiconductive Compound

Extruded semiconductive layer applied in triple extrusion process with insulation. Creates uniform electric field distribution and eliminates air gaps between conductor and insulation.

3

Insulation — Cross-Linked Polyethylene (XLPE)

High dielectric strength XLPE insulation providing exceptional thermal stability up to +90°C continuous operation. Offers superior moisture resistance and aging characteristics compared to EPR alternatives.

4

Insulation Screen — Semiconductive Layer

Strippable semiconductive compound applied over insulation. Maintains uniform electric field and facilitates cable termination and jointing operations.

5

Longitudinal Waterblocking (F) — Swellable Tapes

Water-swellable tapes and/or powders applied above and below metallic screen. Upon moisture contact, material expands to form barrier preventing water propagation along cable length.

6

Metallic Screen — Copper Wires + Copper Tape

Helically applied copper wire screen combined with counter-helix wound copper tape. Provides EMI shielding, contains electric field within core, and serves as fault current return path.

7

Radial Waterblocking (L) — Aluminium Laminate

Aluminium tape tightly bonded to sheath creates radial water barrier. Prevents moisture ingress in event of mechanical sheath damage (puncture, abrasion, or impact).

8

Outer Sheath — LSZH Compound

Low Smoke Zero Halogen thermoplastic sheath per IEC 60754. CPR compliant, flame retardant, UV resistant for internal and external installation. Traditionally red color for identification.

Material Performance Comparison

PropertyXLPE (N2XS_H)EPR AlternativePVC Alternative
Max Operating Temp90°C90°C70°C
Dielectric Constant (εr)2.33.0–3.54.0–8.0
Dielectric Loss (tan δ)0.00040.0050.08
Water AbsorptionVery LowLowModerate
FlexibilityModerateHighModerate

4. Standards Compliance and Certifications

The N2XS(FL)H cable is manufactured to meet stringent international standards ensuring consistent quality, performance, and safety across global installations. According to research from amplexmining.com.au, compliance with recognized cable standards provides assurance that cables will perform reliably in demanding industrial conditions, with rigorous testing requirements covering everything from insulation integrity to mechanical protection.

Primary Manufacturing Standards

StandardDesignationScope
IEC 60502-2Power Cables with Extruded InsulationCables 6 kV to 30 kV — Construction, dimensions, test requirements
VDE 0276-620German National StandardPower cables — MV cables with polymeric insulation
HD 620CENELEC Harmonized DocumentEuropean MV cable harmonization standard
EN 60228Conductor ClassesConductors of insulated cables (Class 1/2 specifications)

Fire Performance Standards

StandardTest MethodRequirement
IEC/EN 60332-1-2Single cable flame propagationFlame retardant — Self-extinguishing
IEC/EN 60332-3-24Bundled cables Category CLimited flame spread in grouped installation
IEC/EN 61034-1/2Smoke density measurementLow smoke emission ≥ 60% light transmittance
IEC/EN 60754-1/2Halogen gas emissionZero halogen — pH ≥ 4.3, conductivity ≤ 10 µS/mm

Construction Products Regulation (CPR) Compliance

For installations within the European Union where cables enter or are installed inside buildings, CPR compliance under EU Regulation 305/2011 is mandatory. The N2XS(FL)H cable with LSZH sheath achieves Euroclass ratings suitable for CPR requirements, enabling continuous cable runs from external to internal environments without jointing at the point of entry.

CPR Euroclass
B2ca

-s1, d1, a1 (typical)

UV Resistance
EN 50396

Suitable for outdoor exposure

Operating Life
30+

Years expected service life

5. Safety Thresholds and Operational Limits

Understanding and adhering to the safety thresholds of N2XS(FL)H cables is essential for maintaining system integrity and preventing premature failure. As noted in mining cable guidance from Feichun Cables, industrial cables must be rated appropriately for their operating environment, with safety margins built into specifications to account for transient conditions and installation variations.

Critical Temperature Thresholds

⚠️ Maximum Temperature Limits

Exceeding rated temperatures accelerates insulation degradation following the Arrhenius equation. Every 10°C increase above rated temperature approximately halves expected cable service life. Continuous operation at +90°C conductor temperature is the design limit; emergency overload to +130°C should be limited to 8-hour duration maximum with subsequent derating.

Operating ConditionTemperature LimitDuration LimitEffect on Service Life
Normal Operation+90°CContinuousDesign basis (30+ years)
Emergency Overload+130°C8 hours maximumLimited cycles permitted
Short Circuit+250°C5 seconds maximumPost-fault inspection required
Minimum Installation-20°CN/AAvoid bending below this temp

Electrical Safety Parameters

ParameterValueNotes
Insulation Resistance (MΩ·km)≥ 1000At 20°C, minimum acceptable value
Maximum Screen Voltage≤ 65VTouch voltage limit under fault conditions
Partial Discharge Extinction≤ 5 pCAt 1.5 × U₀, factory test requirement
Water Tree ResistanceHighTR-XLPE grade where specified

Mechanical Safety Limits

Conductor SizeMin Bending Radius (Fixed)Min Bending Radius (During Install)Max Pulling Tension
≤ 150 mm²12 × OD15 × OD50 N/mm² conductor area
185 – 400 mm²15 × OD20 × OD50 N/mm² conductor area
≥ 500 mm²18 × OD25 × OD40 N/mm² conductor area

6. Installation Precautions and Best Practices

Proper installation procedures are critical to achieving the full design life and performance of N2XS(FL)H cables. Research from miningcable.cl and industry sources emphasizes that cable selection is only part of the equation—correct installation techniques, environmental considerations, and ongoing maintenance determine actual operational performance and longevity.

Pre-Installation Requirements

✓

Cable Inspection

Visually inspect drum and cable for transport damage. Check seal integrity on cable ends. Verify cable marking matches specification. Perform insulation resistance test before installation.

✓

Temperature Verification

Confirm ambient temperature exceeds -20°C before handling or bending cable. Store cable drums in temperature-controlled environment if installation will occur in cold conditions. Pre-warm cable if necessary.

✓

Route Preparation

Clear cable route of sharp edges, debris, and obstructions. Install appropriate cable supports, guides, and rollers. Verify duct internal diameter and clear obstructions. Calculate pulling tension and compare to limits.

Installation Method Guidelines

Installation TypeKey RequirementsSpecial Considerations
Direct BurialMin 700mm depth, cable route marking, sand bedding 100mm above/belowThermal resistivity of backfill affects ampacity; use thermal sand where required
Cable DuctUse cable lubricant, respect pulling tension, verify duct integrityWaterblocking essential for ducts subject to flooding; FL version mandatory
Cable TrayAdequate support spacing, separation from other services, fire barriersLSZH sheath required for indoor cable trays; maintain cleating intervals
Tunnel/GalleryProper ventilation for heat dissipation, fire compartmentalizationConsider forced cooling for heavily loaded installations

Critical Installation Cautions

⚠️ Critical Installation Precautions

Never exceed bending radius limits — Insulation damage may not be immediately visible but will cause premature failure. Avoid sidewall pressure during pulling operations. Seal cable ends immediately after cutting to prevent moisture ingress. Ground screens at both ends for cables > 25m to prevent circulating currents. Test before energization — perform DC hipot or VLF testing per manufacturer recommendations.

Jointing and Termination

Cable jointing and termination must be performed by qualified personnel using manufacturer-approved accessories. The dual waterblocking layers (FL) require specific joint designs to maintain water barrier integrity across the joint. Heat-shrink or cold-shrink terminations should be specified for the LSZH sheath type.

7. Frequently Asked Questions (FAQ)

What is the difference between N2XS(F)H and N2XS(FL)H cables?
The (F) designation indicates longitudinal waterblocking only, using swellable tapes/powders that expand when exposed to moisture to prevent water propagation along the cable length. The (FL) designation includes both longitudinal AND radial waterblocking, adding an aluminium laminate tape bonded to the sheath that prevents water ingress if the outer sheath is mechanically damaged (punctured, abraded, or cut). FL versions are recommended for installations in cable ducts subject to flooding, direct burial in high water table areas, or any location where sheath damage is possible.
Can N2XS(FL)H cables be installed outdoors in direct sunlight?
Yes, the LSZH outer sheath is UV stabilized and suitable for outdoor exposure per EN 50396 requirements. The traditional red sheath color provides good UV resistance. However, for installations with prolonged direct sun exposure in high-temperature climates, derating factors should be applied to account for solar heating effects. The cable is rated for ambient temperatures up to +40°C under standard conditions.
What conductor options are available for N2XS(FL)H cables?
Standard N2XS(FL)H cables feature Class 2 stranded copper conductors offering optimal conductivity-to-size ratio for applications where space is limited. Aluminium conductor variants are designated NA2XS(FL)H and are typically selected where weight reduction is beneficial and space constraints permit the larger conductor diameter required for equivalent current capacity. Copper cables are approximately 35% smaller in diameter than equivalent-ampacity aluminium cables.
What is the expected service life of N2XS(FL)H cables?
When installed and operated within rated parameters, N2XS(FL)H cables are designed for a service life exceeding 30 years. Key factors affecting longevity include: maintaining conductor temperature below 90°C during normal operation, avoiding repeated emergency overloads, protecting against mechanical damage, and proper termination/jointing. Elevated operating temperatures significantly reduce service life—each 10°C increase above design temperature approximately halves expected life per the Arrhenius aging model.
How does N2XS(FL)H compare to N2XSY (PVC sheath) cables?
The key differences are fire performance and installation flexibility. N2XS(FL)H (LSZH) offers low smoke, zero halogen properties essential for internal installations, tunnels, and buildings where fire safety is critical—it is CPR compliant for EU installations. N2XSY (PVC) is suitable primarily for external/underground installations where fire performance is less critical but may not be used internally in CPR-regulated buildings. The LSZH sheath is also more environmentally friendly, releasing no corrosive hydrogen chloride gas during combustion.
Is the N2XS(FL)H cable suitable for mining applications?
While N2XS(FL)H cables are excellent for fixed power distribution in surface mining facilities, substations, and processing plants, they are not designed for trailing/reeling applications on mobile mining equipment. Mining trailing cables require flexible Class 5/6 conductors, enhanced mechanical reinforcement, and specialized sheath compounds for abrasion resistance. Consult amplexmining.com.au for AS/NZS 2802 compliant mining cable specifications or contact Feichun Cable for trailing cable solutions.
What testing is required before energizing N2XS(FL)H cables?
Pre-commissioning testing should include: Insulation resistance test (minimum 1000 MΩ·km at 20°C using 5kV megger for 12/20kV cables), continuity verification of conductors and screens, and VLF or DC high-potential test per manufacturer/utility requirements (typically 3×U₀ for VLF). After jointing or termination work, localized testing should verify joint integrity. Partial discharge testing may be specified for critical installations.

8. Common Cable Variants and Alternatives

The N2XS(FL)H belongs to a family of medium voltage cables sharing common design principles but optimized for different installation requirements or conductor materials.

Sheath Type Variants

DesignationSheath MaterialFire PerformanceTypical Application
N2XS(FL)HLSZH (Zero Halogen)Low smoke, flame retardant, CPR compliantInternal/external, buildings, tunnels
N2XS(FL)YPVCStandard flame retardantExternal only, direct burial
N2XS(FL)2YPE/HDPEStandard, UV resistantExternal, high UV exposure areas

Waterblocking Variants

DesignationWaterblockingProtection LevelRecommended For
N2XSHNoneStandard sheath onlyDry indoor installations
N2XS(F)HLongitudinal onlyPrevents axial water propagationDucts with occasional moisture
N2XS(FL)HLongitudinal + RadialComplete water barrierFlooded ducts, water table burial, critical installations

Conductor Type Variants

Copper VersionAluminium VersionSize ComparisonWeight Comparison
N2XS(FL)HNA2XS(FL)HCu ~35% smaller ODAl ~50% lighter
N2XS(F)HNA2XS(F)HFor equivalent currentFor equivalent current
N2XSHNA2XSHCu preferred for limited spaceAl preferred for long runs