Что такое ÖLFLEX® FIRE 6387 MC: инженерный анализ огнестойкого многожильного силового кабеля 0.6/1 kV
ÖLFLEX® FIRE 6387 MC — это fire resistant multicore power cable с номинальным напряжением U0/U 600/1000 V. Кабель специально разработан для wiring applications в critical life safety systems общественных и промышленных зданий, включая airports, hotels, hospitals, subways, train stations, building management systems, emergency lighting, standby power supplies, lifts and elevators. Конструкция включает stranded plain annealed copper wire, mica based fire resistance tape, XLPE insulation and LSHF outer sheath. Цвет кабеля — orange.
Definition and application range
1. Что такое ÖLFLEX® FIRE 6387 MC?
ÖLFLEX® FIRE 6387 MC — это многожильный огнестойкий силовой кабель низкого напряжения 0.6/1 kV. Его основная задача — питание и подключение цепей, связанных с critical life safety systems, где требуется сочетание fire resistance, flame retardance, halogen-free behavior, low smoke density and practical multicore installation.
В отличие от single-core исполнения SC, версия MC объединяет несколько жил в одном кабеле. Это удобно для цепей building management systems, emergency lighting, standby power supplies, lifts and elevators, а также для plant engineering, industrial machinery and power station applications.
Technical thesis
Инженерный тезис: ÖLFLEX® FIRE 6387 MC — это multicore fire resistant low voltage power cable с stranded plain annealed copper conductors, mica based fire resistance tape, XLPE insulation, LSHF outer sheath, orange colour, BS 6387 Cat. CWZ fire test certification, IEC 60332-3-22 Cat. A approval, 600/1000 V nominal voltage, 10×D minimum bending radius and -30°C to +90°C temperature range.
1.1 Application profile decoded
| Application dimension | Datasheet wording | Engineering meaning |
|---|---|---|
| Main product identity | Fire resistant cables; multicore power cable, 0.6/1 kV | Огнестойкий многожильный силовой кабель низкого напряжения. |
| Critical systems | Wiring applications in critical life safety system | Для цепей, связанных с безопасностью людей и аварийной инфраструктурой. |
| Public buildings | Airports, hotels, hospitals, subways, train stations | Подходит для объектов с высокой плотностью людей и строгими требованиями безопасности. |
| Building systems | Building management systems, emergency lightings, standby power supplies | Используется в инженерных системах зданий и резервном электропитании. |
| Vertical transport | Lifts and elevators | Применяется в цепях лифтового и эвакуационно важного оборудования. |
| Industrial use | Plant engineering and construction, industrial machinery, power station | Подходит для промышленного строительства, машин и энергетических объектов. |
Standards and fire performance
2. Нормативная база: BS 6387 Cat. CWZ, IEC 60332, IEC 60754 and IEC 61034
ÖLFLEX® FIRE 6387 MC сертифицирован по fire test to BS 6387 Cat. CWZ. Также указано approval to IEC 60332-3-22 Cat. A. Для систем безопасности зданий важны дополнительные характеристики: flame retardance according to IEC 60332-1-2 and IEC 60332-3-22, halogen free according to IEC 60754-1, acid and corrosive gases according to IEC 60754-2 and smoke density test according to IEC 61034.
| Reference / classification | Provided statement | Engineering interpretation |
|---|---|---|
| BS 6387 Cat. CWZ | Fire test certified to BS 6387 Cat. CWZ | Кабель заявлен как прошедший fire resistance test по категории CWZ. |
| IEC 60332-3-22 Cat. A | Approved to IEC 60332-3-22 Cat. A | Flame retardant behavior для групповой прокладки категории A. |
| IEC 60332-1-2 | Flame retardant acc. to IEC 60332-1-2 | Проверка flame retardant behavior для одиночного кабеля. |
| IEC 60754-1 | Halogen free acc. to IEC 60754-1 | Низкий риск выделения галогенсодержащих газов при горении. |
| IEC 60754-2 | Acid and corrosive gases acc. to IEC 60754-2 | Оценка кислотности и коррозионности газов при пожаре. |
| IEC 61034 | Smoke density test acc. to IEC 61034 | Проверка дымообразования, важная для эвакуационных путей. |
| ETIM 5.0 | Class-Description: Low voltage power cable; Class-ID: EC000057 | Классифицируется как low voltage power cable. |
| IEC 60228 Class 2 | Conductor stranding acc. to IEC 60228 Cl. 2 | Многопроволочная медная жила класса 2 для стационарной силовой прокладки. |
Technical data
3. Технические параметры ÖLFLEX® FIRE 6387 MC
| Parameter | Value from supplied data | Engineering interpretation |
|---|---|---|
| Product type | Fire resistant multicore power cable | Многожильный силовой кабель для ответственных цепей. |
| Nominal voltage | U0/U: 600/1000 V | Низковольтный силовой кабель класса 0.6/1 kV. |
| Conductor | Stranded plain annealed copper wire | Многопроволочная мягкая медная жила. |
| Conductor stranding | IEC 60228 Class 2 | Класс 2 для стационарной силовой проводки. |
| Fire resistance layer | Mica based fire resistance tape | Слюдяная лента является ключевым слоем огнестойкой конструкции. |
| Insulation | XLPE insulation | Сшитый полиэтилен как изоляционный материал жил. |
| Outer sheath | LSHF outer sheath | Безгалогенная малодымная наружная оболочка. |
| Colour | Orange | Оранжевый цвет визуально выделяет fire resistant cable route. |
| Minimum bending radius | 10 × cable diameter | Монтаж должен учитывать минимальный радиус изгиба. |
| Temperature range | -30°C to +90°C | Рабочий температурный диапазон кабеля. |
Construction analysis
4. Конструкция: copper conductor, mica tape, XLPE insulation and LSHF sheath
Конструкция ÖLFLEX® FIRE 6387 MC ориентирована на fire resistance, flame retardance, halogen-free behavior and low smoke density. Внутреннюю электрическую часть формируют stranded plain annealed copper conductors. Поверх жил применяется mica based fire resistance tape. Далее используется XLPE insulation, а внешнюю защиту обеспечивает LSHF outer sheath. Наружный цвет кабеля — orange.
SC versus MC
5. ÖLFLEX® FIRE 6387 SC и MC: ключевое различие
ÖLFLEX® FIRE 6387 SC — это single-core power cable, тогда как ÖLFLEX® FIRE 6387 MC — multicore power cable. Обе версии относятся к fire resistant cable family 0.6/1 kV и имеют BS 6387 Cat. CWZ fire test certification. При этом MC-версия использует XLPE insulation and LSHF outer sheath и предназначена для случаев, когда несколько силовых жил удобнее объединить в одном кабеле.
| Comparison item | FIRE 6387 SC | FIRE 6387 MC | Engineering meaning |
|---|---|---|---|
| Cable type | Single-core power cable | Multicore power cable | SC — отдельная жила; MC — несколько жил в одном кабеле. |
| Nominal voltage | 600/1000 V | 600/1000 V | Обе версии являются low voltage power cable 0.6/1 kV. |
| Fire test | BS 6387 Cat. CWZ | BS 6387 Cat. CWZ | Обе версии заявлены как fire test certified. |
| Insulation / sheath concept | LSHF insulation | XLPE insulation + LSHF outer sheath | MC имеет отдельную изоляцию жил и общую LSHF оболочку. |
| Use case | Single-core routing and feeder arrangements | Multicore routing for combined circuits | Выбор зависит от схемы прокладки, количества жил и проектной спецификации. |
Product size table
6. Таблица типоразмеров ÖLFLEX® FIRE 6387 MC
Линейка включает 2-core, 3-core, 4-core and 5-core versions с сечениями от 1.5 mm² до 25 mm². Все значения наружного диаметра, copper index and weight приведены как номинальные значения из предоставленной таблицы.
| Article number | Number of cores and mm² per conductor | Outer diameter mm | Copper index kg/km | Weight kg/km | Engineering reading |
|---|---|---|---|---|---|
| 3806521 | 2 X 1.5 | 10.0 | 28.8 | 126 | Two-core 1.5 mm² fire resistant multicore cable for compact safety circuits. |
| 3806522 | 2 X 2.5 | 10.9 | 48.0 | 160 | Two-core 2.5 mm² cable for emergency lighting and building safety wiring. |
| 3806523 | 2 X 4 | 12.3 | 76.8 | 218 | Two-core 4 mm² fire resistant cable for higher-load circuits. |
| 3806524 | 2 X 6 | 13.6 | 115.2 | 285 | Two-core 6 mm² multicore cable for standby power and plant wiring. |
| 3806525 | 2 X 10 | 15.5 | 192.0 | 404 | Two-core 10 mm² low-voltage fire resistant power cable. |
| 3806526 | 2 X 16 | 17.8 | 307.2 | 573 | Two-core 16 mm² cable for heavier safety-related power circuits. |
| 3806527 | 2 X 25 | 21.4 | 480.0 | 852 | Two-core 25 mm² largest listed 2-core FIRE 6387 MC format. |
| 3806531 | 3 X 1.5 | 10.7 | 43.2 | 151 | Three-core 1.5 mm² fire resistant cable for compact multicore wiring. |
| 3806532 | 3 X 2.5 | 11.6 | 72.0 | 195 | Three-core 2.5 mm² cable for building safety and emergency power circuits. |
| 3806533 | 3 X 4 | 13.2 | 115.2 | 270 | Three-core 4 mm² multicore power cable for medium-load circuits. |
| 3806534 | 3 X 6 | 14.5 | 172.8 | 359 | Three-core 6 mm² cable for standby power and industrial wiring. |
| 3806535 | 3 X 10 | 16.6 | 288.0 | 520 | Three-core 10 mm² fire resistant low-voltage power cable. |
| 3806536 | 3 X 16 | 19.1 | 460.8 | 748 | Three-core 16 mm² cable for substantial safety-related power loads. |
| 3806537 | 3 X 25 | 23.0 | 720.0 | 1,120 | Three-core 25 mm² largest listed 3-core FIRE 6387 MC format. |
| 3806541 | 4 X 1.5 | 11.7 | 57.6 | 181 | Four-core 1.5 mm² fire resistant multicore cable for small control-power routes. |
| 3806542 | 4 X 2.5 | 12.8 | 96.0 | 236 | Four-core 2.5 mm² cable for emergency and building management circuits. |
| 3806543 | 4 X 4 | 14.5 | 153.6 | 332 | Four-core 4 mm² multicore cable for medium building safety loads. |
| 3806544 | 4 X 6 | 16.0 | 230.4 | 445 | Four-core 6 mm² fire resistant cable for standby supply circuits. |
| 3806545 | 4 X 10 | 18.4 | 384.0 | 650 | Four-core 10 mm² low-voltage multicore power cable. |
| 3806546 | 4 X 16 | 21.1 | 614.4 | 942 | Four-core 16 mm² cable for heavier emergency power distribution. |
| 3806547 | 4 X 25 | 25.4 | 960.0 | 1,416 | Four-core 25 mm² largest listed 4-core FIRE 6387 MC format. |
| 3806551 | 5 X 1.5 | 12.8 | 72.0 | 215 | Five-core 1.5 mm² fire resistant cable for compact multicore safety wiring. |
| 3806552 | 5 X 2.5 | 14.1 | 120.0 | 283 | Five-core 2.5 mm² cable for building systems and emergency circuits. |
| 3806553 | 5 X 4 | 16.0 | 192.0 | 399 | Five-core 4 mm² multicore cable for medium-load safety power routes. |
| 3806554 | 5 X 6 | 17.7 | 288.0 | 538 | Five-core 6 mm² fire resistant power cable for standby supply wiring. |
| 3806555 | 5 X 10 | 20.3 | 480.0 | 790 | Five-core 10 mm² cable for higher-capacity emergency power systems. |
| 3806556 | 5 X 16 | 23.3 | 768.0 | 1,149 | Five-core 16 mm² multicore cable for substantial low-voltage power routes. |
| 3806557 | 5 X 25 | 28.1 | 1,200.0 | 1,732 | Five-core 25 mm² largest listed FIRE 6387 MC format. |
Engineering interpretation
7. Что делает ÖLFLEX® FIRE 6387 MC технически важным?
Главная инженерная ценность ÖLFLEX® FIRE 6387 MC состоит в сочетании multicore low-voltage power cable construction, fire resistance, XLPE insulation and LSHF outer sheath. Кабель предназначен для ситуаций, где важны не только электрическая нагрузка и удобство многожильной прокладки, но и поведение кабеля при пожаре: flame retardance, halogen-free gases, reduced smoke density and fire test certification.
| Technical feature | Why it matters | Practical engineering value |
|---|---|---|
| BS 6387 Cat. CWZ | Подтверждает fire test certification. | Используется для critical life safety wiring applications. |
| Mica based fire resistance tape | Ключевой слой огнестойкой конструкции. | Повышает устойчивость кабеля при пожарном воздействии. |
| XLPE insulation | Электрическая изоляция жил в многожильной силовой конструкции. | Поддерживает надежность низковольтной power cable system. |
| LSHF outer sheath | Halogen free and smoke density performance. | Важна для общественных зданий, эвакуации и критического оборудования. |
| IEC 60332-3-22 Cat. A | Flame retardant behavior for grouped cable installation. | Подходит для кабельных трасс с групповой прокладкой. |
| 0.6/1 kV rating | Low voltage power cable capability. | Используется для аварийного освещения, standby power and building systems. |
| Orange colour | Visual identification. | Облегчает различение fire resistant circuits during installation and maintenance. |
Selection note
При выборе ÖLFLEX® FIRE 6387 MC важно согласовать number of cores, conductor cross-section, current load, voltage drop, route length, installation method, ambient temperature, bending radius, fire performance requirement and building safety specification. Для всех размеров следует учитывать minimum bending radius 10× cable diameter.
Engineer FAQ
8. Частые инженерные вопросы
Вопрос 1 — Что такое ÖLFLEX® FIRE 6387 MC?
Ответ: Это fire resistant multicore low voltage power cable с номинальным напряжением U0/U 600/1000 V, предназначенный для critical life safety systems and emergency power wiring.
Вопрос 2 — Какой стандарт огнестойкости указан?
Ответ: Кабель fire test certified to BS 6387 Cat. CWZ. Также указан approval to IEC 60332-3-22 Cat. A.
Вопрос 3 — Является ли кабель безгалогенным?
Ответ: Да. В данных указано halogen free according to IEC 60754-1, acid and corrosive gases according to IEC 60754-2 and smoke density test according to IEC 61034.
Вопрос 4 — Где применяется этот кабель?
Ответ: В airports, hotels, hospitals, subways, train stations, building management systems, emergency lighting, standby power supplies, lifts, elevators, plant engineering, industrial machinery and power stations.
Вопрос 5 — Какой материал используется для огнестойкости?
Ответ: В конструкции используется mica based fire resistance tape вместе со stranded plain annealed copper wire.
Вопрос 6 — Какая изоляция используется в MC версии?
Ответ: В ÖLFLEX® FIRE 6387 MC используется XLPE insulation и LSHF outer sheath.
Вопрос 7 — Какой цвет кабеля?
Ответ: Цвет кабеля — orange.
Вопрос 8 — Какой температурный диапазон?
Ответ: Temperature range составляет -30°C to +90°C.
Вопрос 9 — Какой минимальный радиус изгиба?
Ответ: Minimum bending radius is 10 × cable diameter.
Engineering View
ÖLFLEX® FIRE 6387 MC is a fire resistant multicore 0.6/1 kV low voltage power cable for critical life safety systems in public and industrial buildings. Its construction includes stranded plain annealed copper wire according to IEC 60228 Class 2, mica based fire resistance tape, XLPE insulation and LSHF outer sheath in orange colour. The cable is fire test certified to BS 6387 Cat. CWZ, approved to IEC 60332-3-22 Cat. A, flame retardant according to IEC 60332-1-2 and IEC 60332-3-22, halogen free according to IEC 60754-1, tested for acid and corrosive gases according to IEC 60754-2 and smoke density according to IEC 61034. It is suitable for building management systems, emergency lighting, standby power supplies, lifts and elevators, airports, hotels, hospitals, subways, train stations, plant engineering, industrial machinery and power station applications. Engineering selection should verify number of cores, conductor cross-section, load current, voltage drop, installation route, bending radius, fire performance requirement and project safety specification.